Plan Review Details - Permit 02022301
Plan Review Stops For Permit 02022301
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-03-15 Cont ID  
Sent By pkrauss Date 2002-03-11 Time 13:34 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-03-15 00:00:00SBC 3401.5 REQUIRES THAT THE ENTIRE
 BUILDING BE BROUGHT UP TO CURRENT CODES
 WHEN A BUILDING IS INCREASED IN HEIGHT.
  
 PROVIDE CALCULATIONS AND PLANS PREPARED
 BY A PROFESSIONAL ENGINEER
 DEMONSTRATING THE EXISTING BUILDING
 WILL SUPPORT ALL OF THE STRUCTURAL
 LOADS THAT WILL BE IMPOSED UPON IT BY
 THE ADDITION. SEE SBC 104.2.
  
 SHEET S2 SHOWS A PORTION OF THE
 PROPOSED SECOND FLOOR TO BE PLACED ON
 THE TOP CHORD OF THE EXISTING TRUSSES
 WITHOUT ADDITIONAL SUPPORT.THIS IS
 NOT A VIABLE DESIGN.
  
 THE AREA OF THE OPENINGS ON THE WEST
 ELEVATION OF THE ADDITION EXCEED THE
 20% ALLOWED BY SBC TABLE 600 FOR TYPE
 VI CONSTRUCTION LOCATED 3' TO 10' FROM A
 PROPERTY LINE.PLEASE REVISE AS
 NECESSARY.
  
  
 THE ADDITION WILL BE SUBJECT TO IMPACT
 FEES COLLECTED BY THE COUNTY FOR THE
 CITY.THE PERMIT PLANS MUST BE STAMPED
 BY THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 233-5025 FOR MORE
 INFORMATION.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-06 Cont ID  
Sent By dpalmer Date 2002-03-06 Time 08:41 Rev Time 0.00
Received By dpalmer Date 2002-03-06 Time 08:41 Sent To P
Notes
2002-03-06 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2)NOTE: PLEASE CLARIFY IF THERE IS A
 DOOR GOING INTO MASTER BEDROOM. NONE
 SHOWN ON ELECTRICAL PLAN. PLEASE NOTE
 THAT A SD IS REQ`D INSIDE AND OUTSIDE
 RM.
 PLEASE NOTE SD`S WILL BE REQD IN
 EXISTING BEDROOMS.
  
 3)NOTE: PLEASE NOTE LOAD CALCS SHOW
 WASHER, BUT NONE SHOWN ON PLANS OR PANEL
 SCHEUDLE? PLEASE CLARIFY.
  
 4)NOTE: PLEASE NOTE LOADS FOR A/C`S
 ARE SHOWN AT 5KW AND 8KW AND SHOWN AT
 14500 ON LOAD CALCS, PLEASE CORRELATE.
  
 5)NOTE: PLEASE CLARIFY TWO WATER SPA
 CIRCUITS AND LOADS? ELEC ON E-2 ONLY
 SHOWS ONE?
  
 6)NOTE: PLEASE NOTE MISSING GFI OUTLET
 ON KITCHEN PENINSULAR. 210-52-C-3
  
 7)NOTE: PLEASE CLARIFY DISPOSAL SHOWN
 ON LOAD CALCS, BUT NOT ON PANEL SCHEDULE
 ?
  
 8)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTION FOR BEDRROMS, PER 210-12.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-03-11 Cont ID  
Sent By kstevens Date 2002-03-11 Time 13:47 Rev Time 1.00
Received By pkrauss Date 2002-03-11 Time 13:07 Sent To P
Notes
2002-03-11 00:00:00*******************DENIED***************
  
 INSUFFICIENT INFORMAION FOR MECHANICAL
 REVIEW.PLEASE PROVIDE THE FOLLOWING
 INFORMATION.
  
 1.PROVIDE SIZE OF DUCTWORK BEING
 INSTALLED.
  
 2.INDICATE GRILLE SIZE & CFM
 DISTRIBUTION.
  
 3.PROVIDE BTU INFORMATION FOR THE
 EXISTING GAS WATER HEATER.
  
 4.INDICATE SIZE OF NEW FLUE PIPE.
  
 PLEASE NOTE, ADDTIONAL PERMIT REQUIRED
 FOR GAS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-03-08 Cont ID  
Sent By pkrauss Date 2002-03-11 Time 13:36 Rev Time 0.50
Received By kstevens Date 2002-03-08 Time 17:22 Sent To M
Notes
2002-03-08 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) SUBMIT SANITARY RISER DIAGRAM FOR
 SECOND FLOOR. SHOW HOW IT TIES INTO BLDG
 DRAIN OR SEWER. SHOW PIPE SIZES.
 2) IS THERE A MASTER BATH ON THE FIRST
 FLOOR AND THE SECOND FLOOR? SEE PAGE P1.
 THE FLOOR PLAN ON THIS PAGE DOES NOT
 MATCH THE FLOOR PLAN ON PAGE A3.
 3) SEPARATE GAS PERMIT REQUIRED. PLEASE
 SUBMIT PLANS WITH GAS PERMIT APPLICATION
 INFORMATION REQUIRED FOR PERMIT IS SHOWN
 ON GAS PERMIT APPLICATION REQUIREMENT
 SHEET. (SEE ATTACHED).
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-05 Cont ID  
Sent By gjoyce Date 2002-03-05 Time 11:57 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***