Plan Review Details - Permit 02022292
Plan Review Stops For Permit 02022292
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-08-14 Cont ID  
Sent By hpiskura Date 2002-08-14 Time 13:17 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-07-18 Cont ID  
Sent By hpiskura Date 2002-07-18 Time 14:39 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-07-18 00:00:00SHEETS A9 AND A10.ARCHITECT
 CLARIFY HOW THE ATTIC VENT CALCULATIONS
 WERE ARRIVED AT.AN ATTIC AREA OF 6240
 SQUARE FEET VENTILATED AT THE RATIO OF
 ONE SQUARE FOOT TO EACH 150 SQUARE FEET
 WILL REQUIRE 41.6 SQUARE FEET "NET FREE
 AREA", NOT THE TWENTY FIVE SQUARE FEET
 DECLARED.
  
 THE 4" X 24" SCREENED VENTS WILL LOSE
 AREA TO THE SPACE OCCUPIED BY THE
 SCREENING SOMEWHERE ON THE ORDER OF 40%
 TO 60%. THE NET FREE AREA OPENING OF
 THE VENT IS GENERALLY AVAILABLE FROM
 THE MANUFACTURER OF THE PRODUCT.
  
 THE PREVIOUSLY REQUESTED INFORMATION
 FOR"CEMENTITIOUS" SOFFIT MATERIAL HAS
 NOT
 BEEN PROVIDED.IT IS SOMEWHAT VAGUE
 AND LEAVES A GREAT DEAL TO THE
 IMAGINATION AS TO WHAT MAY APPEAR IN
 THE FINISHED PRODUCT.
  
 PLEASE BE A LITTLE MORE SPECIFIC, IE
 STUCCO OVER LATH, HARDIPANEL, DUROC,
 ETC.
  
 THE USE OF SHUTTERS ON MULTI STORY
 AND/OR MULTIPLE BUILDINGS IN A PROJECT
 ARE SUBJECT TO A SPECIAL EXCEPTION BY
 THE BUILDING OFFICIAL.
  
 THE INFORMATION IN THE METRO DADE NOA
 000602.04, BERTHA SHUTTERS, IS
 ILLEGIBLE.PLEASE PROVIDE CLEAR
 COPIES, IF APPROVED FOR FINAL USE AS
 NOTED ABOVE.
  
 NOA 011120.01 LAWSON MULLION HAS AN
 ILLEGIBLE DRAWING, PLEASE PROVIDE CLEAR
 COPIES.
  
 THE NOA 990803.05 PIONEER ROOF TILE IS
 EXPIRED.
  
 SBCCI REPORT 9606C CLOPAY GARAGE DOORS
 IS ILLEGIBLE.PLEASE PROVIDE CLEAR
 COPIES.
  
 RAMMS ENGINEERING RAILINGS.PLEASE
 PROVIDE COMPLETE CALCULATIONS,
 INCLUDING THE SOURCES USED FOR DESIGN
 IN THE "RATIONAL ANALYSIS" DECLARED.
 DEMONSTRATE COMPLIANCE WITH THE LOADS
 IN FBC 1608.2.2
  
 HOW WILL THE FOUR INCH PICKET SPACING
 DEPICTED IN THE "DECORATIVE OPTION" BE
 ACCOMPLISHED WITH FOUR 3/4" PICKETS?
  
 SPECIFY WHAT THE ANCHORS ARE SHOWN AS
 1/4" X 2 1/2" AND 1/4" X 3".INCLUDE IN
 CALCULATIONS THE LOAD VALUES ASSUMED.
  
 THIS PROJECT WILL REQUIRE A RESIDENT
 INSPECTOR, TO THAT END PLEASE PROVIDE
 PERMIT APPLICATION IN TRIPLICATE.
  
 BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED, IMPACT FEES MUST BE PAID TO THE
 COUNTY, THE PERMIT PLANS STAMPED BY
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-09 Cont ID  
Sent By hpiskura Date 2002-04-09 Time 08:40 Rev Time 0.00
Received By hpiskura Date 2002-04-08 Time 16:44 Sent To  
Notes
2002-04-09 00:00:00A COPY OF THE NOTES FROM 7507 ORCHID
 HAMMOCK 02022300 ARE ATTACHED TO THE
 PLANS.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2003-05-15 Cont ID  
Sent By dpalmer Date 2003-05-15 Time 15:14 Rev Time 0.50
Received By dpalmer Date 2003-05-15 Time 15:14 Sent To  
Notes
2003-05-15 00:00:00PLANS FOR FLR LAYOUT ONLY,
 RISER NOT REVISED

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-07-09 Cont ID  
Sent By shernand Date 2003-05-15 Time 09:23 Rev Time 0.00
Received By dpalmer Date 2002-07-09 Time 13:28 Sent To  
Notes
2002-07-09 00:00:00************ NOTE*****
 PLANS REDLINED WITH MISSING EQUIPMENT
 GROUNDING COND. BETWEEN MAIN DISC AND
 PANELS.
 ALSO REDLINED MAINS ON RISER DIAGRAM AS
 SHOWN ON A-14..

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-20 Cont ID  
Sent By dpalmer Date 2002-03-20 Time 06:27 Rev Time 0.00
Received By dpalmer Date 2002-03-20 Time 06:27 Sent To  
Notes
2002-03-20 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT IRSER DIAGRAM
 SHOWS MAIN DISCONNECTS BETWEEN METERS
 AND PANELS? PLEASE SHOW LOCATIONS OF
 THESE DISC`S ON PLANS.230-72.
 PLEASE NOTE THAT THERE IS NO INDICATION
 OF PANELS BEING "MLO" OR "MCB".?
  
 2)NOTE: PLEASE NOTE IF MAIN DISC`S ARE
 INSTALLED, THEN AN EQUIPMENT GROUNDING
 CONDUCTOR IS REQ`D BETWEEN MAIN DISC AND
 PANEL. SIZE PER 250-122.
  
 3)NOTE: PLEASE NOTE MISSING SD`S AT THE
 BOTTOM OF STAIRS FOR UPPER UNITS,PER
 NFPA-72 2-2.1.1.1,2-5.2.1.3
  
 4)NOTE: PLEASE LIST THE REQ`D ACR FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULES
 PER 210-12.
  
 5)NOTE: PLEASE SEE OPT PAGE A-18. PLEASE
 NOTE MISSING MANY SD`S.
 SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2002-09-12 Cont ID  
Sent By mamini Date 2002-09-12 Time 09:13 Rev Time 1.00
Received By mamini Date 2002-09-12 Time 09:13 Sent To  
Notes
2002-09-12 00:00:00N/A
 1. SEE PERMIT # 02090588 FOR CIVIL/SITE
 REVIEW AND COMMENTS.
 IF ANY QUESTION PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2002-08-20 Cont ID  
Sent By mamini Date 2002-08-19 Time 14:00 Rev Time 1.00
Received By mamini Date 2002-08-19 Time 13:59 Sent To  
Notes
2002-08-19 00:00:00FAILED:
 1. ITEMS 1 THROUGH 3 OF LAST REVIEW HAVE
 NOT BEEN ADDRESSED , CONTRACTOR WILL
 APPLY FOR CIVIL/ SITE WORKS SEPARATELY.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2002-06-20 Cont ID  
Sent By mamini Date 2002-06-20 Time 10:29 Rev Time 1.00
Received By mamini Date 2002-06-20 Time 10:29 Sent To  
Notes
2002-06-20 00:00:00FAILED :
 1. PLEASE SUMIT CIVIL/ SITE PLANS FOR
 OUR REVIEW AND APPROVAL. PLANS SHOULD
 ALSO INCLUDE STORM WATER CALCULATIONS,
 PERVIOUS AND IMPERVIOUS CALCULATIONS AND
 POLLUTION / EROSION PREVENTION PLAN.
 2. PLEASE SUBMIT A COPY OF NORTHERN
 PERMIT.
 3. A SEPARATE PERMIT APPLICATION AND
 FEES FOR CIVIL / SITE WORKS WILL BE
 REQUIRED.
 IF ANY QUESTIONS PLEASE CONTACT 659-8096
 EXT. 8492 MOHAMMAD R. AMINI

