Plan Review Details - Permit 02022325
Plan Review Stops For Permit 02022325
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-12-02 Cont ID  
Sent By hpiskura Date 2002-12-02 Time 08:51 Rev Time 0.00
Received By hpiskura Date 2002-12-02 Time 08:51 Sent To  
Notes
2002-12-02 00:00:00REVISION #2 DATED 11/21/02

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-06-12 Cont ID  
Sent By btrobaug Date 2002-11-22 Time 18:09 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-05-14 Cont ID  
Sent By hpiskura Date 2002-05-14 Time 08:30 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-05-14 00:00:00THE THREE SETS OF PLANS PROVIDED CALL
 OUT A "SPRAY POLYURETHANE FOAM ROOFING
 SYSTEM"PROVIDE AN EVALUATION REPORT
 FROM A RECOGNIZED AGENCY FOR THE FIRE
 AND WIND RESISTANCE CLASSIFICATION.IF
 THE ATTACHED REPORT FROM METRO DADE FOR
 ULTRAGUARD PVC IS INTENDED TO BE USED,
 PLEASE AMEND THE PLANS TO REFLECT THAT.
  
 THE PLANS STILL INDICATE THE USE OF
 PLYWOOD IN THE EXTERIOR WALL, AS NOTED
 IN THE 3/8/02 CHECKLIST, PLEASE REVISE
 AS NECESSARY.
  
 PLEASE PROVIDE THE PRODUCT EVALUATION
 REPORT FOR THE SPECIFIC DRYVIT SYSTEM
 TO BE USED AS PREVIOUSLY REQUESTED.IF
 THE PAREX SYSTEM IS TO BE USED, PROVIDE
 THATEVALUATION REPORT AND AMEND THE
 PLANS ACCORDINGLY.
  
 PROVIDE A SPECIFIC CONNECTION DETAIL FOR
 THE "SUSPENDED CLOUDS" INCLUDING AN
 ANALYSIS OF THE EXISTING STRUCTURE TO
 ACCEPT THE ADDED LOADS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-03-08 Cont ID  
Sent By hpiskura Date 2002-03-08 Time 10:12 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-03-08 00:00:00SHEET A103, PROVIDE TEST REPORTS FOR THE
 SKYLIGHTS TO BE INSTALLED DEMONSTRATING
 COMPLIANCE WITH HURRICANE MISSILE
 IMPACT RESISTANCE. SEE SBC 1707.4 AS
 AMENDED.
  
 PROVIDE TEST REPORTS FOR THE ROOF
 COVERING FOR WIND AND FIRE.SEE SBC
 1503
  
 THE PLANS INDICATE THE PROPOSED USE OF
 PLYWOOD IN THE EXTERIOR WALLS.THE
 EXTERIOR WALLS OF BUILDINGS LOCATED IN
 THE FIRE DISTRICT ARE REQUIRED TO BE OF
 NON-COMBUSTIBLE CONSTRUCTION.SEE SBC F
 102.1
  
 SHEET A202 SHOW THE SERVICE ASVISORS
 BOOTHS ON AN HC ACCESSIBLE ROUTE.
  
 PROVIDE THE EVALUATION REPORT FOR THE
 DRYVIT SYSTEM TO BE USED.
  
 PROVIDE THE HURRICANE MISSILE IMPACT REP
 ORTS FOR THE GLAZING SYSTEM TO BE USED I
 N THE SERVICE ADVISORS BOOTHS.
  
 WHAT ARE THE "SUSPENDED CLOUDS"?

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-10-24 Cont ID  
Sent By btrobaug Date 2002-10-24 Time 16:27 Rev Time 0.25
Received By btrobaug Date 2002-10-24 Time 16:01 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-10-21 Cont ID  
Sent By btrobaug Date 2002-10-21 Time 14:10 Rev Time 0.50
Received By btrobaug Date 2002-10-21 Time 14:10 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-11 Cont ID  
Sent By dpalmer Date 2002-03-11 Time 07:13 Rev Time 0.00
Received By dpalmer Date 2002-03-11 Time 06:52 Sent To  
Notes
2002-03-11 00:00:00***** NOTE****
  
