| 2002-04-05 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | SBC = STANDARD BUILDING CODE 1997 |
| | SBC*= STANDARD BUILD'G CODE (CITY AMEND) |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) SHEET A1, AREA CALCULATIONS.THE |
| | TOTAL AREA FOR THE NEW COVERED PORCH AND |
| | NEW COVERED ENTRY SHOULD BE 371 SQFT |
| | (APPROX. 287 SQFT AND 84 SQFT |
| | RESPECTIVELY).REVIEW AND AMEND. |
| | |
| | 4) THE SUBMITTED DESIGN CERTIFICATION |
| | SHEET REFERS TO SBC 1994 (SHOULD BE |
| | SBC 1997).THE INFORMATION ON THE SHEET |
| | SHALL BE STATED ON THE PLANS.A |
| | SEPARATE SHEET IS NOT REQUIRED. |
| | |
| | 5) SBC* 104.1.1A SEPARATE ROOFING |
| | PERMIT APPLICATION IS REQUIRED. |
| | |
| | 6) SBC* 104.2.5THE SUBMITTED SURVEY |
| | DRAWING IS NOT ADEQUATE FOR PUBLIC |
| | RECORD.IT IS A COPY OF COPY, THE NOTES |
| | ARE NOT LEGIBLE, THERE IS NO DISCERNABLE |
| | DATE AND IT IS NOT SEALED (REF. CH. |
| | 472.025 FLORIDA STATUTES) |
| | |
| | 7) SBC* 1606.4.2STORM PANEL SHUTTERS. |
| | THE PRODUCT APPROVAL NOTICE OF |
| | ACCEPTANCE IS MISSING THE ASSOCIATED |
| | DRAWING SHEETS REFERENCED ON SHEET 2OF3 |
| | UNDER 'PRODUCT DESCRIPTION' |
| | |
| | 8) SBC* 104.2.2SUBMIT TYPICAL DETAILS |
| | TO SHOW THE BASEPLATE HOLDING DOWN FOR |
| | THE STEEL COLUMNS AT THE COVERED PORCH, |
| | AND TO SHOW THE ANCHORING OF THE FILLED |
| | CELL COLUMNS TO THE FOUNDATION AT THE |
| | COVERED ENTRY. |
| | |
| | 9) SBC 1804.1.3SHEET A1 TYPICAL WALL |
| | SECTION.THE BOTTOM OF THE FOUNDATION |
| | SHALL BE NO LESS THAN 12" BELOW FINISH |
| | GRADE. |
| | |
| | 10) SBC* 104.2ANNOTATE SHEET A3 ROOF |
| | PLANS (AND SHEET A1 TYPICAL WALL |
| | SECTION) TO CLARIFY THAT THE SPECIFIED |
| | HANGERS, TIES, STRAPS AND STUD PLATE |
| | TIES ARE 'SIMPSON' REFERENCES. |
| | |
| | 11) SBC 2309.6SHEET A2 REAR FLOOR PLAN |
| | THE ATTIC ACCESS SHALL BE NO LESS THAN |
| | 22"X36" |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUERIES PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |