Plan Review Details - Permit 02022328
Plan Review Stops For Permit 02022328
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2003-02-07 Cont ID  
Sent By hpiskura Date 2003-02-07 Time 08:58 Rev Time 0.00
Received By hpiskura Date 2003-02-07 Time 07:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2003-01-16 Cont ID  
Sent By hpiskura Date 2003-01-16 Time 14:25 Rev Time 0.00
Received By hpiskura Date 2003-01-16 Time 13:22 Sent To FIRE
Notes
2003-01-16 00:00:00SHEETS A1, A2 AND A5 OF THE JI PEREZ
 PLANS DATED 12/19/02 SATISFY MOST OF
 THE COMMENTS CONTAINED ON THE 12/03/02
 LIST.
  
 SHEET A3 DATED 11/5/02 HAS INCORRECT
 INFORMATION RE: THE EXTERIOR WALL
 SHEATHING
 BEING WOOD.PLEASE REVISE AS NECESSARY.
  
 SHEET S3 IS DATED 10/9/02 AND DOES NOT
 ADDRESS THE CHANGE FROM WOOD SHEATHING
 TOGYPSUM BOARD.PROVIDE A SIGNED AND
 SEALED STATEMENT FROM THE ENGINEER THAT
 THE REVISED MATERIAL HAS BEEN
 CONSIDERED IN HIS DESIGN AND IS
 ADEQUATE, INCLUDE A
 FASTENING SCHEDULE.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY, THE PERMIT PLANS
 STAMPED BY THAT OFFICE, AND A COPY OF
 THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.
 CALL 561-233-5025 FOR MORE INFORMATION.
  
 PLEASE CONSOLIDATE THE PLANS INTO TWO,
 CONCISE, CURRENT SETS.REMOVE ANY OLD
 PAGES AND INSERT ANY NEW ONES AS
 NECESSARY.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-12-02 Cont ID  
Sent By sgraham Date 2002-11-26 Time 08:52 Rev Time 0.00
Received By hpiskura Date 2002-12-02 Time 12:52 Sent To  
Notes
2003-01-16 00:00:00COMMENTS ARE UNDER 02080218

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-08-22 Cont ID  
Sent By btrobaug Date 2003-08-22 Time 15:28 Rev Time 1.00
Received By btrobaug Date 2003-08-22 Time 14:08 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2003-05-13 Cont ID  
Sent By csiegber Date 2003-08-19 Time 16:32 Rev Time 1.00
Received By btrobaug Date 2003-05-13 Time 09:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-11-26 Cont ID  
Sent By shernand Date 2003-05-08 Time 12:47 Rev Time 1.00
Received By btrobaug Date 2002-11-26 Time 17:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-09-02 Cont ID  
Sent By mcarsill Date 2003-09-02 Time 16:33 Rev Time 0.00
Received By mcarsill Date 2003-09-02 Time 16:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2003-01-16 Cont ID  
Sent By nmccray Date 2003-01-16 Time 15:53 Rev Time 0.00
Received By nmccray Date 2003-01-16 Time 15:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-12-10 Cont ID  
Sent By hpiskura Date 2003-01-16 Time 14:26 Rev Time 0.00
Received By nmccray Date 2002-12-10 Time 14:52 Sent To  
Notes
2002-12-10 00:00:001) SEE NOTES UNDER PERMIT # 02080218
 12/10/02 NAM

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2003-09-12 Cont ID  
Sent By csiegber Date 2003-09-12 Time 15:16 Rev Time 0.00
Received By csiegber Date 2003-09-12 Time 15:15 Sent To  
Notes
2003-09-12 00:00:00COMM BD #60

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2003-08-22 Cont ID  
Sent By btrobaug Date 2003-08-22 Time 15:28 Rev Time 0.00
Received By btrobaug Date 2003-08-22 Time 15:28 Sent To  
Notes
2003-08-22 00:00:00TO COMM BOARD #32./WRT

