Plan Review Details - Permit 02030583
| Plan Review Stops For Permit 02030583 |
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2002-03-05 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-03-05 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-03-05 |
Time |
13:25 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FS |
|
| Rev No |
3 |
Status |
F |
Date |
2002-04-04 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-04-04 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-04-04 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2002-04-04 00:00:00 | A) PLEASE BE ADVISED THAT THE DRAWINGS | | | SUBMITTED ARE NOT REVISIONAL. THE | | | NEW EQUIPMENT AND DEVICES WERE NOT SHOWN | | | ON THE FIRE SPRINKLER PERMIT THAT WAS | | | APPROVED. PLEASE SUBMIT A PERMIT | | | APPLICATION FOR THE NEW DRAWINGS AFTER | | | THEY ARE CORRECTED. | | | B) THE FIRE HYDRANT SHOWN DOES NOT | | | MEET CITY STANDARDS. ALSO THE FIRE | | | HYDRANT VALVE SHOULD BE NOT MORE THAN | | | FOUR FEET FROM THE FIRE HYDRANT. | | | C) ALL NEW PIPING IS TO BE PRESSURE | | | TESTED AT 200 PSI FOR TWO HOURS. | | | D) THE NEW FIRE HYDRANT SHALL PROVIDE | | | AT LEAST 7' - 6" TO THE FRONT AND SIDES | | | AND 4' TO THE REAR. | | | E) A MINIMUM OF 7' - 6" IS TO BE | | | PROVIDED FOR FIRE PROTECTION APPLIANCES. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FS |
|
| Rev No |
2 |
Status |
P |
Date |
2002-03-08 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-03-08 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-03-08 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2002-03-08 00:00:00 | A) THE EXISTING FIRE DEPARTMENT | | | CONNECTION IS TO BE RELOCATED FROM | | | ITS PRESENT LOCATION, SINCE IT IS | | | LOCATED IN A FENCED LOCATION. THE | | | RELOCATED FIRE DEPARTMENT CONNECTION IS | | | TO BE LOCATED WITHIN 150 FEET OF A FIRE | | | HYDRANT. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FS |
|
| Rev No |
1 |
Status |
F |
Date |
2002-03-05 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-03-05 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-03-05 |
Time |
13:26 |
Sent To |
|
|
| Notes |
| 2002-03-05 00:00:00 | A) DRAWINGS REFLECT TWO DIFFERENT | | | WATER MAIN SIZES FOR EXISTING | | | CONDITIONS. | | | B) PLEASE PROVIDE CLARIFICATION OF | | | NUMBER SYMBOLS, 0-5 NOTED ON THE | | | DRAWINGS. | | | C) IS THE EXISTING FIRE LINE THAT | | | ENTERS THE BMW SHOWROOM LOCATED | | | UNDER THE FOUNDATION OR OVERHEAD. | | | D) PLEASE DEMONSTRATE THAT THE NEW | | | FIRE SPRINKLER HEAD INSTALLATION WILL | | | NOT MAX OUT EXISTING FIRE SPRINKLER | | | WATER SUPPLY. | | | E) PLEASE SHOW EXISTING FIRE HYDRANT | | | AND FIRE DEPARTMENT CONNECTIONS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2002-03-08 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-03-05 |
Time |
13:33 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-03-05 |
Time |
13:33 |
Sent To |
|
|
| Notes |
|
|
|