Plan Review Details - Permit 02022293
Plan Review Stops For Permit 02022293
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-08-20 Cont ID  
Sent By rmcdouga Date 2002-08-20 Time 14:43 Rev Time 3.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-08-20 00:00:00************BUILDING PROVISO************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE AN ACCEPTABLE STORM PANEL
 INSTALLATION PLAN AS REQUIRED BY THE
 BUILDING OFFICIAL PRIOR TO INSTALLATION
 OF ANY NON-IMPACT RATED GLAZING.
  
 4) SUBMIT SHOP DRAWINGS OF SECOND FLOOR
 GUARDRAILS FOR APPROVAL PRIOR TO
 INSTALLATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-07-23 Cont ID  
Sent By rmcdouga Date 2002-07-23 Time 15:20 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-07-23 00:00:00BUILDING DENIED
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) THE ATTIC VENTING CALCULATIONS ARE
 NOT CORRECT. THE 6240 SQ.FT. OF ATTIC
 WHEN DIVIDED BY 150 SQ.FT. REQUIRES
 41.6 SQ.FT. OF NET FREE VENTILATING AREA
 DETERMINE THE NET FREE VENT AREA OF THE
 4"X24" SCEEN VENT (MANUFACTURERS SPECS.)
 AND INDICATE THE NUMBER OF SCREEN VENTS
 THAT WILL BE REQUIRED. THE CALCULATIONS
 FOR 1ST FLOOR ATTIC SPACE IS ALSO
 INCORRECT.
  
 4) SUBMIT A WRITTEN PLAN TO THE BUILDING
 OFFICIAL FOR HURRICANE MISSLE IMPACT FOR
 HIS APPROVAL.
 THE PLAN MUST INCLUDE THE FOLLOWING
 INFORMATION:
 A) WHO WILL INSTALL PANELS (MUST BE
 BUILDING STAFF)
 B) ESTIMATED TIME TO INSTALL
 C) INDICATE ON PLANS WHERE THEY WILL BE
 STORED ON SITE (IF STORED IN STANDING
 POSITION, AN ENGINEER IS TO DESIGN THE
 ENCLOSURE)
 D) PANELS ON FIRST FLOOR ONLY, WITHOUT
 USE OF LADDERS OR LIFTS
 E) BUILDING OFFICIAL MUST APPROVE THE
 WRITTEN PLAN
  
 5) ENGINEERED TRUSS DRAWINGS AND LAYOUT
 WILL BE REQUIRED TO BE SUBMITTED FOR
 REVIEW PRIOR TO INSTALLATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-12 Cont ID  
Sent By dpalmer Date 2002-07-09 Time 10:11 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To FIRE
Notes
2002-04-12 00:00:00*************BUILDING DENIED************
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) PROVIDE A KEY PLAN AND INSTALLATION
 SCHEDULE FOR THE STORM PANELS OR APPLY
 UNDER A SEPARATE PERMIT. REMOVABLE STORM
 PANELS CAN NOT BE USED ABOVE THE GROUND
 FLOOR. IMPACT RESISTANT GLAZING OR
 PERMANETLY AFFIXED PROTECTIVE DEVICES SH
 ALL BE INSTALLED. PERMANENTLY AFFIXED
 PROTECTIVE DEVICES REQUIRE THE WRITTEN
 APPROVAL OF THE BUILDING OFFICIAL.
  
 4) SHEET A1 IS MISSING THE FOOTING
 DESIGNATIONS. PLEASE CORRECT.
  
 5) PLEASE CLARIFY DETAIL 27/A11 AS TO
 HOW GABLE END WILL BE CONSTRUCTED AT THE
 VAULTED CEILING AT SECOND FLOOR BEDROOM.
  
 6) THE BALCONY RAIL IS SHOWN ON SHEET A5
 WITH A 4" SPACE BELOW THE BOTTOM RAIL.
 THIS WILL NOT REJECT A 2" SPHERE AS CODE
 REQUIRES. PLEASE CORRECT.
  
 7) THE FRONT ELEVATION ON A5 INDICATES A
 CEMENTITIOUS FINISH OVER CONCRETE BLOCK
 AT THE SECOND FLOOR BEDROOM, WHICH IS
 WOOD FRAME. PLEASE CORRECT.
  