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2003-08-19 Cont ID  
Sent By csiegber Date 2003-08-19 Time 16:32 Rev Time 0.00
Received By csiegber Date 2003-08-19 Time 16:32 Sent To E
Notes
2003-08-19 00:00:00TO BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2003-05-08 Cont ID  
Sent By shernand Date 2003-05-08 Time 12:47 Rev Time 0.00
Received By shernand Date 2003-05-08 Time 12:47 Sent To E
Notes
2003-05-08 00:00:00BT DESK

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2003-02-06 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 17:22 Rev Time 0.00
Received By dpalmer Date 2003-02-06 Time 17:22 Sent To  
Notes
2003-02-06 00:00:00TO COMM BOARD #15

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2002-12-27 Cont ID  
Sent By sgraham Date 2003-01-06 Time 16:41 Rev Time 0.00
Received By dpalmer Date 2002-12-27 Time 12:24 Sent To Z
Notes
2002-12-27 00:00:00SENT TO ZONING AS IT SHOWS F IN COMP.
 ON FIRST TWO REVIEWS.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-26 Cont ID  
Sent By btrobaug Date 2002-11-26 Time 13:26 Rev Time 0.00
Received By btrobaug Date 2002-11-26 Time 13:26 Sent To  
Notes
2002-11-26 00:00:00TO COMM BOARD# 64./WRT.
 COMM BOARD #63/WRT

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2003-09-15 Cont ID  
Sent By hmoser Date 2003-09-15 Time 14:10 Rev Time 0.50
Received By hmoser Date 2003-09-15 Time 14:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2003-09-09 Cont ID  
Sent By hmoser Date 2003-09-08 Time 14:14 Rev Time 0.50
Received By hmoser Date 2003-09-08 Time 14:14 Sent To  
Notes
2003-09-08 00:00:00PLAN DENIED
 1 REFER TO SECTION 601.4 EXCEPTION # 1
 FOR RETURN AIR.
 2 NO A/C SPECIFICATIONS ON PLAN.
 3 WHAT IS 3X8 METAL DUCT GOING THROUGH
 ROOF.
 PLAN REVIEW BY HAROLD MOSER
 (561)805-6732

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2003-01-10 Cont ID  
Sent By pkrauss Date 2003-01-10 Time 14:42 Rev Time 0.00
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2003-01-08 Cont ID  
Sent By pkrauss Date 2003-01-08 Time 12:54 Rev Time 0.45
Received By pkrauss Date 2003-01-08 Time 09:45 Sent To  
Notes
2003-01-08 00:00:00CALLED DAVID ROMKE, IS EQUIPMENT NEW OR
 EXISTING?(EQUIPMENT SCHEDULE NOT
 SHOWN ON PLAN

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-12-02 Cont ID  
Sent By pkrauss Date 2002-12-02 Time 11:25 Rev Time 0.50
Received By pkrauss Date 2002-12-02 Time 10:37 Sent To  
Notes
2002-12-02 00:00:00DENIED:
  
 AS PER 2001 FBC 705.6, ALL PENETRATIONS
 OF A FLOOR, FLOOR/CEILING ASSEMBLY, OR
 CEILING MEMBRANE OF A ROOF/CEILING
 ASSEMBLY SHALL BE PROTECTED BY SHAFT
 ENCLOSURE IN ACCORDANCE WITH 705.2 OR
 SHALL COMLY WITH 705.6.1.1 OR 705.6.1.2.
  
 PROVIDE OUTSIDE AIR CACULATIONS FOR THE
 RESIDENTIAL SPACES.SHOW COMPLIANCE
 WITH 2001 FBC(M) 402.2 FOR NATURAL
 VENTILATION OR TABLE 403.3 MECHANICAL
 VENTILATION.
  
