| Plan Review Stops For Permit 02030574 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2002-09-24 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-09-24 |
Time |
13:41 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-09-24 |
Time |
11:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
F |
Date |
2002-07-08 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-07-08 |
Time |
15:36 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-07-08 00:00:00 | THE INFORMATION ON THE "REDDI-FORM | | | SYSTEM" WAS PREVIOUSLY REQUESTED TWICE. | | | IT IS STILL ABSENT. | | | | | | THE PLANS RESUBMITTED 6/19/02 UNDER THE | | | SEAL AND SIGNATURE OF WALTER KARPINIA, | | | PE, DO NOT HAVE ENOUGH STRUCTURAL | | | DETAILS. | | | | | | SHEET A1 DECLARES ON THE FOUNDATION | | | PLANA - 10" POST AND BEAM STRUCTURAL | | | SYSTEM AS PER REDDI-FORM STAY IN PLACE | | | INSULATED WALL SYSTEM.SEE CHAPTER | | | 61G15-31 RESPONSIBILITY RULES OF | | | PROFESSIONAL ENGINEERS CONCERNING THE | | | DESIGN OF STRUCTURES.WITH REGARDS TO | | | DELEGATED DESIGN RESPONSIBILTY AND | | | GENERAL RESPONSIBILITY. | | | | | | THE THICKNESS OF THE CONCRETE AND THE | | | INSULATION IS NOT SHOWN.HOW IS THE | | | INSULATION ADDRESSED WHEN THE VARIOUS | | | STRUCTURAL COMPONENTS ARE ATTACHED TO | | | THE WALL? | | | | | | SHEET A2 DECLARES #5 VERT @ 12" OC AND | | | #5 HORIZ @ 48" OC.THERE ARE NO | | | DETAILS FOR CORNERS, FOUNDATION | | | CONNECTION, OR INTERUPTION AT OPENINGS. | | | | | | PROVIDE AN EVALUATION REPORT LISTING | | | FOR THE SIMPSON ICFLC/ICFLC-W LEDGER | | | BRACKETS. | | | | | | SHEET A3 WHAT IS THE EMBED DEPTH OF THE | | | 5/8" BOLT FOR THE LEDGER SUPPORTING THE | | | PORCH ROOF? | | | | | | THE BUILDING CODE IN EFFECT IS THE FBC | | | NOT SBCCI. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
|
Date |
2002-07-02 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-07-01 |
Time |
20:04 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-07-01 |
Time |
20:04 |
Sent To |
|
|
| Notes |
| 2002-07-01 00:00:00 | REVIEW TO BE CARRIED OUT BY H. PISKURA |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2002-05-21 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-05-21 |
Time |
14:48 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-05-21 00:00:00 | THE MINIMUM DESIGN PRESSURE ON SHEET | | | A-3DOES NOT MAKE SENSE. BOTH THE | | | INTERNAL PRESSURE COEFFICENT AND | | | COMPONENT DECLARE 16.1/ -30.2. | | | | | | | | | INFORMATION PREVIOUSLY REQUESTED FOR THE | | | "REDI FORMSYSTEM" HAS NOT BEEN | | | PROVIDED. IF THE WALLS ARE TO BE OF | | | REINFORCED CONCRETE PROVIDE A DESIGN BY | | | A STRUCTURAL ENGINEER DEMONSTRATING | | | COMPLIANCE WITH FBC 1901.1.2. | | | | | | THE SPECIFICATION FOR THE LAMINATED | | | LUMBER HAS NOT BEEN PROVIDED.SEE FBC | | | 2301.2.5. | | | | | | THE PLANS MUST BE REVIEWED BY THE COUNTY | | | FOR IMPACT FEES.CALL 233-5025 FOR | | | MORE INFORMATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-04-16 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-04-16 |
Time |