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-07-19 Cont ID  
Sent By mcarsill Date 2002-07-19 Time 09:45 Rev Time 0.00
Received By mcarsill Date 2002-07-19 Time 09:45 Sent To  
Notes
2002-07-19 00:00:00APPROVED BY FIRE ON 6.21.02

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-04-03 Cont ID  
Sent By mcarsill Date 2002-04-03 Time 10:22 Rev Time 0.00
Received By mcarsill Date 2002-04-03 Time 10:22 Sent To  
Notes
2002-04-03 00:00:00A) PLANS INDICATE THAT SMOKE DETECTORS
 ARE MISSING.
 B) WET FIRE HYDRANTS ARE REQUIRED PRIOR
 TO, DURING AND AFTER CONSTRUCTION.
 C) ELECTRIC POWERED SMOKE DETECTORS
 REQUIRED.
 D) NO SMOKE DETECTORS SHOWN IN THE DEN.
 PLEASE INDICATE THAT THE DEN IS NOT TO
 BE USED FOR SLEEPING OR PROVIDE PROPER
 SMOKE DETECTION.
 E) BUILDING ADDRESS REQUIRED ON BUILDING
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-05-15 Cont ID  
Sent By shernand Date 2003-05-15 Time 09:23 Rev Time 0.00
Received By shernand Date 2003-05-15 Time 09:23 Sent To E
Notes
2003-05-15 00:00:00DP DESK

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-03-28 Cont ID  
Sent By pkrauss Date 2002-03-28 Time 13:47 Rev Time 0.40
Received By pkrauss Date 2002-03-28 Time 13:30 Sent To  
Notes
2002-03-28 00:00:00MECHANICAL PERMIT 02030575
  
 PROVISO:
  
 PLEASE SUBMIT SPECIFIC MANUFACTURER FOR
 DRYERS SHOWING CONCURRENCE WITH DRYER
 EXHAUST INFORMATION INDICATED ON PLAN
 SHEET A-3 DETAIL 3.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-07-10 Cont ID  
Sent By kstevens Date 2002-07-10 Time 15:20 Rev Time 0.00
Received By kstevens Date 2002-07-10 Time 15:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-04-01 Cont ID  
Sent By kstevens Date 2002-04-01 Time 10:42 Rev Time 0.00
Received By kstevens Date 2002-04-01 Time 10:42 Sent To  
Notes
2002-04-01 00:00:00DENIED
 REFERENCE: SPC-94 - FHA AMEND-98 DESIGN
 MANUAL
  
 1) SHT-A-16 SANITARY RISER DIAGRAM UNITS
 "A" & "C" - BATH #3 FROM "C" UNIT SHALL
 NOT DRAIN PAST LAUNDRY TRAY ON FIRST
 FLOOR. BATH #3 SHALL BE TAKEN OFF BELOW
 LAUNDRY TRAY.
 2) SHT A-16 SANITARY RISER DIAGRAM UNITS
 "A" & "C" - MASTER BATH FROM "C" UNIT
 SHALL NOT DRAIN INTO 2" DRAIN FROM SHOW-
 ER. RISER FOR MASTER BATH SHALL BE TAKEN
 OFF BEFORE MASTER BATH IN "A" UNIT.
 3) SHT A-16 SANITARY RISER DIAGRAM UNITS
 "B" & "D" - LAUNDRY TRAY NOT SHOWN FOR
 UNIT "D".
 4) SHT A-16 SANITARY RISER DIAGRAM UNITS
 "B" & "D" - MASTER BATH FROM "D" UNIT
 SHALL NOT DRAIN INTO 2" DRAIN FROM SHOW-
 ER. RISER FOR MASTER BATH SHALL BE TAKEN
 OFF BEFORE MASTER BATH IN "B" UNIT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 2 Status P Date 2002-08-20 Cont ID  
Sent By sgraham Date 2002-08-20 Time 12:51 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-06 Cont ID  
Sent By gjoyce Date 2002-03-06 Time 11:29 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***