| Plan Review Stops For Permit 02022293 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-08-20 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2002-08-20 |
Time |
14:43 |
Rev Time |
3.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-08-20 00:00:00 | ************BUILDING PROVISO************ | | | | | | 1) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 2) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 3) PROVIDE AN ACCEPTABLE STORM PANEL | | | INSTALLATION PLAN AS REQUIRED BY THE | | | BUILDING OFFICIAL PRIOR TO INSTALLATION | | | OF ANY NON-IMPACT RATED GLAZING. | | | | | | 4) SUBMIT SHOP DRAWINGS OF SECOND FLOOR | | | GUARDRAILS FOR APPROVAL PRIOR TO | | | INSTALLATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-07-23 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2002-07-23 |
Time |
15:20 |
Rev Time |
4.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-07-23 00:00:00 | BUILDING DENIED | | | | | | 1) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 2) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 3) THE ATTIC VENTING CALCULATIONS ARE | | | NOT CORRECT. THE 6240 SQ.FT. OF ATTIC | | | WHEN DIVIDED BY 150 SQ.FT. REQUIRES | | | 41.6 SQ.FT. OF NET FREE VENTILATING AREA | | | DETERMINE THE NET FREE VENT AREA OF THE | | | 4"X24" SCEEN VENT (MANUFACTURERS SPECS.) | | | AND INDICATE THE NUMBER OF SCREEN VENTS | | | THAT WILL BE REQUIRED. THE CALCULATIONS | | | FOR 1ST FLOOR ATTIC SPACE IS ALSO | | | INCORRECT. | | | | | | 4) SUBMIT A WRITTEN PLAN TO THE BUILDING | | | OFFICIAL FOR HURRICANE MISSLE IMPACT FOR | | | HIS APPROVAL. | | | THE PLAN MUST INCLUDE THE FOLLOWING | | | INFORMATION: | | | A) WHO WILL INSTALL PANELS (MUST BE | | | BUILDING STAFF) | | | B) ESTIMATED TIME TO INSTALL | | | C) INDICATE ON PLANS WHERE THEY WILL BE | | | STORED ON SITE (IF STORED IN STANDING | | | POSITION, AN ENGINEER IS TO DESIGN THE | | | ENCLOSURE) | | | D) PANELS ON FIRST FLOOR ONLY, WITHOUT | | | USE OF LADDERS OR LIFTS | | | E) BUILDING OFFICIAL MUST APPROVE THE | | | WRITTEN PLAN | | | | | | 5) ENGINEERED TRUSS DRAWINGS AND LAYOUT | | | WILL BE REQUIRED TO BE SUBMITTED FOR | | | REVIEW PRIOR TO INSTALLATION. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-04-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-07-09 |
Time |
10:11 |
Rev Time |
4.00 |
| Received By |
rmcdouga |
Date |
|
Time |
|
Sent To |
FIRE |
|
| Notes |
| 2002-04-12 00:00:00 | *************BUILDING DENIED************ | | | | | | 1) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 2) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 3) PROVIDE A KEY PLAN AND INSTALLATION | | | SCHEDULE FOR THE STORM PANELS OR APPLY | | | UNDER A SEPARATE PERMIT. REMOVABLE STORM | | | PANELS CAN NOT BE USED ABOVE THE GROUND | | | FLOOR. IMPACT RESISTANT GLAZING OR | | | PERMANETLY AFFIXED PROTECTIVE DEVICES SH | | | ALL BE INSTALLED. PERMANENTLY AFFIXED | | | PROTECTIVE DEVICES REQUIRE THE WRITTEN | | | APPROVAL OF THE BUILDING OFFICIAL. | | | | | | 4) SHEET A1 IS MISSING THE FOOTING | | | DESIGNATIONS. PLEASE CORRECT. | | | | | | 5) PLEASE CLARIFY DETAIL 27/A11 AS TO | | | HOW GABLE END WILL BE CONSTRUCTED AT THE | | | VAULTED CEILING AT SECOND FLOOR BEDROOM. | | | | | | 6) THE BALCONY RAIL IS SHOWN ON SHEET A5 | | | WITH A 4" SPACE BELOW THE BOTTOM RAIL. | | | THIS WILL NOT REJECT A 2" SPHERE AS CODE | | | REQUIRES. PLEASE CORRECT. | | | | | | 7) THE FRONT ELEVATION ON A5 INDICATES A | | | CEMENTITIOUS FINISH OVER CONCRETE BLOCK | | | AT THE SECOND FLOOR BEDROOM, WHICH IS | | | WOOD FRAME. PLEASE CORRECT. | | | | | | 8) THE FIRE RATED DOORS BETWEEN THE | | | UNITS AND THE GARAGE ARE REQUIRED TO | | | HAVE APPROVED CLOSERS PER 97SBC SECT. | | | 705.1.3.5. | | | | | | 9) THE RISE AND RUN DIMENSIONS ON DETAIL | | | 1/A7 DO NOT CORRESPOND WITH THOSE GIVEN | | | IN SECTION B-B. TREADS EXCLUSIVE OF | | | NOSING IS REQUIRED TO BE A MINIMUM OF 9" | | | WIDE AND TREADS LESS THAN 10" WIDE ARE | | | REQUIRED TO HAVE A NOSING OF APPROX. 