Plan Review Details - Permit 02022358
Plan Review Stops For Permit 02022358
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-12-20 Cont ID  
Sent By jwitmer Date 2002-12-20 Time 10:58 Rev Time 1.25
Received By jwitmer Date   Time   Sent To  
Notes
2002-12-20 00:00:00RESTAMP PLANS JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-11-27 Cont ID  
Sent By jwitmer Date 2002-11-27 Time 15:24 Rev Time 1.00
Received By jwitmer Date 2002-11-27 Time 15:24 Sent To  
Notes
2002-11-27 00:00:00REV 10-21-02JW

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-06-29 Cont ID  
Sent By jwitmer Date 2002-06-29 Time 14:52 Rev Time 1.75
Received By jwitmer Date 2002-06-29 Time 13:30 Sent To  
Notes
2002-06-29 00:00:00PROVISO: PROVIDE FACTORY BUILT BAR-B-Q
 MANUFACTURERS APPROVALJW

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-09 Cont ID  
Sent By jwitmer Date 2002-04-09 Time 10:01 Rev Time 3.00
Received By jwitmer Date 2002-04-09 Time 10:01 Sent To  
Notes
2002-04-09 00:00:00BUILDING PLAN REVIEW
 PERMIT# 02022358
 2717 SENECA CIRCLE
 CONT SHELTER CONST
 TEL: 687-3600
  
 SBC= 1997 STANDARD BUILDING CODE
 SBC*= AMENDMENTS STANDARD BUILDING CODE
  
 THIS REVIEW WAS COMPLETED USING THE 1997
 STANDARD BUILDING CODE, THE PLANS DO NOT
 INDICATE AS TO WHICH CODE THEY ARE DE-
 SIGNED TOO? PLANS SUBMITTED BETWEEN JAN
 & FEB 2002 MAY BE DESIGNED & SUBMITTED
 UNDER EITHER THE 1997 SBC OR 2001 FL
 CODE.
  
 1) SBC 104.2.2* ADDITIONAL INFORMATION
 SUBMIT A SURVEY LESS THAN A YEAR OLD.
 2) SBC 1804.2.7.2(3) MISSING SOILS
 REPORT AND THE MINIMUM SAFE BEARING
 VALUE.
 3) SBC 1606, MISSING THE DESIGN PARAM-
 ETERS & ASSUMPTIONS,ALSO MISSING INFO
 WIND PRESSURE ON ALL OPENINGS BOTH
 POSSITIVE AND NEGATIVE PRESSURES IN-
 CLUDING END ZONES!
 4) PRODUCT APPROVALS:
 GARAGE DOOR, OVERHEAD, WHICH MODEL #
 DOOR SHALL BE USED FOR 9' & 16' OPENINGS
 GARAGE SWING DOOR, EXTERIOR MISSING
 REPORT. MISING REPORT ON GLASS BLOCK,
 ALSO WHAT WALL THICKNESS IS THE GLASS
 BLOCK GOING TO BE?
 5) SBC 2808 BARBECUES-FACTORY BUILT,
 SHALL BE AN APPROVED TYPE AND SHALL BE
 INSTALLED IN ACCORDANCE WITH THE MANU-
 FACTURES INSTRUCTION.
 6) TRUSS CONNECTION VALUES FOR SIMPSON
 & USP DO NOT CORRESPOND WITH THE CURRENT
 2001 CATALOGS. THE ULT. AVERAGE UPLIFT
 SHALL NOT BE USED AS THIS IS THE AVERAGE
 OF RATE FOR FAILURE. THE 160% UPIFT FOR
 YELLOW PINE SHALL BE USED.
 SIMPON HUM412/ HUCM 412 NOT IN CATOLOG?
 SIMPON HGT-2 18,665 CATALOG @160% 10980
 USP HC-10 1472/1543 CAT 1325/1542
 USP SHA-6 10,560 CATALOG 2 PLY 3745
 CATALOG 3 PLY 5615
 SHA-6T CATALOG 7550
 7) MISSING GRAVITY LOADS ON GIRDERS
 8) SHEET A-8 2 STORY DETAIL QUESTION,
 CONTINEOUS LOAD PATH, THE DETAIL INDI-
 CATES THE TIE DOWN OF THE FLOOR TRUSSES
 USING A USP STRAP. THE SAME DETAIL INDI-
 CATES THE TIE DOWN OF THE BOTTOM OF STUD
 TO PLATE AND ANOTHER STRAP ENVERTED TIE-
 ING THE PLATE TO RIM JOIST? IS THIS TRUE
 LY A 1 1/2 X 24" RIM JOIST? THERE IS NO
 TIE FROM THE RIM JOIST TO BOND BEAM!
 9) SHEET A-8 /A-9 DISCREPANCY SHEET A-8
 TYPICAL SECTION INDICATES A (2) COURSE
 BOND BEAM VS. SHEET A-9 "NOTE" WHERE CON
 CRETE IS OVER CBS WALLS PROVIDE A
 8"X12" FORMED / PORED CONCRETE BEAM W
 4@5'S, MISSING INFORMATION HOOPS OVER
 OPENINGS?
 10) SHEET A-9 STAIR DETAIL: SBC 1007.3.1
 2R+1T=>24" BUT <25".
 11) CONTRACTOR SHALL SUBMIT PLANS TO
 PB COUNTY FOR ASSESSMENT FOR IMPACT FEES
 BUILDING PLAN REVIW
 JIM WITMER
 (561)659-8096X8412

