| Plan Review Stops For Permit 02022292 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-08-14 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-08-14 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-07-18 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-07-18 |
Time |
14:39 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-07-18 00:00:00 | SHEETS A9 AND A10.ARCHITECT | | | CLARIFY HOW THE ATTIC VENT CALCULATIONS | | | WERE ARRIVED AT.AN ATTIC AREA OF 6240 | | | SQUARE FEET VENTILATED AT THE RATIO OF | | | ONE SQUARE FOOT TO EACH 150 SQUARE FEET | | | WILL REQUIRE 41.6 SQUARE FEET "NET FREE | | | AREA", NOT THE TWENTY FIVE SQUARE FEET | | | DECLARED. | | | | | | THE 4" X 24" SCREENED VENTS WILL LOSE | | | AREA TO THE SPACE OCCUPIED BY THE | | | SCREENING SOMEWHERE ON THE ORDER OF 40% | | | TO 60%. THE NET FREE AREA OPENING OF | | | THE VENT IS GENERALLY AVAILABLE FROM | | | THE MANUFACTURER OF THE PRODUCT. | | | | | | THE PREVIOUSLY REQUESTED INFORMATION | | | FOR"CEMENTITIOUS" SOFFIT MATERIAL HAS | | | NOT | | | BEEN PROVIDED.IT IS SOMEWHAT VAGUE | | | AND LEAVES A GREAT DEAL TO THE | | | IMAGINATION AS TO WHAT MAY APPEAR IN | | | THE FINISHED PRODUCT. | | | | | | PLEASE BE A LITTLE MORE SPECIFIC, IE | | | STUCCO OVER LATH, HARDIPANEL, DUROC, | | | ETC. | | | | | | THE USE OF SHUTTERS ON MULTI STORY | | | AND/OR MULTIPLE BUILDINGS IN A PROJECT | | | ARE SUBJECT TO A SPECIAL EXCEPTION BY | | | THE BUILDING OFFICIAL. | | | | | | THE INFORMATION IN THE METRO DADE NOA | | | 000602.04, BERTHA SHUTTERS, IS | | | ILLEGIBLE.PLEASE PROVIDE CLEAR | | | COPIES, IF APPROVED FOR FINAL USE AS | | | NOTED ABOVE. | | | | | | NOA 011120.01 LAWSON MULLION HAS AN | | | ILLEGIBLE DRAWING, PLEASE PROVIDE CLEAR | | | COPIES. | | | | | | THE NOA 990803.05 PIONEER ROOF TILE IS | | | EXPIRED. | | | | | | SBCCI REPORT 9606C CLOPAY GARAGE DOORS | | | IS ILLEGIBLE.PLEASE PROVIDE CLEAR | | | COPIES. | | | | | | RAMMS ENGINEERING RAILINGS.PLEASE | | | PROVIDE COMPLETE CALCULATIONS, | | | INCLUDING THE SOURCES USED FOR DESIGN | | | IN THE "RATIONAL ANALYSIS" DECLARED. | | | DEMONSTRATE COMPLIANCE WITH THE LOADS | | | IN FBC 1608.2.2 | | | | | | HOW WILL THE FOUR INCH PICKET SPACING | | | DEPICTED IN THE "DECORATIVE OPTION" BE | | | ACCOMPLISHED WITH FOUR 3/4" PICKETS? | | | | | | SPECIFY WHAT THE ANCHORS ARE SHOWN AS | | | 1/4" X 2 1/2" AND 1/4" X 3".INCLUDE IN | | | CALCULATIONS THE LOAD VALUES ASSUMED. | | | | | | THIS PROJECT WILL REQUIRE A RESIDENT | | | INSPECTOR, TO THAT END PLEASE PROVIDE | | | PERMIT APPLICATION IN TRIPLICATE. | | | | | | BEFORE A PERMIT TO CONSTRUCT MAY BE | | | ISSUED, IMPACT FEES MUST BE PAID TO THE | | | COUNTY, THE PERMIT PLANS STAMPED BY | | | RECEIPT ATTACHED TO THE PERMIT | | | APPLICATION.CALL 561-233-5025 FOR | | | MORE INFORMATION. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-04-09 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-04-09 |
Time |
08:40 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-04-08 |
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2002-04-09 00:00:00 | A COPY OF THE NOTES FROM 7507 ORCHID | | | HAMMOCK 02022300 ARE ATTACHED TO THE | | | PLANS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2003-05-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-05-15 |