 SHOW WINDOW OUTLETS MISSING.
 REDLINED ON PLANS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-05-17 Cont ID  
Sent By mcarsill Date 2002-05-17 Time 15:08 Rev Time 0.00
Received By mcarsill Date 2002-05-17 Time 15:08 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-03-27 Cont ID  
Sent By pkrauss Date 2002-05-06 Time 09:00 Rev Time 0.00
Received By mcarsill Date 2002-03-27 Time 13:43 Sent To  
Notes
2002-03-27 00:00:00A) PLEASE PROVIDE MORE DETAILS ON
 SUSPENDED CLOUDS.
 B) PLEASE INDICATE EXIT PATHS IN
 VEHICLE SHOWROOM AREA.
 C) INTERIOR FINISH CLASSIFICATION
 INFORMATION REQUIRED ON WALLS AND
 CEILINGS.
 D) PLEASE INDICATE FIRE RATING OF
 EXISTING WALL BETWEEN SERVICE AND
 OFFICE AREAS.
 E) BUILDING ADDRESS REQUIRED ON
 BUILDING.
 F) PLEASE PROVIDE MORE DETAILS ON
 POLYURETHANE FOAM ROOFING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2002-11-22 Cont ID  
Sent By btrobaug Date 2002-11-22 Time 18:09 Rev Time 0.00
Received By btrobaug Date 2002-11-22 Time 18:08 Sent To B
Notes
2002-11-22 00:00:00TO HAROLD./WRT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-05-06 Cont ID  
Sent By pkrauss Date 2002-05-06 Time 08:16 Rev Time 0.35
Received By pkrauss Date 2002-05-06 Time 07:52 Sent To FIRE
Notes
2002-05-06 00:00:00PROVISO:
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR WITH
 NOTIFICATION AS PER 2001 FBC(M) 606.2.1
 & NFPA 90A 4-4.4.3.
  
 AIR BALANCE REQUIRED - .001 WC OR LESS
 ACROSS CLOSED DOORS AS PER 2001 FBC(M)
 601.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-03-04 Cont ID  
Sent By pkrauss Date 2002-03-04 Time 15:53 Rev Time 0.45
Received By pkrauss Date 2002-03-04 Time 15:53 Sent To  
Notes
2002-03-04 00:00:00 
 PLAN SHEET E-M-201, PLEASE CLARIFY
 EXISTING A/C RETURN FROM ROOMS A109
 THROUGH A111.IS THIS RETURN AIR OR
 EXHAUST?AS PER 1997 SMC 503.3.1, AIR
 EXHAUSTED FROM BATH, TOILET, URINAL,
 LAVATORY, LOCKER, COAT ROOM OR SIMILAR
 ROOMS SHALL NOT BE RECIRCULATED.
  
 INDICATE MANUFACTURER, MODEL, & TONNAGE
 OF EXISTING RTU.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-06-11 Cont ID  
Sent By kstevens Date 2002-06-11 Time 14:23 Rev Time 0.00
Received By kstevens Date 2002-06-11 Time 14:23 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-05-25 Cont ID  
Sent By kstevens Date 2002-05-25 Time 11:07 Rev Time 0.00
Received By kstevens Date 2002-05-25 Time 11:07 Sent To  
Notes
2002-05-25 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) COMMENT FROM PREVIOUS REVIEW. PLEASE
 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS. NEW ROOF AREA IS
 BEING ADDED (SEE SHT A-103). ALSO 1/2
 AREA OF ALL VERTICAL WALLS. SHOW DETAILS
 OF HOW WEST ROOF DRAINS ON TO EAST ROOF.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-03-15 Cont ID  
Sent By kstevens Date 2002-03-15 Time 14:38 Rev Time 1.50
Received By kstevens Date 2002-03-15 Time 14:38 Sent To  
Notes
2002-03-15 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SHT A-103 PLEASE SUBMIT CALCULATIONS
 FOR ROOF DRAINS. ADD NEW ROOFING SECT-
 IONS AND 1/2 ALL VERTICAL WALLS. SHOW
 DETAILS HOW THE WEST ROOF DRAINS ON TO
 THE EAST ROOF.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377