Plan Review Details - Permit 02030289
Plan Review Stops For Permit 02030289
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-05-07 Cont ID  
Sent By pkrauss Date 2002-03-19 Time 15:08 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-08 Cont ID  
Sent By btrobaug Date 2002-03-08 Time 13:49 Rev Time 0.00
Received By btrobaug Date 2002-03-08 Time 14:06 Sent To M
Notes
2002-03-08 00:00:00NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-03-19 Cont ID  
Sent By btrobaug Date 2002-03-08 Time 13:50 Rev Time 0.45
Received By pkrauss Date 2002-03-19 Time 14:44 Sent To B
Notes
2002-03-19 00:00:00 
 PROVISO:MECHANICAL PERMIT 02030289
  
 RETURN AIR SOFFIT SHALL COMPLY WITH 1997
 FLORIDA ENERGY CODE 610.1.ABC.3.6 -
  
 SOFFITS & WALLS SHALL NOT BE USED TO
 DELIVER AIR FROM OR RETURN AIR TO THE
 CONDITIONING SYSTEM UNLESS THEY CONTAIN
 AN AIR DUCT INSERT WHICH IS INSULATED
 IN ACCORDANCE WITH SECTION 610.1.ABC.2
 & CONSTRUCTED & SEALED IN ACCORDANCE
 WITH THE REQUIREMENTS OF SECTION
 610.1.ABC.3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop Z ZONING
Rev No 1 Status N Date 2002-03-01 Cont ID  
Sent By wlehnhar Date 2002-03-01 Time 18:01 Rev Time 0.10
Received By wlehnhar Date   Time   Sent To  
Notes
***NONE***