 8) THE FIRE RATED DOORS BETWEEN THE
 UNITS AND THE GARAGE ARE REQUIRED TO
 HAVE APPROVED CLOSERS PER 97SBC SECT.
 705.1.3.5.
  
 9) THE RISE AND RUN DIMENSIONS ON DETAIL
 1/A7 DO NOT CORRESPOND WITH THOSE GIVEN
 IN SECTION B-B. TREADS EXCLUSIVE OF
 NOSING IS REQUIRED TO BE A MINIMUM OF 9"
 WIDE AND TREADS LESS THAN 10" WIDE ARE
 REQUIRED TO HAVE A NOSING OF APPROX. 1".
 97SBC SECT. 1007.3.2 & 1007.3.3 SECTION
 B-B INDICATES A 9.5" WIDE TREAD
 INCLUDING THE NOSING. PLEASE CORRECT.
  
 10) THE DIAPHRAM SCHEDULE ON A13 NOTES
 16"O.C. WALL FRAMING AND A7 INDICATES
 24" SPACING. PLEASE CORRECT.
  
 11) SECTION 8/A8 CALLS FOR 4"X24" SOFFIT
 VENTS SPACED 8'O.C. PROVIDE AN ATTIC
 AREA CALCULATION AND INCLUDE THE FREE
 AREA OF THE SOFFIT VENT SCREEN. ALSO,
 PLEASE SPECIFY THE "CEMENTITIOUS"
 SOFFIT MATERIAL.
  
 12) PROVIDE WINDOW, DOOR AND GARAGE DOOR
 BUCK FASTENING DETAILS.
  
 13)DETAILS 13 & 23 ON A11 ARE MISLABELED
 AS A17. PLEASE CORRECT.
  
 14) DETAIL 23 ON A11 MUST INDICATE THAT
 THE ONE HOUR TENANT SEPARATION IS
 MAINTAINED TO THE UNDERSIDE OF THE ROOF
 SHEATHING.
  
 15) PROVIDE AN ADDITIONAL COPY OF THE
 PRODUCT APPROVAL FOR THE FRONT DOOR.
 (TWO ARE REQUIRED)
  
 16) THE OPTIONS SHOWN ON SHEETS A17-A19
 MUST COMPLY WITH THE REQUIREMENTS OF THE
 FAIR HOUSING ACT.
  
 17) THE PA23 CONNECTOR LISTED IN DETAIL
 19 ON A11 FOR TRUSS GT2, IS A PURLIN
 ANCHOR AND IS NOT DESIGNED FOR USE AS A
 TRUSS ANCHOR.
  
 18) PLEASE SPECIFY A CONNECTOR OR
 CONNECTION DETAIL FOR TRUSS GT1. DETAIL
 32 ON A11 INDICATES THE ATTACHMENT OF
 THE WOOD FRAME WALL TO THE MASONRY.
  
 19) NO TRUSS DRAWINGS WERE SUBMITTED
 WITH THE TRUSS LAYOUTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2003-03-18 Cont ID  
Sent By btrobaug Date 2003-03-18 Time 17:06 Rev Time 0.75
Received By btrobaug Date 2003-03-18 Time 16:15 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-08-20 Cont ID  
Sent By sthyng Date 2003-03-12 Time 15:19 Rev Time 0.00
Received By dpalmer Date 2002-08-20 Time 08:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-08-13 Cont ID  
Sent By dpalmer Date 2002-08-13 Time 10:19 Rev Time 0.00
Received By dpalmer Date 2002-08-13 Time 10:18 Sent To  
Notes
2002-08-13 00:00:00************** UNSAT *****************
  
 PLEASE SEE NOTE ATTACHED FOR FS/FAC.
 PLEASE NOTE THAT PLANS BEING TURNED
 DOWN FOR THE SAME COMMENTS FOUR OR MORE
 TIMES ARE SUBJECT TO 4X FEE FOR PLAN
 REVIEW PORTION OF FEES.
  
