Plan Review Details - Permit 02022361
Plan Review Stops For Permit 02022361
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-01-22 Cont ID  
Sent By rbrown Date 2003-01-22 Time 12:15 Rev Time 0.00
Received By rbrown Date 2003-01-22 Time 12:15 Sent To  
Notes
2003-01-22 00:00:00BUILDING REVISION SUBMITTAL 1-15-03 FOR
 REMEDIAL WORK TO EXISTING WINDOWS

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-01-15 Cont ID  
Sent By dpalmer Date 2003-01-15 Time 13:52 Rev Time 0.00
Received By rbrown Date 2003-01-15 Time 11:38 Sent To  
Notes
2003-01-15 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 REVISION SUBMITTED 1-6-03 FOR CHANGE OF
 FRENCH DOOR PRODUCT APPROVAL.
  
 --PROVISO--
 SHEET 5 OF 6 IS MISSING FROM THE
 SUBMITTED COPY.SUBMIT A COMPLETE COPY
 BEFORE BUCK INSPECTION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-04-26 Cont ID  
Sent By dpalmer Date 2003-01-06 Time 17:31 Rev Time 0.00
Received By rbrown Date 2002-04-26 Time 13:47 Sent To  
Notes
2002-04-26 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
  
 --PROVISO--
 SBC* 104.1.1A SEPARATE ROOFING PERMIT
 APPLICATION IS REQUIRED.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-05 Cont ID  
Sent By pkrauss Date 2002-04-04 Time 07:05 Rev Time 0.00
Received By rbrown Date 2002-04-05 Time 20:06 Sent To  
Notes
2002-04-05 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SHEET A1, AREA CALCULATIONS.THE
 TOTAL AREA FOR THE NEW COVERED PORCH AND
 NEW COVERED ENTRY SHOULD BE 371 SQFT
 (APPROX. 287 SQFT AND 84 SQFT
 RESPECTIVELY).REVIEW AND AMEND.
  
 4) THE SUBMITTED DESIGN CERTIFICATION
 SHEET REFERS TO SBC 1994 (SHOULD BE
 SBC 1997).THE INFORMATION ON THE SHEET
 SHALL BE STATED ON THE PLANS.A
 SEPARATE SHEET IS NOT REQUIRED.
  
 5) SBC* 104.1.1A SEPARATE ROOFING
 PERMIT APPLICATION IS REQUIRED.
  
 6) SBC* 104.2.5THE SUBMITTED SURVEY
 DRAWING IS NOT ADEQUATE FOR PUBLIC
 RECORD.IT IS A COPY OF COPY, THE NOTES
 ARE NOT LEGIBLE, THERE IS NO DISCERNABLE
 DATE AND IT IS NOT SEALED (REF. CH.
 472.025 FLORIDA STATUTES)
  
 7) SBC* 1606.4.2STORM PANEL SHUTTERS.
 THE PRODUCT APPROVAL NOTICE OF
 ACCEPTANCE IS MISSING THE ASSOCIATED
 DRAWING SHEETS REFERENCED ON SHEET 2OF3
 UNDER 'PRODUCT DESCRIPTION'
  
 8) SBC* 104.2.2SUBMIT TYPICAL DETAILS
 TO SHOW THE BASEPLATE HOLDING DOWN FOR
 THE STEEL COLUMNS AT THE COVERED PORCH,
 AND TO SHOW THE ANCHORING OF THE FILLED
 CELL COLUMNS TO THE FOUNDATION AT THE
 COVERED ENTRY.
  
 9) SBC 1804.1.3SHEET A1 TYPICAL WALL
 SECTION.THE BOTTOM OF THE FOUNDATION
 SHALL BE NO LESS THAN 12" BELOW FINISH
 GRADE.
  
 10) SBC* 104.2ANNOTATE SHEET A3 ROOF
 PLANS (AND SHEET A1 TYPICAL WALL
 SECTION) TO CLARIFY THAT THE SPECIFIED
 HANGERS, TIES, STRAPS AND STUD PLATE
 TIES ARE 'SIMPSON' REFERENCES.
  
 11) SBC 2309.6SHEET A2 REAR FLOOR PLAN
 THE ATTIC ACCESS SHALL BE NO LESS THAN
 22"X36"
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-08 Cont ID  
Sent By dpalmer Date 2002-03-08 Time 15:27 Rev Time 0.00
Received By dpalmer Date 2002-03-08 Time 15:27 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-01-15 Cont ID  
Sent By dpalmer Date 2003-01-15 Time 13:51 Rev Time 0.00
Received By dpalmer Date 2003-01-15 Time 13:51 Sent To B
Notes
2003-01-15 00:00:00TO ROBERT BROWN'S DESK.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-01-06 Cont ID  
Sent By dpalmer Date 2003-01-06 Time 17:30 Rev Time 0.00
Received By dpalmer Date 2003-01-06 Time 17:30 Sent To B
Notes
2003-01-06 00:00:00TO ROBERT BROWN'S DESK.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-12-06 Cont ID  
Sent By pkrauss Date 2002-12-06 Time 09:14 Rev Time 0.30
Received By pkrauss Date 2002-12-06 Time 08:22 Sent To  
Notes
2002-12-06 00:00:00MECH REV 02101205

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-04-25 Cont ID  
Sent By pkrauss Date 2002-04-25 Time 13:37 Rev Time 0.25
Received By pkrauss Date 2002-04-25 Time 13:37 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-04-04 Cont ID  
Sent By kstevens Date 2002-03-13 Time 10:41 Rev Time 0.35
Received By pkrauss Date 2002-03-14 Time 16:53 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-03-13 Cont ID  
Sent By kstevens Date 2002-03-13 Time 10:40 Rev Time 0.50
Received By kstevens Date 2002-03-13 Time 10:36 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-06 Cont ID  
Sent By gjoyce Date 2002-03-06 Time 11:49 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***