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-07-25 Cont ID  
Sent By alange Date 2003-07-25 Time 09:35 Rev Time 0.50
Received By btrobaug Date 2003-07-24 Time 12:04 Sent To P
Notes
2003-07-25 00:00:00PROVISO
 ~~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 THE RISER DIAGRAM SHOWS TWO MAIN
 BREAKER PANELS.THE REVISION ON SHEET
 A-10 INDICATES ADDING DISCONNECTS TO
 THE SERVICE,PLEASE SUBMIT A DRAWING
 REFLECTING ACTUAL CONDITIONS FOR REVIEW
 PRIOR TO OBTAINING A CO.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-12-16 Cont ID  
Sent By alange Date 2003-07-24 Time 11:35 Rev Time 0.50
Received By btrobaug Date 2002-12-16 Time 14:54 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-11-12 Cont ID  
Sent By btrobaug Date 2002-11-12 Time 15:34 Rev Time 0.50
Received By btrobaug Date 2002-11-12 Time 15:02 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-06-24 Cont ID  
Sent By btrobaug Date 2002-11-06 Time 16:34 Rev Time 0.00
Received By btrobaug Date 2002-06-24 Time 15:46 Sent To R
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-04-02 Cont ID  
Sent By dpalmer Date 2002-04-02 Time 06:33 Rev Time 0.00
Received By dpalmer Date 2002-04-02 Time 06:33 Sent To  
Notes
2002-04-02 00:00:00**************** UNSAT ***************
  
 1) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 PLEASE NOTE CLOSE PROXIMITY TO STAIRWAYS
 PER 2-5.2.1.3.
 MISSING TOP AND BOTTOM OF STAIRS AND IN
 DEN.
  
 2) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 3) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
 MISSING BLDG/FOOTER STEEL.
  
 4)NOTE: PLEASE CLARIFY LOCATIONS OF
 PANELS/ PLANS SHOW PANELS IN GARAGE,
 BUT DO NOT SHOW MAIN DISC`S? OR GUTTER
 LOCATION. PLEASE SHOW MAINS ON PLANS.
  
 5)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTED CIRCUITS PER 210-12 ON PANEL
 SCHEDULE(S).
  
 6)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN DISC`S
 AND PANELS. SIZE PER 250-122.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-07-25 Cont ID  
Sent By alange Date 2003-07-25 Time 09:35 Rev Time 0.00
Received By alange Date 2003-07-25 Time 09:35 Sent To E
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2003-07-25 Cont ID  
Sent By alange Date 2003-07-24 Time 11:35 Rev Time 0.00
Received By alange Date 2003-07-24 Time 10:49 Sent To E
Notes
2003-07-24 00:00:00TO BT DESK
 BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-06 Cont ID  
Sent By btrobaug Date 2002-11-06 Time 16:29 Rev Time 0.00
Received By btrobaug Date 2002-11-06 Time 16:29 Sent To E
Notes
2002-11-06 00:00:00TO "E" IN BOX./WRT

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2002-06-17 Cont ID  
Sent By pkrauss Date 2002-06-17 Time 15:28 Rev Time 0.45
Received By pkrauss Date 2002-06-17 Time 15:27 Sent To  
Notes
2002-06-17 00:00:001997 SMC- MECHANICAL PERMIT REQUIRED
  
 PLEASE PROVIDE PLANS WITH MECHANICAL
 PERMIT APPLICATION.
  
 PLEASE PROVIDE MANUFACTURER INSTALLATION
 INSTRUCTIONS FOR ALL GAS APPLIANCES.
 SHOP COMPLIANCE WITH 1997 SMC CHAPTER 7
 FOR COMBUSTION AIR & VENTILATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-03-30 Cont ID  
Sent By hmoser Date 2002-03-30 Time 11:58 Rev Time 0.33
Received By hmoser Date 2002-03-30 Time 11:58 Sent To  
Notes
2002-03-30 00:00:00NO MECHANICAL PLANS 3/30/02 H.M.

Review Stop P PLUMBING
Rev No 4 Status P Date 2003-07-25 Cont ID  
Sent By btrobaug Date 2003-07-25 Time 11:18 Rev Time 0.50
Received By kstevens Date 2003-07-25 Time 10:58 Sent To  
Notes
2003-07-25 00:00:00REVISION OK - NEW SINK IN KITCHEN WITH A
 AAV STUDOR VENT.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-11-23 Cont ID  
Sent By btrobaug Date 2002-12-16 Time 15:12 Rev Time 0.25
Received By jleech Date 2002-11-23 Time 12:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-06-15 Cont ID  
Sent By btrobaug Date 2002-11-12 Time 15:34 Rev Time 0.33
Received By jleech Date 2002-06-15 Time 08:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-03-30 Cont ID  
Sent By jleech Date 2002-03-30 Time 06:42 Rev Time 0.33
Received By jleech Date 2002-03-30 Time 06:28 Sent To  
Notes
2002-03-30 00:00:00DENIED;
 FLOOR PLAN DOESNOT MATCH RISER DIAGRAM.
 A.6 W/C'S ON RISER DIAGRAM 4 ON FLOOR
 PLAN.
 B.NO BIDET ON FLOOR PLAN.
 C.5 TUBS ON RISER DIA. 3 ON FLOOR
 PLAN
 D.3 SHOWERS ON RISER DIA. 1 ON FLOOR
 PLAN.
 PLUMBING PLAN REVIEW BY
 JOHN LEECH
 659-8096 EXT. 8369

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2002-04-09 Cont ID  
Sent By btrobaug Date 2002-06-24 Time 16:35 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-20 Cont ID  
Sent By btrobaug Date 2002-11-06 Time 16:31 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***