 1)NOTE: PLEASE NOTE THAT ELECTRICAL
 RISER DIAGRAM IS STILL NOT SHOWING ANY
 MAINS? PLEASE NOTE PANELS SHOWN AS "MLO"
 PLEASE ALSO NOTE THAT NO MAINS ARE
 SHOWN ON PLANS. A-14.
  
  
 2)NOTE; PLEASE NOTE THAT AN EQUIPMENT
 GRND IS REQ`D BETWEEN MAINS AND PANELS.
 250-122
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PLAMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-07-09 Cont ID  
Sent By dpalmer Date 2002-07-09 Time 10:14 Rev Time 0.00
Received By dpalmer Date 2002-07-09 Time 10:12 Sent To  
Notes
2002-07-09 00:00:00*************** UNSAT ******************
  
  
 1)NOTE: PLEASE NOTE, NOT ALL NOTES FROM
 FIRST REVIEW WERE ADDRESSED. PLEASE SEE
 FIRST REVIEW NOTES.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-22 Cont ID  
Sent By dpalmer Date 2002-03-22 Time 07:05 Rev Time 0.00
Received By dpalmer Date 2002-03-22 Time 07:05 Sent To B
Notes
2002-03-22 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 SHOWS MAIN DISCONNECTS BETWEEN METERS
 AND PANELS. PLEASE SHOW LOCATION OF
 THESE DISC`SON PLANS.
 PLEASE NOTE THAT 150A PANELS HAVE NO
 INDICATION OF BEING "MCB" OR "MLO"
  
 2)NOTE: PLEASE NOTE THAT IF A MAIN
 DISCONNECT IS USED, THEN AN EQUIPMENT
 GROUNDING CONDUCTOR MAY IS REQ`D. SIZE
 PER 250-122.
  
 3)NOTE: PLEASE NOTE MISSING SD`S AT THE
 BOTTOM OF STAIRS FOR UPPER UNITS. PLEASE
 SEE NFPA-72 2-2.1.1.1/ 2-5.2.1.3.
  
 4)NOTE: PLEASE LIST THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE PER 210-12.
  
 5)NOTE: PLEASE NOTE MISSING SD`S FOR
 ROOMS THAT ARE ADAPTABLE SLEEPING ROOMS
 WITH CLOSETS AND/OR BATHS. NFPA-72
 2-2.1.1.1. UPPER UNIT/DEN.
  
 6)NOTE: PLEASE SEE OPT PAGE A-18, PLEASE
 NOTE MISSING MANY SD`S. INSIDE AND OUT-
 -SIDE ALL SLEEPING ROOMS AND ON EACH
 LEVEL OF MULTI LEVEL UNITS. SD`S ARE TO
 BE CLOSE VICINTY OF STAIRS ON EACH LEVEL
 .
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
 '
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2002-08-20 Cont ID  
Sent By mamini Date 2002-08-20 Time 15:24 Rev Time 1.00
Received By mamini Date 2002-08-20 Time 15:24 Sent To  
Notes
2002-08-20 00:00:00PASSED WITH PROVISOS:
 1. ITEMS 1 THROUGH 3 OF LAST REVIEW HAVE
 NOT BEEN ADDRESSED, CONTRACTOR WILL
 APPLY FOR CIVIL/SITE WORKS SEPARATELY.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2002-06-20 Cont ID  
Sent By mamini Date 2002-06-20 Time 09:32 Rev Time 1.00
Received By mamini Date 2002-06-20 Time 09:32 Sent To  
Notes
2002-06-20 00:00:00FAILED:
 1. PLEASE REFER TO THE PREVIOUS REVIEW
 COMMENTS DATED 4-30-02. ITEMS REQUESTED
 MUST BE PROVIDED FOR OUR REVIEW AND
 APPROVAL BEFOR ANY PERMIT FOR
 CONSTRUCTION CAN BE ISSUED.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2002-04-30 Cont ID  
Sent By mamini Date 2002-04-30 Time 10:34 Rev Time 1.00
Received By mamini Date 2002-04-30 Time 10:33 Sent To  
Notes
2002-04-30 00:00:00FAILED:
 1. PLEASE SUBMIT CIVIL/SITE PLANS FOR
 REVIEW AND APPROVAL.PLAN SHOULD ALSO
 INCLUDE STORM WATER CALCULATION,
 PERVIOUS AND IMPERVIOUS CALCULATION,
 POLLUTION PREVENTION PLANS.
 2. A SEPARATE PERMIT APPLICATION AND
 FEES FOR CIVIL / SITE WORKS WILL BE
 REQUIRED.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2003-03-26 Cont ID  
Sent By nmccray Date 2003-03-26 Time 11:12 Rev Time 0.00
Received By nmccray Date 2003-03-26 Time 11:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-07-05 Cont ID  
Sent By btrobaug Date 2003-03-18 Time 17:06 Rev Time 0.00
Received By mcarsill Date 2002-07-05 Time 11:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-04-19 Cont ID  
Sent By rmcdouga Date 2002-04-12 Time 16:15 Rev Time 0.00
Received By mcarsill Date 2002-04-19 Time 17:14 Sent To  
Notes
2002-04-19 00:00:00A) PLEASE INDICATE LOCATION OF NEAREST
 WET FIRE HYDRANT.
 B) SEVERAL REQUIRED SMOKE DETECTORS ARE
 MISSING FROM THE PLANS.
 C) PLEASE INDICATE ON THE PLANS THAT
 THE DENS ARE NOT TO BE USED FOR
 SLEEPING PURPOSES.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-03-12 Cont ID  
Sent By sthyng Date 2003-03-12 Time 15:19 Rev Time 0.00
Received By sthyng Date 2003-03-12 Time 15:19 Sent To E
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2003-04-07 Cont ID  
Sent By hmoser Date 2003-04-07 Time 08:35 Rev Time 0.50
Received By hmoser Date 2003-04-07 Time 08:34 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-08-20 Cont ID  
Sent By pkrauss Date 2002-08-20 Time 11:02 Rev Time 0.45
Received By pkrauss Date 2002-08-20 Time 10:31 Sent To  
Notes
2002-08-20 00:00:00MECHANICAL PERMIT 02022472

