Plan Review Details - Permit 02022214
| Plan Review Stops For Permit 02022214 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-05-23 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-05-23 |
Time |
14:43 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-05-23 00:00:00 | SHEET M1 REVISION DATE 4/15/02.THE | | | DUCT WORK SHOWN AS "EXISTING" IN THE | | | PARTIAL 2ND 3RD FLOOR PLAN AT STAIR #3 | | | IS A CODE VIOLATION AS NOTED | | | PREVIOUSLY, AND WOULD HAVE BEEN A CODE | | | VIOLATION AT THE TIME IT WAS | | | CONSTRUCTED.SEE SBC 104.6.1 AND SBC | | | 1006.1.3. | | | | | | THIS PERMIT IS BEING ISSUED WITH THE | | | PROVISO THAT ANOTHER PERMIT BE TAKEN TO | | | CORRECT THE ABOVE CODE VIOLATIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-03-19 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-03-19 |
Time |
09:35 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-19 00:00:00 | SHEETS M1 AND E1, SBC 1006.1.3 PROHIBITS | | | THE USE OF STAIR ENCLOSURES FOR | | | PURPOSES OTHER THAN MEANS OF EGRESS. | | | PLEASE REVISE AS NECESSARY. | | | | | | PLEASEPROVIDE ENERGY CODE CALCULATIONS |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2002-03-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-05 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-03-05 |
Time |
11:09 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-05-22 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-05-22 |
Time |
10:52 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-05-22 |
Time |
10:52 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-03-01 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-03-01 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-03-01 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2002-03-01 00:00:00 | A) IT WAS NOTED THAT EQUIPMENT APPEARS | | | TO BE RUNNING THROUGH EXIT(S). PLEASE | | | BE ADVISED THAT THE ONLY PENETRATIONS | | | ALLOWED ARE: ELECTRICAL CONDUIT SERVING | | | THE STAIRWAY, REQUIRED EXIT DOORS, | | | DUCTWORK AND EQUIPMENT NECESSARY FOR | | | INDEPENDENT STAIR PRESSURIZATION, WATER | | | OR STEAM PIPING FOR HEATING AND COOLING | | | OF THE EXIT ENCLOSURE, SPRINKLER | | | PIPING, STANDPIPES. RE: NFPA 101, | | | THE LIFE SAFETY CODE, 2000 EDITION, | | | SECTION 7.1.3.2.1 (E). | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-05-22 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-22 |
Time |
12:07 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-05-22 |
Time |
12:07 |
Sent To |
|
|
| Notes |
| 2002-05-22 00:00:00 | PERMIT IS FOR CLOUDED AREAS ONLY. | | | MECHANICAL PERMIT 02022216 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-03-04 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-04 |
Time |
13:17 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-03-04 |
Time |
13:01 |
Sent To |
|
|
| Notes |
| 2002-03-04 00:00:00 | *******************DENIED*************** | | | | | | AS PER 1997 SBC 1006.1.3.1, | | | PENETRATIONS INTO AND OPENINGS THROUGH A | | | STAIRWAY ENCLOSURE ARE PROHIBITED. | | | | | | AS PER NFPA 90A 3-3.4.3, SHAFTS THAN | | | ENCLOSE AIR DUCTS SHALL NOT ENCLOSE: | | | (F) PIPING. | | | | | | CONDENSER UNIT - EQUIPMENT RAILS - | | | 18" MINIMUM BETWEEN THE ROOF SURFACE AND | | | THE BOTTOM OF THE SUPPORT RAIL AS PER | | | COUNTYWIDE AMENDMENTS 1997 SMC 304.2.5 | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
|