1". | | | 97SBC SECT. 1007.3.2 & 1007.3.3 SECTION | | | B-B INDICATES A 9.5" WIDE TREAD | | | INCLUDING THE NOSING. PLEASE CORRECT. | | | | | | 10) THE DIAPHRAM SCHEDULE ON A13 NOTES | | | 16"O.C. WALL FRAMING AND A7 INDICATES | | | 24" SPACING. PLEASE CORRECT. | | | | | | 11) SECTION 8/A8 CALLS FOR 4"X24" SOFFIT | | | VENTS SPACED 8'O.C. PROVIDE AN ATTIC | | | AREA CALCULATION AND INCLUDE THE FREE | | | AREA OF THE SOFFIT VENT SCREEN. ALSO, | | | PLEASE SPECIFY THE "CEMENTITIOUS" | | | SOFFIT MATERIAL. | | | | | | 12) PROVIDE WINDOW, DOOR AND GARAGE DOOR | | | BUCK FASTENING DETAILS. | | | | | | 13)DETAILS 13 & 23 ON A11 ARE MISLABELED | | | AS A17. PLEASE CORRECT. | | | | | | 14) DETAIL 23 ON A11 MUST INDICATE THAT | | | THE ONE HOUR TENANT SEPARATION IS | | | MAINTAINED TO THE UNDERSIDE OF THE ROOF | | | SHEATHING. | | | | | | 15) PROVIDE AN ADDITIONAL COPY OF THE | | | PRODUCT APPROVAL FOR THE FRONT DOOR. | | | (TWO ARE REQUIRED) | | | | | | 16) THE OPTIONS SHOWN ON SHEETS A17-A19 | | | MUST COMPLY WITH THE REQUIREMENTS OF THE | | | FAIR HOUSING ACT. | | | | | | 17) THE PA23 CONNECTOR LISTED IN DETAIL | | | 19 ON A11 FOR TRUSS GT2, IS A PURLIN | | | ANCHOR AND IS NOT DESIGNED FOR USE AS A | | | TRUSS ANCHOR. | | | | | | 18) PLEASE SPECIFY A CONNECTOR OR | | | CONNECTION DETAIL FOR TRUSS GT1. DETAIL | | | 32 ON A11 INDICATES THE ATTACHMENT OF | | | THE WOOD FRAME WALL TO THE MASONRY. | | | | | | 19) NO TRUSS DRAWINGS WERE SUBMITTED | | | WITH THE TRUSS LAYOUTS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)659-8096 EXT.8202 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2003-03-18 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-03-18 |
Time |
17:06 |
Rev Time |
0.75 |
| Received By |
btrobaug |
Date |
2003-03-18 |
Time |
16:15 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2002-08-20 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-12 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-08-20 |
Time |
08:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2002-08-13 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-08-13 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-08-13 |
Time |
10:18 |
Sent To |
|
|
| Notes |
| 2002-08-13 00:00:00 | ************** UNSAT ***************** | | | | | | PLEASE SEE NOTE ATTACHED FOR FS/FAC. | | | PLEASE NOTE THAT PLANS BEING TURNED | | | DOWN FOR THE SAME COMMENTS FOUR OR MORE | | | TIMES ARE SUBJECT TO 4X FEE FOR PLAN | | | REVIEW PORTION OF FEES. | | | | | | 1)NOTE: PLEASE NOTE THAT ELECTRICAL | | | RISER DIAGRAM IS STILL NOT SHOWING ANY | | | MAINS? PLEASE NOTE PANELS SHOWN AS "MLO" | | | PLEASE ALSO NOTE THAT NO MAINS ARE | | | SHOWN ON PLANS. A-14. | | | | | | | | | 2)NOTE; PLEASE NOTE THAT AN EQUIPMENT | | | GRND IS REQ`D BETWEEN MAINS AND PANELS. | | | 250-122 | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PLAMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2002-07-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-07-09 |