13:15 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-04-16 00:00:00 | BEFORE A PERMIT TO CONSTRUCT MAY BE | | | ISSUED IMPACT FEES MUST BE PAID TO THE | | | COUNTY FOR THE CITY, THE PERMIT PLANS | | | STAMPED BY THAT OFFICE AND A COPY OF | | | THE PAID RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION.CALL 233-5025 FOR MORE | | | INFORMATION. | | | | | | SHOW THE DESIGN WINDLOAD INFORMATION ON | | | THE PLANS IN ACCORDANCE WITH FBC 1606.1. | | | 7. | | | | | | PROVIDE INFORMATION ON THE "REDDI FORM" | | | WALL SYSTEM TO BE USED.IS THIS THE | | | "INSULATED CONCRETE FORM" DESCRIBED IN | | | FBC 1916?IF SO SEE THOSE LIMITATIONS. | | | | | | PLEASE PROVIDE A VALID SIGNED AND | | | SEALEDSURVEY. | | | | | | DECLARE THE USE OF THE LOFT. | | | | | | SHOW THE FINISH FLOOR ELEVATION. | | | | | | SPECIFY THE MINMUM GRADE AND SPECIES FOR | | | THE FRAMING LUMBER.SPECIFY THE DESIGN | | | INFORMATION FOR THE LAMINATED TIMBER. | | | | | | PROVIDE A LOADING ANALYSIS FOR THE | | | LUMBER AT THE 5/8" BOLT SHOWN SPACED | | | 36" O.C.CARRYING THE LOFT. | | | | | | SPECIFY THE APPROPRIATE ANCHOR FOR THE | | | LAMINATED LUMBER. | | | | | | PROVIDE A MORE SPECIFIC DETAIL FOR THE | | | CONNECTION OF THE 6X6 CYPRESS POSTS TO | | | THE BEAM AND FOOTING. | | | | | | SHOW THE CONNECTION FOR THE ROOF TRUSSES | | | TO THE WALL, OR THE LOCATION, NATURE, | | | DIRECTION AND MAGNITUDE OF THE FORCES | | | TO BE RESISTED. | | | | | | SHOW THE ATTIC VENTILATION AND ACCESS IN | | | ACCORDANCE WITH FBC 2309.6 AND 2309.7. | | | | | | PROVIDE ADDITIONAL DIMENSIONS TO LOCATE | | | THE FOOTING PADS ON THE SOUTH ELEVATION | | | FOR THE COVERED LOGGIA. | | | | | | PROVIDE CALCULATIONS FOR THE | | | CANTILEVERED 6X8 CYPRESS BEAMS AT THE | | | SOUTH WEST CORNER OF THE LOGGIA. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2002-04-04 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2002-04-04 |
Time |
11:42 |
Rev Time |
0.75 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-06-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-06-24 |
Time |
13:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-06-24 |
Time |
13:25 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2002-05-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-05-13 |
Time |
06:09 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-05-13 |
Time |
06:09 |
Sent To |
P |
|
| Notes |
| 2002-05-13 00:00:00 | ***************** UNSAT ************** | | | | | | 1)NOTE: PLEASE NOTE , NOW A RISER | | | DIAGRAM IS SUBMITTED AND SHOWS A NEW | | | 100A FEED FROM EXISTING PANEL?? | | | PLEASE NOTE, NO INFORMATION WAS GIVEN | | | FOR EXISTING PANEL, SIZE? PLEASE | | | SUBMIT A LOAD CALCUALTION, NOW THAT YOU | | | SHOW ADDING A NEW LOAD OF 98AMPS? | | | 215-5 | | | | | | 2)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR BETWEEN EXIST PANEL | | | AND DETACHED BLDG.250-32 SIZE PER 250- | | | 122. | | | | | | 3)NOTE: PLEASE NOTE PLANS NOW SHOW A NEW | | | PANEL, PLEASE SHOW AIC RATING FOR NEW | | | EQUIPMENT.110-9 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | '561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-03-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-15 |
Time |
05:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-03-15 |
Time |
05:16 |
Sent To |
P |
|
| Notes |
