Plan Review Details - Permit 02030434
Plan Review Stops For Permit 02030434
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-05-15 Cont ID  
Sent By lsmith Date 2002-05-15 Time 13:39 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-04-23 Cont ID  
Sent By hpiskura Date 2002-04-23 Time 08:58 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-04-23 00:00:00DRAWING #0089 IS ILLEGIBLE AND THE
 COMPONENTS ARE NOT PROPERLY MARKED.
 REFER TO SBCCI REPORT 9857.NOTE ALSO
 THE "SPECIAL INSPECTION" REQUIRED BY
 THAT REPORT.
  
 THE REPORT FAXED TO ME 4/16/02 IS A POOR
 REPRODUCTION.THE DRAWING #98-156
 CITEE IN THE REPORT WAS NOT INCLUDED.
 ASSUMING DWG. #00-271 IS A VALID
 SUBSTITUTE, THE COMPONENTS AND
 FASTENERS ARE NOT PROPERLY SELECTED AND
 "SPECIAL INSPECTION" IS REQUIRED ALSO.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-03-29 Cont ID  
Sent By hpiskura Date 2002-03-29 Time 08:19 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-03-29 00:00:00THE CURRENCY LISTING FOR SBC REPORT
 #2045 HAS EXPIRED.PLEASE PROVIDE A
 CURRENT LISTING.
  
 REPORT #9857 IS MOSTLY ILLEGIBLE,
 PARTICLARLY THE DRAWING.PLEASE
 PROVIDE LEGIBLE INFORMATION WITH ALL OF
 THE COMPONENTS AND FASTENERS TO BE USED
 CLEARLY INDICATED.