Time |
10:14 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-07-09 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2002-07-09 00:00:00 | *************** UNSAT ****************** | | | | | | | | | 1)NOTE: PLEASE NOTE, NOT ALL NOTES FROM | | | FIRST REVIEW WERE ADDRESSED. PLEASE SEE | | | FIRST REVIEW NOTES. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-03-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-22 |
Time |
07:05 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-03-22 |
Time |
07:05 |
Sent To |
B |
|
| Notes |
| 2002-03-22 00:00:00 | ***************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT RISER DIAGRAM | | | SHOWS MAIN DISCONNECTS BETWEEN METERS | | | AND PANELS. PLEASE SHOW LOCATION OF | | | THESE DISC`SON PLANS. | | | PLEASE NOTE THAT 150A PANELS HAVE NO | | | INDICATION OF BEING "MCB" OR "MLO" | | | | | | 2)NOTE: PLEASE NOTE THAT IF A MAIN | | | DISCONNECT IS USED, THEN AN EQUIPMENT | | | GROUNDING CONDUCTOR MAY IS REQ`D. SIZE | | | PER 250-122. | | | | | | 3)NOTE: PLEASE NOTE MISSING SD`S AT THE | | | BOTTOM OF STAIRS FOR UPPER UNITS. PLEASE | | | SEE NFPA-72 2-2.1.1.1/ 2-5.2.1.3. | | | | | | 4)NOTE: PLEASE LIST THE REQUIRED ARC | | | FAULT PROTECTED CIRCUITS ON PANEL | | | SCHEDULE PER 210-12. | | | | | | 5)NOTE: PLEASE NOTE MISSING SD`S FOR | | | ROOMS THAT ARE ADAPTABLE SLEEPING ROOMS | | | WITH CLOSETS AND/OR BATHS. NFPA-72 | | | 2-2.1.1.1. UPPER UNIT/DEN. | | | | | | 6)NOTE: PLEASE SEE OPT PAGE A-18, PLEASE | | | NOTE MISSING MANY SD`S. INSIDE AND OUT- | | | -SIDE ALL SLEEPING ROOMS AND ON EACH | | | LEVEL OF MULTI LEVEL UNITS. SD`S ARE TO | | | BE CLOSE VICINTY OF STAIRS ON EACH LEVEL | | | . | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | ' | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
P |
Date |
2002-08-20 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2002-08-20 |
Time |
15:24 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2002-08-20 |
Time |
15:24 |
Sent To |
|
|
| Notes |
| 2002-08-20 00:00:00 | PASSED WITH PROVISOS: | | | 1. ITEMS 1 THROUGH 3 OF LAST REVIEW HAVE | | | NOT BEEN ADDRESSED, CONTRACTOR WILL | | | APPLY FOR CIVIL/SITE WORKS SEPARATELY. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2002-06-20 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2002-06-20 |
Time |
09:32 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2002-06-20 |
Time |
09:32 |
Sent To |
|
|
| Notes |
| 2002-06-20 00:00:00 | FAILED: | | | 1. PLEASE REFER TO THE PREVIOUS REVIEW | | | COMMENTS DATED 4-30-02. ITEMS REQUESTED | | | MUST BE PROVIDED FOR OUR REVIEW AND | | | APPROVAL BEFOR ANY PERMIT FOR | | | CONSTRUCTION CAN BE ISSUED. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2002-04-30 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2002-04-30 |
Time |
10:34 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2002-04-30 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2002-04-30 00:00:00 | FAILED: | | | 1. PLEASE SUBMIT CIVIL/SITE PLANS FOR | | | REVIEW AND APPROVAL.PLAN SHOULD ALSO | | | INCLUDE STORM WATER CALCULATION, | | | PERVIOUS AND IMPERVIOUS CALCULATION, | | | POLLUTION PREVENTION PLANS. | | | 2. A SEPARATE PERMIT APPLICATION AND | | | FEES FOR CIVIL / SITE WORKS WILL BE | | | REQUIRED. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2003-03-26 |
|
|
Cont ID |
|
| Sent By |
nmccray |
Date |
2003-03-26 |
Time |
11:12 |
Rev Time |
0.00 |
| Received By |
nmccray |
Date |
2003-03-26 |
Time |
11:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-07-05 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-03-18 |
Time |
17:06 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-07-05 |
Time |
11:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-04-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2002-04-12 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-04-19 |
Time |
17:14 |
Sent To |
|
|
| Notes |
| 2002-04-19 00:00:00 | A) PLEASE INDICATE LOCATION OF NEAREST | | | WET FIRE HYDRANT. | | | B) SEVERAL REQUIRED SMOKE DETECTORS ARE | | | MISSING FROM THE PLANS. | | | C) PLEASE INDICATE ON THE PLANS THAT | | | THE DENS ARE NOT TO BE USED FOR | | | SLEEPING PURPOSES. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-03-12 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-12 |
Time |
15:19 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-12 |
Time |
15:19 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2003-04-07 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2003-04-07 |
Time |
08:35 |
Rev Time |
0.50 |
| Received By |
hmoser |
Date |
2003-04-07 |
Time |
08:34 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2002-08-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-08-20 |
Time |
11:02 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-08-20 |
Time |
10:31 |
Sent To |
|
|
| Notes |
| 2002-08-20 00:00:00 | MECHANICAL PERMIT 02022472 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2002-06-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-22 |
Time |
11:02 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-06-22 |
Time |
11:02 |
Sent To |
|
|
| Notes |
| 2002-06-22 00:00:00 | DENIED: | | | 2ND REQUEST - | | | NO MANUAL J CALCULATIONS SUBMITTED WITH | | | THE ENERGY CALCS. | | | | | | PLANS SUBMITTED ARE OKAY. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-03-21 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2002-03-21 |
Time |
17:13 |
Rev Time |
0.33 |
| Received By |
hmoser |
Date |
2002-03-21 |
Time |
17:13 |
Sent To |
|
|
| Notes |
| 2002-03-21 00:00:00 | PLAN DENIED | | | PLANS AND ENERGY CALCS DO NOT MATCH. | | | PLANS SHOW FOR A/C UNIOTS.CALCS SHOW ONE | | | NO MANUAL J | | | PLAN REVIEW BY HAROLD MOSER | | | [561]659-8096 EXT.8390 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-07-09 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-07-09 |
Time |
13:22 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-07-09 |
Time |
13:21 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-03-09 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2002-03-09 |
Time |
09:26 |
Rev Time |
1.00 |
| Received By |
jleech |
Date |
2002-03-09 |
Time |
09:26 |
Sent To |
|
|
| Notes |
| 2002-03-09 00:00:00 | DENIED; | | | 1.PAGE A-16 PLUMBING RISER UNITS A & C. | | | A.SECOND FLOOR MASTER BATH 3" RISER | | | CANNOT DISCHARGE INTO 2" SHOWER | | | DRAIN. | | | B.W/C WET VENT. PIPE SIZE MUST | | | INCREASE FROM 2" TO 3" WHEN THE | | | FIXTURE LOAD IS MORE THAN 4 FU'S. | | | 2.PAGE A-16 PLUMBING RISER UNITS B & D. | | | A. SEE NOTE 1-A & B. | | | B.LAUNDRY TUB MISSING FOR UNIT D. | | | 3.SHOW DIMENSIONS FOR MASTER BATH W/C | | | TO COMPLY WITH FHA 7.43. MOST CONST- | | | UCTION COMPANY'S DO NOT HAVE THE FHA | | | DESIGN MANUAL. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT 8369 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-03-05 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2002-03-05 |
Time |
09:05 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|