Plan Review Details - Permit 02030574
Plan Review Stops For Permit 02030574
Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2002-09-24 Cont ID  
Sent By hpiskura Date 2002-09-24 Time 13:41 Rev Time 0.00
Received By hpiskura Date 2002-09-24 Time 11:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status F Date 2002-07-08 Cont ID  
Sent By hpiskura Date 2002-07-08 Time 15:36 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-07-08 00:00:00THE INFORMATION ON THE "REDDI-FORM
 SYSTEM" WAS PREVIOUSLY REQUESTED TWICE.
 IT IS STILL ABSENT.
  
 THE PLANS RESUBMITTED 6/19/02 UNDER THE
 SEAL AND SIGNATURE OF WALTER KARPINIA,
 PE, DO NOT HAVE ENOUGH STRUCTURAL
 DETAILS.
  
 SHEET A1 DECLARES ON THE FOUNDATION
 PLANA - 10" POST AND BEAM STRUCTURAL
 SYSTEM AS PER REDDI-FORM STAY IN PLACE
 INSULATED WALL SYSTEM.SEE CHAPTER
 61G15-31 RESPONSIBILITY RULES OF
 PROFESSIONAL ENGINEERS CONCERNING THE
 DESIGN OF STRUCTURES.WITH REGARDS TO
 DELEGATED DESIGN RESPONSIBILTY AND
 GENERAL RESPONSIBILITY.
  
 THE THICKNESS OF THE CONCRETE AND THE
 INSULATION IS NOT SHOWN.HOW IS THE
 INSULATION ADDRESSED WHEN THE VARIOUS
 STRUCTURAL COMPONENTS ARE ATTACHED TO
 THE WALL?
  
 SHEET A2 DECLARES #5 VERT @ 12" OC AND
 #5 HORIZ @ 48" OC.THERE ARE NO
 DETAILS FOR CORNERS, FOUNDATION
 CONNECTION, OR INTERUPTION AT OPENINGS.
  
 PROVIDE AN EVALUATION REPORT LISTING
 FOR THE SIMPSON ICFLC/ICFLC-W LEDGER
 BRACKETS.
  
 SHEET A3 WHAT IS THE EMBED DEPTH OF THE
 5/8" BOLT FOR THE LEDGER SUPPORTING THE
 PORCH ROOF?
  
 THE BUILDING CODE IN EFFECT IS THE FBC
 NOT SBCCI.

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status   Date 2002-07-02 Cont ID  
Sent By rbrown Date 2002-07-01 Time 20:04 Rev Time 0.00
Received By rbrown Date 2002-07-01 Time 20:04 Sent To  
Notes
2002-07-01 00:00:00REVIEW TO BE CARRIED OUT BY H. PISKURA

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2002-05-21 Cont ID  
Sent By hpiskura Date 2002-05-21 Time 14:48 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-05-21 00:00:00THE MINIMUM DESIGN PRESSURE ON SHEET
 A-3DOES NOT MAKE SENSE. BOTH THE
 INTERNAL PRESSURE COEFFICENT AND
 COMPONENT DECLARE 16.1/ -30.2.
  
  
 INFORMATION PREVIOUSLY REQUESTED FOR THE
 "REDI FORMSYSTEM" HAS NOT BEEN
 PROVIDED. IF THE WALLS ARE TO BE OF
 REINFORCED CONCRETE PROVIDE A DESIGN BY
 A STRUCTURAL ENGINEER DEMONSTRATING
 COMPLIANCE WITH FBC 1901.1.2.
  
 THE SPECIFICATION FOR THE LAMINATED
 LUMBER HAS NOT BEEN PROVIDED.SEE FBC
 2301.2.5.
  
 THE PLANS MUST BE REVIEWED BY THE COUNTY
 FOR IMPACT FEES.CALL 233-5025 FOR
 MORE INFORMATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-04-16 Cont ID  
Sent By hpiskura Date 2002-04-16 Time 13:15 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-04-16 00:00:00BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO THE
 COUNTY FOR THE CITY, THE PERMIT PLANS
 STAMPED BY THAT OFFICE AND A COPY OF
 THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 233-5025 FOR MORE
 INFORMATION.
  