 BEDROOM AREAS REQUIRE RETURN AIR -
 BALANCED RETURN AIR - 2001 FBC(M) 601.4
 RETURN AIR SHALL BE EQUAL TO SUPPLY
 AIR BY MEANS OF AIR TRANSFER OR A RETURN
 AIR (JUMPER).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 5 Status P Date 2003-09-15 Cont ID  
Sent By kstevens Date 2003-09-15 Time 13:40 Rev Time 1.50
Received By kstevens Date 2003-09-15 Time 13:40 Sent To  
Notes
2003-09-15 00:00:00REVISION OK - DELETED 1ST FLOOR RES.
 CHANGED ROUTING OF SANT. & WATER LINES

Review Stop P PLUMBING
Rev No 4 Status F Date 2003-09-05 Cont ID  
Sent By kstevens Date 2003-09-05 Time 13:08 Rev Time 1.00
Received By kstevens Date 2003-09-05 Time 13:08 Sent To  
Notes
2003-09-05 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 1) SHT P-3 1ST FLOOR SANT. RISER DOES
 NOT REFLECT SHT P-1 FLOOR PLAN.
 2) SHT P-3 SANITARY RISER DIAGRAM FOR
 THE 1ST FLOOR OFFICE DOES NOT REFLECT
 THE FLOOR PLAN ON SHT P-1.
 3) SHT P-3 1ST FLOOR WATER RISER DOES
 NOT REFLECT THE FLOOR PLAN ON SHT P-1.
 4) PERMIT NUMBER FOR THIS BLDG HAS BEEN
 CHANGED TO 02080218. PLEASE SUBMIT ANY
 FUTURE REVISIONS/SUBMITTALS ECT UNDER
 APPROPRIATE PERMIT NUMBER.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2003-01-13 Cont ID  
Sent By kstevens Date 2003-01-13 Time 14:33 Rev Time 0.33
Received By kstevens Date 2003-01-13 Time 14:32 Sent To  
Notes
2003-01-13 00:00:00PER N. MELICK, OK TO SIGN OFF UNDER
 FBC-2001. 1 HDCP TOILET ROOM REQUIRED.
 SIGNED SEALED LETTER REQUIRED FROM ARCH-
 ITCET.

Review Stop P PLUMBING
Rev No 2 Status F Date 2003-01-11 Cont ID  
Sent By kstevens Date 2003-01-11 Time 14:51 Rev Time 0.75
Received By kstevens Date 2003-01-11 Time 14:51 Sent To  
Notes
2003-01-11 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) FROM PREVIOUS REVIEW: PER TABLE 407,
 SEPARATE TOILET FACILITIES ARE REQUIRED
 FOR MEN AND WOMEN. 1 WATER CLOSET AND 1
 LAV FOR MEN, 1 WATER CLOSET AND 1 LAV
 FOR WOMEN. SINCE THIS DOES NOT SPACE FOR
 FUTURE TENANT #2 THE FIXTURE COUNT HAS
 LOWERED FOR WOMEN'S CALCULATION.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-12-11 Cont ID  
Sent By kstevens Date 2002-12-10 Time 18:50 Rev Time 1.00
Received By kstevens Date 2002-12-10 Time 18:49 Sent To  
Notes
2002-12-10 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) PER TABLE 407 SEPARATE TOILET FACIL-
 ITIES ARE REQUIRED FOR MEN AND WOMEN.
 1 WATER CLOSET AND 1 LAV FOR MEN
 2 WATER CLOSETS AND 2 LAV'S FOR WOMEN
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377
 FIXTURES,

Review Stop Z ZONING
Rev No 3 Status P Date 2003-01-06 Cont ID  
Sent By sgraham Date 2003-01-06 Time 16:41 Rev Time 0.00
Received By sgraham Date   Time   Sent To I
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2002-11-26 Cont ID  
Sent By dpalmer Date 2002-12-27 Time 12:24 Rev Time 0.25
Received By sgraham Date   Time   Sent To B
Notes
2002-11-26 00:00:00DENIED 2ND CK LIST, LANDSCAPE PLAN
 SHOULD SHOW HEDGE INSTEAD OF WALL IN
 THE FRONT

Review Stop Z ZONING
Rev No 1 Status F Date 2002-03-12 Cont ID  
Sent By sgraham Date 2002-03-12 Time 10:37 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
2002-04-12 00:00:001. NEED LANDSCAPE PLAN
 2. SITE WALL MUST BE A MAX HEIGHT OF 42"
 3. MUST MEET PARKING REQUIREMENTS
 4. WINDOWS NOT TO CODE
2002-03-12 00:00:00PLANS DO NOT MEET REQUIREMENTS OF
 CODE
 PLANS DO NOT MEET REQUIREMENTS OF CODE