Plan Review Details - Permit 02030164
Plan Review Stops For Permit 02030164
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-04-15 Cont ID  
Sent By hpiskura Date 2002-04-15 Time 15:15 Rev Time 0.00
Received By hpiskura Date   Time   Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-03-19 Cont ID  
Sent By hpiskura Date 2002-03-19 Time 10:27 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-03-19 00:00:00THE LISTING AGENCY STAMP DECLARES A 130
 MPH WIND ZONE AND ASCE 7-98. THE CITY OF
 WEST PALM BEACH IS LOCATED IN AN 140
 MPH WIND ZONE.SEVERAL OF THE PAGES
 CITE THE 1997 SBC.PLEASE PROVIDE
 LISTED PLANS FOR 140 MPH WIND ZONE AND
 THE DCA LETTER OF LISTING RENEWAL.
  
 THE SURVEY SITE PLAN INDICATES THE
 FINISH FLOOR AT 21.60' AND THE BOTTOM
 OF THE HC RAMP AT 20.91'.HOW WILL THE
 18" CLEARANCE IN SECTION FD/1 BE
 MAINTAINED?
  
 WHAT PORTION OF THIS WORK IS INTENDED TO
 BE ACCOMPLISHED FOR THE $5000 PERMIT
 VALUATION?

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2002-04-19 Cont ID  
Sent By dpalmer Date 2002-04-19 Time 07:31 Rev Time 0.00
Received By dpalmer Date 2002-04-19 Time 07:31 Sent To  
Notes
2002-04-19 00:00:00*************** NOTE ****************
  
 PLEASE NOTE THAT THERE IS STILL NOTHING
 SUBMITTED FOR REVIEW. PLEASE NOTE THAT
 THE TRAILER DOES NOT GET AN ELECTRICAL
 REVIEW.
 PLEASE NOTE THAT THERE IS NO ELECTRICAL
 RISER DIAGRAM/HOOK UP FOR TRAILER
 SUBMITTED.
  
 PLEASE NOTE WHEN THE ELETCRICAL CONTR
 COMES IN TO PULL THEIR PERMIT, A RISER
 DIAGRAM WILL NEED TO BE SUBMITTED AT
 THAT TIME.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2002-03-12 Cont ID  
Sent By dpalmer Date 2002-03-12 Time 12:32 Rev Time 0.00
Received By dpalmer Date 2002-03-12 Time 12:32 Sent To  
Notes
2002-03-12 00:00:00************** NOTHING***************
  
 1)NOTE: PLEASE NOTE THAT NOTHING WAS
 SUBMITTED FOR REVIEW.
 PLEASE SUBMIT AN ELECTRICAL RISER
 DIAGRAM FOR TRAILER HOOK-UP.
 PLEASE ALSO SUBMIT WITH ELECTRICAL
 PERMIT APPLICATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2002-04-22 Cont ID  
Sent By nleiva Date 2002-04-22 Time 14:48 Rev Time 1.00
Received By nleiva Date   Time   Sent To  
Notes
2002-04-22 00:00:00THE WATER AND SEWER HAS BEEN SATISFIED H
 OWEVER THE DRIVEWAY WILL BE REQUIRED TO
 BE CONCRETE IF IT WILL REMAIN AS A PERMA
 NENT STRUCTURE, IF IT WILL BE TEMPORARY
 ASPHALT THEN THE DESIGN MUST BE PER CITY
 'S STANDARD DRIVEWAY APPROACH.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2002-03-05 Cont ID  
Sent By mamini Date 2002-03-05 Time 14:30 Rev Time 0.00
Received By mamini Date 2002-03-18 Time 15:32 Sent To  
Notes
2002-03-05 00:00:00FAILED :
 1. PLEASE SHOW WATER & SANITARY
 CONNECTIONS FOR THE PROPOSED SALES
 TRAILER, IF TEMPORARY WELL AND HOLDING
 TANKS ARE USED, THEN HEALTH DEPARTMENT'S
 PERMITS FOR BOTH WILL BE REQUIRED.
 2. PLEASE SPECIFY THICKNESS FOR ASPHALT,
 BASE AND SUB-GRADE.
 3. ALL OFF-STREET PARKING STALLS MUST BE
 PAINTED WITH DOUBLE 4" WHITE FOR REGULAR
 AND BLUE FOR H.C., MUST COMPLY WITH FL.
 ACCESSIBLITY CODE FOR BUILDING CONST.
 4. THE COST OF SITE/UTILITY WORKS AND
 LANDSCAPINGMUST BE INCLUDED IN VALUE
 AND AND PRMITTING FEES.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-04-17 Cont ID  
Sent By hpiskura Date 2002-04-15 Time 15:18 Rev Time 0.00
Received By mcarsill Date 2002-04-17 Time 11:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-04-02 Cont ID  
Sent By mcarsill Date 2002-04-02 Time 13:02 Rev Time 0.00
Received By mcarsill Date 2002-04-02 Time 13:02 Sent To  
Notes
2002-04-02 00:00:00A) PLEASE INDICATE IN WRITING HOW LONG
 THE SALES TRAILER WILL BE USED AT
 SUBJECT LOCATION.
 B) PLEASE INDICATE THE LOCATION OF
 THE NEAREST WET FIRE HYDRANT TO THE
 PROPOSED SALES TRAILER.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-03-26 Cont ID  
Sent By pkrauss Date 2002-03-26 Time 11:49 Rev Time 0.30
Received By pkrauss Date 2002-03-26 Time 11:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-04-24 Cont ID  
Sent By kstevens Date 2002-04-24 Time 10:23 Rev Time 0.00
Received By kstevens Date 2002-04-24 Time 10:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-03-18 Cont ID  
Sent By kstevens Date 2002-03-18 Time 16:41 Rev Time 0.50
Received By kstevens Date 2002-03-18 Time 16:41 Sent To  
Notes
2002-03-18 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) PLEASE SHOW WATER AND SEWER UTILITIES
 FOR SALES TRAILER.
 2) BACKFLOW REQUIRED ON WATER SERVICE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-11 Cont ID  
Sent By sgraham Date 2002-04-11 Time 09:40 Rev Time 0.25
Received By sgraham Date 2002-04-03 Time 10:16 Sent To  
Notes
***NONE***