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-06-22 Cont ID  
Sent By pkrauss Date 2002-06-22 Time 11:02 Rev Time 0.45
Received By pkrauss Date 2002-06-22 Time 11:02 Sent To  
Notes
2002-06-22 00:00:00DENIED:
 2ND REQUEST -
 NO MANUAL J CALCULATIONS SUBMITTED WITH
 THE ENERGY CALCS.
  
 PLANS SUBMITTED ARE OKAY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-03-21 Cont ID  
Sent By hmoser Date 2002-03-21 Time 17:13 Rev Time 0.33
Received By hmoser Date 2002-03-21 Time 17:13 Sent To  
Notes
2002-03-21 00:00:00PLAN DENIED
 PLANS AND ENERGY CALCS DO NOT MATCH.
 PLANS SHOW FOR A/C UNIOTS.CALCS SHOW ONE
 NO MANUAL J
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-07-09 Cont ID  
Sent By kstevens Date 2002-07-09 Time 13:22 Rev Time 0.00
Received By kstevens Date 2002-07-09 Time 13:21 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-03-09 Cont ID  
Sent By jleech Date 2002-03-09 Time 09:26 Rev Time 1.00
Received By jleech Date 2002-03-09 Time 09:26 Sent To  
Notes
2002-03-09 00:00:00DENIED;
 1.PAGE A-16 PLUMBING RISER UNITS A & C.
 A.SECOND FLOOR MASTER BATH 3" RISER
 CANNOT DISCHARGE INTO 2" SHOWER
 DRAIN.
 B.W/C WET VENT. PIPE SIZE MUST
 INCREASE FROM 2" TO 3" WHEN THE
 FIXTURE LOAD IS MORE THAN 4 FU'S.
 2.PAGE A-16 PLUMBING RISER UNITS B & D.
 A. SEE NOTE 1-A & B.
 B.LAUNDRY TUB MISSING FOR UNIT D.
 3.SHOW DIMENSIONS FOR MASTER BATH W/C
 TO COMPLY WITH FHA 7.43. MOST CONST-
 UCTION COMPANY'S DO NOT HAVE THE FHA
 DESIGN MANUAL.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 EXT 8369

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-05 Cont ID  
Sent By gjoyce Date 2002-03-05 Time 09:05 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***