Time |
15:14 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-05-15 |
Time |
15:14 |
Sent To |
|
|
| Notes |
| 2003-05-15 00:00:00 | PLANS FOR FLR LAYOUT ONLY, | | | RISER NOT REVISED |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-07-09 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-15 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-07-09 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2002-07-09 00:00:00 | ************ NOTE***** | | | PLANS REDLINED WITH MISSING EQUIPMENT | | | GROUNDING COND. BETWEEN MAIN DISC AND | | | PANELS. | | | ALSO REDLINED MAINS ON RISER DIAGRAM AS | | | SHOWN ON A-14.. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-03-20 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-20 |
Time |
06:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-03-20 |
Time |
06:27 |
Sent To |
|
|
| Notes |
| 2002-03-20 00:00:00 | ****************** UNSAT ************* | | | | | | 1)NOTE: PLEASE NOTE THAT IRSER DIAGRAM | | | SHOWS MAIN DISCONNECTS BETWEEN METERS | | | AND PANELS? PLEASE SHOW LOCATIONS OF | | | THESE DISC`S ON PLANS.230-72. | | | PLEASE NOTE THAT THERE IS NO INDICATION | | | OF PANELS BEING "MLO" OR "MCB".? | | | | | | 2)NOTE: PLEASE NOTE IF MAIN DISC`S ARE | | | INSTALLED, THEN AN EQUIPMENT GROUNDING | | | CONDUCTOR IS REQ`D BETWEEN MAIN DISC AND | | | PANEL. SIZE PER 250-122. | | | | | | 3)NOTE: PLEASE NOTE MISSING SD`S AT THE | | | BOTTOM OF STAIRS FOR UPPER UNITS,PER | | | NFPA-72 2-2.1.1.1,2-5.2.1.3 | | | | | | 4)NOTE: PLEASE LIST THE REQ`D ACR FAULT | | | PROTECTED CIRCUITS ON PANEL SCHEDULES | | | PER 210-12. | | | | | | 5)NOTE: PLEASE SEE OPT PAGE A-18. PLEASE | | | NOTE MISSING MANY SD`S. | | | SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
N |
Date |
2002-09-12 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2002-09-12 |
Time |
09:13 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2002-09-12 |
Time |
09:13 |
Sent To |
|
|
| Notes |
| 2002-09-12 00:00:00 | N/A | | | 1. SEE PERMIT # 02090588 FOR CIVIL/SITE | | | REVIEW AND COMMENTS. | | | IF ANY QUESTION PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
F |
Date |
2002-08-20 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2002-08-19 |
Time |
14:00 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2002-08-19 |
Time |
13:59 |
Sent To |
|
|
| Notes |
| 2002-08-19 00:00:00 | FAILED: | | | 1. ITEMS 1 THROUGH 3 OF LAST REVIEW HAVE | | | NOT BEEN ADDRESSED , CONTRACTOR WILL | | | APPLY FOR CIVIL/ SITE WORKS SEPARATELY. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
F |
Date |
2002-06-20 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2002-06-20 |
Time |
10:29 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2002-06-20 |
Time |
10:29 |
Sent To |
|
|
| Notes |
| 2002-06-20 00:00:00 | FAILED : | | | 1. PLEASE SUMIT CIVIL/ SITE PLANS FOR | | | OUR REVIEW AND APPROVAL. PLANS SHOULD | | | ALSO INCLUDE STORM WATER CALCULATIONS, | | | PERVIOUS AND IMPERVIOUS CALCULATIONS AND | | | POLLUTION / EROSION PREVENTION PLAN. | | | 2. PLEASE SUBMIT A COPY OF NORTHERN | | | PERMIT. | | | 3. A SEPARATE PERMIT APPLICATION AND | | | FEES FOR CIVIL / SITE WORKS WILL BE | | | REQUIRED. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-07-19 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-07-19 |
