Plan Review Details - Permit 02030430
| Plan Review Stops For Permit 02030430 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2002-06-21 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2002-06-21 |
Time |
12:37 |
Rev Time |
0.75 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2002-05-13 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-05-13 |
Time |
08:11 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-05-13 00:00:00 | WHICH SHUTTER TYPE WAS USED FOR THIS | | | INSTALLATION?ECONOMY OR RESIDENTIAL? | | | | | | THE SBCCI REPORT PROVIDED, #2127, | | | REQUIRES THAT THE FASTENER INSTALLATION | | | HAVE A "SPECIAL INSPECTION".SINCE THE | | | SHUTTERS HAVE BEEN INSTALLED WITHOUT | | | BENFIT OF A PERMIT, PROVIDE A WRITTEN | | | REPORT FROM THE SPECIAL INSPECTOR, | | | INCLUDING THE INSPECTOR'S | | | QUALIFICATIONS AS DEFINED IN SECTION | | | 5.2 OF THE SBCCI REPORT. | | | | | | REPORT # 2127 REFERENCES DWG #98-59 FOR | | | ECONOMY SHUTTERS AND #98-156 FOR | | | RESIDENTIAL SHUTTERS.NEITHER OF THESE | | | DRAWINGS HAVE BEEN PROVIDED IN | | | ACCORDANCE WITH THE REPORT. | | | | | | THE PRINTED SHEET TITLED "ACCORDIONS" IS | | | NOT COMPLETE IN ITS DESCRIPTION IF IT | | | IS INTENDED TO DEFINE THE COMPONENTS | | | USED. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-04-23 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-04-23 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-04-23 00:00:00 | SAME AS PREVIOUS COMMENT LIST, NO | | | CHANGE TO THE PLANS. | | | | | | SEE COMPANION PERMIT #02030434 FOR THOSE | | | COMMENTS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-03-29 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-03-29 |
Time |
08:38 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-29 00:00:00 | THE SBCCI REPORT # 2045 IS EXPIRED. THE | | | TILTECO DWG# 00-271 IS NOT THE DWG CITED | | | IN THE REPORT.PLEASE PROVIDE A | | | REPORTHAVING A CURRENT LISTING WITH THE | | | COMPONENTS AND FASTENERS TO BE USED | | | CLEARLY INDICATED. |
|
|
|