| 2002-03-15 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: | | | | | | | | | | | | | | | 2)NOTE: PLEASE NOTE PLAN FOR ELECTRICAL | | | IS NOT COMPLETE. PLEASE NOTE THAT NO | | | RISER DIAGRAM WAS SUBMITTED TO SHOW | | | WHERE/HOW THE NEW CABANA IS GETTING | | | ELECTRIC?? | | | PLEASE NOTE ,,PANEL(S), DISCONNECT, | | | GROUNDING, WIRE, CONDUIT SIZES ETC. | | | | | | 3)NOTE: PLEASE NOTE MISSING SMOKE | | | DETECTOR ON LOWER LEVEL OF STAIRS. | | | NFPA-72 2-2.1.1.1, 2-5.2.1.3. | | | | | | 4) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 5) NOTE: PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2`,6`,12` RULE PER 210-52. | | | MISSING FOR SECOND FLOOR GUARD RAIL. | | | THIS IS CONSIDERED WALL SPACE. (FLOOR | | | BOX). | | | | | | 6) PLEASE NOTE MISSING OUTLET FOR A/C | | | EQUIPMENT PER 210-63 OF NEC AND 309.2 | | | MECHANICAL CODE. | | | | | | 7) PLEASE NOTE EITHER MISSING EGRESS | | | LIGHTING AND/OR CLARIFY EGRESS LIGHTING | | | PER 210-70 OF THE NEC. | | | ATLEAST ONE LT FOR EGRESS TO OUTSIDE. | | | BOTH LOCATIONS SHOWN AS "J" BOX NOW. | | | | | | 8)NOTE: PLEASE NOTE OUTLETS IN GARAGE TO | | | BE SHOWN AS GFI/GFI PROTECTED. | | | | | | 9)NOTE: PLEASE NOTE THAT AREA CAN ALSO | | | BE USED AS SLEEPING/. PLEASE LIST ARC | | | FAULT PROTECTION PER 210-12. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-05-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-20 |
Time |
16:13 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-05-20 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2002-05-20 00:00:00 | NO MECH PLANS SUBMITTED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-03-27 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-05-18 |
Time |
09:18 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-03-27 |
Time |
16:24 |
Sent To |
|
|
| Notes |
| 2002-03-27 00:00:00 | | | | PROVISO: | | | | | | 2001 FBC, MECHANICAL 402.3.1 - ROOMS | | | CONTAINING BATHTUBS/SHOWERS SHALL BE | | | MECHANICALLY VENTILATED IN ACCORDANCE | | | WITH SECTION 403. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-06-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-06-27 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-06-27 |
Time |
13:12 |
Sent To |
|
|
| Notes |
| 2002-06-27 00:00:00 | RE-STAMPED PER KEN STEVENS/OK. | | | RESTAMP OK |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-05-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-05-18 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-05-18 |
Time |
09:16 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-03-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-05-13 |
Time |
06:09 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-03-27 |
Time |
15:57 |
Sent To |
|
|
| Notes |
| 2002-03-27 00:00:00 | DENIED | | | REFERENCE: FBC-2001 | | | | | | 1) SHT A-1 PLUMBING RISER DIAGRAM. EVERY | | | SANITARY DRAINAGE SYSTEM RECIEVING DIS- | | | CHARGE OF A WATER CLOSET SHALL HAVE A | | | MAIN VENT. SUCH VENT SHALL RUN UNDIMIN- | | | ISHED IN SIZE AND AS DIRECTLY AS POSSIB- | | | LE FROM DRAIN TO OPEN AIR ABOVE THE ROOF | | | SEC 903.1 | | | 2) SHT A-1 NOTES #1 DRAIN LINES 2-1/2" | | | AND SMALLER SHALL SLOPE AT 1/4" PER FOOT | | | MINIMUM. TABLE 704.1 | | | 3) SHT A-1 DISHWASHER NOT TRAPPED AS | | | SHOWN. DISHWASHER SHALL DRAIN INTO BAR | | | SINK TAILPIECE NOT THRU FLOOR INTO BLDG | | | DRAIN. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-03-14 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-03-14 |
Time |
12:05 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|