Plan Review Details - Permit 02030594
Plan Review Stops For Permit 02030594
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-04-15 Cont ID  
Sent By rbrown Date 2002-04-15 Time 23:58 Rev Time 0.00
Received By rbrown Date 2002-04-15 Time 23:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-05 Cont ID  
Sent By rbrown Date 2002-04-05 Time 14:48 Rev Time 0.00
Received By rbrown Date 2002-04-05 Time 14:47 Sent To  
Notes
2002-04-05 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) FBC 1004.1.2NUMBER AND ARRANGEMENT
 OF EXITS.EVERY ROOM OR TENANT SPACE IN
 WHICH THE TRAVEL DISTANCE FROM THE MOST
 REMOTE POINT TO THE EXIT ACCESS EXCEEDS
 75 FEET SHALL HAVE NOT LESS THAN TWO
 EGRESS DOORS.THE TRAVEL DISTANCE FROM
 THE CORNER OF OFFICE 1 IS ALREADY CLOSE
 TO 75 FEET WITHOUT TAKING INTO ACCOUNT
 ANY FURNITURE OR OTHER OBSTRUCTIONS.
 SUBMIT FURNITURE PLANS FOR OFFICE 1,
 'WORK AREA' AND RECEPTION SHOWING THAT
 THE TRAVEL DISTANCE FROM THE CORNER OF
 OFFICE 1 TO THE TENANT EXIT ACCESS DOOR
 DOES NOT EXCEED 75 FEET.NOTE THAT IF
 TWO EXIT ACCESS DOORS ARE REQUIRED, THEY
 MUST BE SEPARATED BY A DISTANCE EQUAL TO
 NOT LESS THAN 1/2 OF THE MAXIMUM OVERALL
 DIAGONAL OF THE TENANT SPACE.
  
 2) FBC 2405.2 THE SIDE LIGHT GLAZING IS
 IN A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-12 Cont ID  
Sent By dpalmer Date 2002-03-12 Time 16:56 Rev Time 0.00
Received By dpalmer Date 2002-03-12 Time 16:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-03-28 Cont ID  
Sent By mcarsill Date 2002-03-28 Time 10:27 Rev Time 0.00
Received By mcarsill Date 2002-03-28 Time 10:27 Sent To  
Notes
2002-03-28 00:00:00A LETTER WAS RECEIVED ON MARCH 27, 2002
 REGARDING FIRE COMMENTS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-03-06 Cont ID  
Sent By mcarsill Date 2002-03-06 Time 15:50 Rev Time 0.00
Received By mcarsill Date 2002-03-06 Time 15:50 Sent To  
Notes
2002-03-06 00:00:00A) EMERGENCY LIGHT IN OFFICE #8 SHOULD
 BE RELOCATED TO THE REAR HALLWAY NEAR
 SERVER FILING ROOM.
 B) THE NEW EXIT SIGN NEAR OFFICE #3
 SHOULD BE RELOCATED NEAR OFFICE #1&2.
 C) IS THE EXISTING SPACE FIRE SPRINKLER
 PROTECTED?
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096 EXT-8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-04-12 Cont ID  
Sent By pkrauss Date 2002-04-12 Time 10:49 Rev Time 0.35
Received By pkrauss Date 2002-04-12 Time 10:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-03-26 Cont ID  
Sent By pkrauss Date 2002-03-26 Time 12:21 Rev Time 0.25
Received By pkrauss Date 2002-03-26 Time 12:18 Sent To  
Notes
2002-03-26 00:00:00 
 PLEASE PROVIDE THE FOLLOWING INFORMATION
  
  
 1.INDICATE SIZE OF "NEW" DUCTWORK
  
 2.RETURN AIR BALANCE REQUIRED AS PER
 2001 FBC, MECHANICAL 601.4.
  
 3.PROVIDE OUTSIDE AIR CALCULATION AS
 PER 2001 FBC, MECH. 403.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop Z ZONING
Rev No 1 Status N Date 2002-04-16 Cont ID  
Sent By rbrown Date 2002-04-16 Time 11:53 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
***NONE***