 SHOW THE DESIGN WINDLOAD INFORMATION ON
 THE PLANS IN ACCORDANCE WITH FBC 1606.1.
 7.
  
 PROVIDE INFORMATION ON THE "REDDI FORM"
 WALL SYSTEM TO BE USED.IS THIS THE
 "INSULATED CONCRETE FORM" DESCRIBED IN
 FBC 1916?IF SO SEE THOSE LIMITATIONS.
  
 PLEASE PROVIDE A VALID SIGNED AND
 SEALEDSURVEY.
  
 DECLARE THE USE OF THE LOFT.
  
 SHOW THE FINISH FLOOR ELEVATION.
  
 SPECIFY THE MINMUM GRADE AND SPECIES FOR
 THE FRAMING LUMBER.SPECIFY THE DESIGN
 INFORMATION FOR THE LAMINATED TIMBER.
  
 PROVIDE A LOADING ANALYSIS FOR THE
 LUMBER AT THE 5/8" BOLT SHOWN SPACED
 36" O.C.CARRYING THE LOFT.
  
 SPECIFY THE APPROPRIATE ANCHOR FOR THE
 LAMINATED LUMBER.
  
 PROVIDE A MORE SPECIFIC DETAIL FOR THE
 CONNECTION OF THE 6X6 CYPRESS POSTS TO
 THE BEAM AND FOOTING.
  
 SHOW THE CONNECTION FOR THE ROOF TRUSSES
 TO THE WALL, OR THE LOCATION, NATURE,
 DIRECTION AND MAGNITUDE OF THE FORCES
 TO BE RESISTED.
  
 SHOW THE ATTIC VENTILATION AND ACCESS IN
 ACCORDANCE WITH FBC 2309.6 AND 2309.7.
  
 PROVIDE ADDITIONAL DIMENSIONS TO LOCATE
 THE FOOTING PADS ON THE SOUTH ELEVATION
 FOR THE COVERED LOGGIA.
  
 PROVIDE CALCULATIONS FOR THE
 CANTILEVERED 6X8 CYPRESS BEAMS AT THE
 SOUTH WEST CORNER OF THE LOGGIA.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-04-04 Cont ID  
Sent By lsmith Date 2002-04-04 Time 11:42 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-06-24 Cont ID  
Sent By dpalmer Date 2002-06-24 Time 13:10 Rev Time 0.00
Received By dpalmer Date 2002-06-24 Time 13:25 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-05-13 Cont ID  
Sent By dpalmer Date 2002-05-13 Time 06:09 Rev Time 0.00
Received By dpalmer Date 2002-05-13 Time 06:09 Sent To P
Notes
2002-05-13 00:00:00***************** UNSAT **************
  
 1)NOTE: PLEASE NOTE , NOW A RISER
 DIAGRAM IS SUBMITTED AND SHOWS A NEW
 100A FEED FROM EXISTING PANEL??
 PLEASE NOTE, NO INFORMATION WAS GIVEN
 FOR EXISTING PANEL, SIZE? PLEASE
 SUBMIT A LOAD CALCUALTION, NOW THAT YOU
 SHOW ADDING A NEW LOAD OF 98AMPS?
 215-5
  
 2)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN EXIST PANEL
 AND DETACHED BLDG.250-32 SIZE PER 250-
 122.
  
 3)NOTE: PLEASE NOTE PLANS NOW SHOW A NEW
 PANEL, PLEASE SHOW AIC RATING FOR NEW
 EQUIPMENT.110-9
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 '561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-15 Cont ID  
Sent By dpalmer Date 2002-03-15 Time 05:27 Rev Time 0.00
Received By dpalmer Date 2002-03-15 Time 05:16 Sent To P
Notes
2002-03-15 00:00:00****************** UNSAT *************
  
 1)NOTE:
  
  
  
  
 2)NOTE: PLEASE NOTE PLAN FOR ELECTRICAL
 IS NOT COMPLETE. PLEASE NOTE THAT NO
 RISER DIAGRAM WAS SUBMITTED TO SHOW
 WHERE/HOW THE NEW CABANA IS GETTING
 ELECTRIC??
 PLEASE NOTE ,,PANEL(S), DISCONNECT,
 GROUNDING, WIRE, CONDUIT SIZES ETC.
  
