Plan Review Details - Permit 02030610
| Plan Review Stops For Permit 02030610 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-03-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-03-19 |
Time |
15:55 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-25 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 02030610 | | | 225 DYER RD | | | | | | PLAN REVIEW: PLANS SHALL BE REVIEWED | | | UNDER THE 2001 FLORIDA BUILDING CODE. | | | | | | 1) THE DESIGNER OF RECORD DREW AND INDI- | | | CATES THE PLANS TO BE DESIGNED TO THE | | | 1997 STANDARD BUILDING CODE. TO HAVE THE | | | PLANS REVIEWED TO THE 1997 STANDARD | | | BUILDING CODE THEY WOULD TO HAVE BEEN | | | SUBMITTED TO THE CITY BEFORE MARCH 1, | | | 2002. PLANS SUBMITTED AFTER THAT DATE | | | ARE TO BE DESIGNED TO THE 2001 FLORIDA | | | CODE. THE DESIGN PROFESSIONAL SUBMITTED | | | A DESIGN CERTIFICATION FOR CODE COMPLIAN | | | CE UNDER THE 1997 STANDARD BUILDING CODE | | | FL BUILD CODE 1606.1.7 INFORMATION | | | ON DRAWINGS, TO BE ON ACTUAL DRAWING. | | | | | | FL BUILD 2001 1005.4.1 EVERY SLEEPING | | | ROOM LOCATED ON THE FIRST, SECOND OR | | | THIRD STORY OF A GROUP "R" OCCUPANCY | | | SHALL HAVE ONE EXTERIOR EMERGENCY ESCAPE | | | AND RESCUE WINDOW. | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | 659-8096 X 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2002-03-18 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-03-18 |
Time |
07:51 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-03-18 |
Time |
07:34 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-03-19 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-03-18 |
Time |
07:51 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2002-03-19 |
Time |
15:42 |
Sent To |
B |
|
| Notes |
| 2002-03-19 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | 1) PER FBC-PLUMBING 2001 TABLE 403.1 | | | 1 AUTOMATIC CLOTHS WASHER CONNECTION IS | | | REQUIRED. PLEASE INDICATE WHERE THIS IS | | | SINCE IT WILL BE REMOVED FOR W/C. | | | 2) SHT 1/2 PLUMBING RISER-TUB NOT VENTED | | | PLEASE CHANGE RISER DIAGRAM TO SHOW PRO- | | | PER VENTING FOR TUB | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2002-03-15 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-03-15 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|