Time |
09:45 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-07-19 |
Time |
09:45 |
Sent To |
|
|
| Notes |
| 2002-07-19 00:00:00 | APPROVED BY FIRE ON 6.21.02 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-04-03 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-04-03 |
Time |
10:22 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-04-03 |
Time |
10:22 |
Sent To |
|
|
| Notes |
| 2002-04-03 00:00:00 | A) PLANS INDICATE THAT SMOKE DETECTORS | | | ARE MISSING. | | | B) WET FIRE HYDRANTS ARE REQUIRED PRIOR | | | TO, DURING AND AFTER CONSTRUCTION. | | | C) ELECTRIC POWERED SMOKE DETECTORS | | | REQUIRED. | | | D) NO SMOKE DETECTORS SHOWN IN THE DEN. | | | PLEASE INDICATE THAT THE DEN IS NOT TO | | | BE USED FOR SLEEPING OR PROVIDE PROPER | | | SMOKE DETECTION. | | | E) BUILDING ADDRESS REQUIRED ON BUILDING | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-05-15 |
|
|
Cont ID |
|
| Sent By |
shernand |
Date |
2003-05-15 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
shernand |
Date |
2003-05-15 |
Time |
09:23 |
Sent To |
E |
|
| Notes |
| 2003-05-15 00:00:00 | DP DESK |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-03-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-28 |
Time |
13:47 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-03-28 |
Time |
13:30 |
Sent To |
|
|
| Notes |
| 2002-03-28 00:00:00 | MECHANICAL PERMIT 02030575 | | | | | | PROVISO: | | | | | | PLEASE SUBMIT SPECIFIC MANUFACTURER FOR | | | DRYERS SHOWING CONCURRENCE WITH DRYER | | | EXHAUST INFORMATION INDICATED ON PLAN | | | SHEET A-3 DETAIL 3. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-07-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-07-10 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-07-10 |
Time |
15:20 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-04-01 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-04-01 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-04-01 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2002-04-01 00:00:00 | DENIED | | | REFERENCE: SPC-94 - FHA AMEND-98 DESIGN | | | MANUAL | | | | | | 1) SHT-A-16 SANITARY RISER DIAGRAM UNITS | | | "A" & "C" - BATH #3 FROM "C" UNIT SHALL | | | NOT DRAIN PAST LAUNDRY TRAY ON FIRST | | | FLOOR. BATH #3 SHALL BE TAKEN OFF BELOW | | | LAUNDRY TRAY. | | | 2) SHT A-16 SANITARY RISER DIAGRAM UNITS | | | "A" & "C" - MASTER BATH FROM "C" UNIT | | | SHALL NOT DRAIN INTO 2" DRAIN FROM SHOW- | | | ER. RISER FOR MASTER BATH SHALL BE TAKEN | | | OFF BEFORE MASTER BATH IN "A" UNIT. | | | 3) SHT A-16 SANITARY RISER DIAGRAM UNITS | | | "B" & "D" - LAUNDRY TRAY NOT SHOWN FOR | | | UNIT "D". | | | 4) SHT A-16 SANITARY RISER DIAGRAM UNITS | | | "B" & "D" - MASTER BATH FROM "D" UNIT | | | SHALL NOT DRAIN INTO 2" DRAIN FROM SHOW- | | | ER. RISER FOR MASTER BATH SHALL BE TAKEN | | | OFF BEFORE MASTER BATH IN "B" UNIT. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2002-08-20 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-08-20 |
Time |
12:51 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-03-06 |
|
|
Cont ID |
|
| Sent By |
gjoyce |
Date |
2002-03-06 |
Time |
11:29 |
Rev Time |
0.25 |
| Received By |
gjoyce |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|