 3)NOTE: PLEASE NOTE MISSING SMOKE
 DETECTOR ON LOWER LEVEL OF STAIRS.
 NFPA-72 2-2.1.1.1, 2-5.2.1.3.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 MISSING FOR SECOND FLOOR GUARD RAIL.
 THIS IS CONSIDERED WALL SPACE. (FLOOR
 BOX).
  
 6) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.2
 MECHANICAL CODE.
  
 7) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 ATLEAST ONE LT FOR EGRESS TO OUTSIDE.
 BOTH LOCATIONS SHOWN AS "J" BOX NOW.
  
 8)NOTE: PLEASE NOTE OUTLETS IN GARAGE TO
 BE SHOWN AS GFI/GFI PROTECTED.
  
 9)NOTE: PLEASE NOTE THAT AREA CAN ALSO
 BE USED AS SLEEPING/. PLEASE LIST ARC
 FAULT PROTECTION PER 210-12.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-05-20 Cont ID  
Sent By pkrauss Date 2002-05-20 Time 16:13 Rev Time 0.35
Received By pkrauss Date 2002-05-20 Time 16:13 Sent To  
Notes
2002-05-20 00:00:00NO MECH PLANS SUBMITTED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-03-27 Cont ID  
Sent By kstevens Date 2002-05-18 Time 09:18 Rev Time 0.40
Received By pkrauss Date 2002-03-27 Time 16:24 Sent To  
Notes
2002-03-27 00:00:00 
 PROVISO:
  
 2001 FBC, MECHANICAL 402.3.1 - ROOMS
 CONTAINING BATHTUBS/SHOWERS SHALL BE
 MECHANICALLY VENTILATED IN ACCORDANCE
 WITH SECTION 403.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-06-27 Cont ID  
Sent By dpalmer Date 2002-06-27 Time 13:26 Rev Time 0.00
Received By kstevens Date 2002-06-27 Time 13:12 Sent To  
Notes
2002-06-27 00:00:00RE-STAMPED PER KEN STEVENS/OK.
 RESTAMP OK

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-05-18 Cont ID  
Sent By kstevens Date 2002-05-18 Time 09:16 Rev Time 0.00
Received By kstevens Date 2002-05-18 Time 09:16 Sent To M
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-03-27 Cont ID  
Sent By dpalmer Date 2002-05-13 Time 06:09 Rev Time 0.00
Received By kstevens Date 2002-03-27 Time 15:57 Sent To  
Notes
2002-03-27 00:00:00DENIED
 REFERENCE: FBC-2001
  
 1) SHT A-1 PLUMBING RISER DIAGRAM. EVERY
 SANITARY DRAINAGE SYSTEM RECIEVING DIS-
 CHARGE OF A WATER CLOSET SHALL HAVE A
 MAIN VENT. SUCH VENT SHALL RUN UNDIMIN-
 ISHED IN SIZE AND AS DIRECTLY AS POSSIB-
 LE FROM DRAIN TO OPEN AIR ABOVE THE ROOF
 SEC 903.1
 2) SHT A-1 NOTES #1 DRAIN LINES 2-1/2"
 AND SMALLER SHALL SLOPE AT 1/4" PER FOOT
 MINIMUM. TABLE 704.1
 3) SHT A-1 DISHWASHER NOT TRAPPED AS
 SHOWN. DISHWASHER SHALL DRAIN INTO BAR
 SINK TAILPIECE NOT THRU FLOOR INTO BLDG
 DRAIN.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-14 Cont ID  
Sent By sgraham Date 2002-03-14 Time 12:05 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***