| 2002-03-01 00:00:00 | A) THE FIRE DEPARTMENT CONNECTION | | | MUST CONTAIN A CHECK VALVE. | | | B) ANY NEW PIPING MUST BE TESTED AT | | | 200 LBS. FOR TWO HOURS. | | | C) THE RELOCATED FIRE DEPARTMENT | | | CONNECTION MUST HAVE 7' 6" CLEARANCE TO | | | THE FRONT AND SIDES OF IT. | | | D) THE PLANS INDICATES AN 1 2/2 EXISTING | | | CONNECTION BUT IT IS BELIEVED THAT 2 | | | 1/2 INCH CONNECTION EXISTS. | | | E) CONNECTION MUST BE POINTED IN THE | | | RIGHT DIRECTION SO THE HOSE WILL NOT | | | KINK. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|