Plan Review Details - Permit 02022214
Plan Review Stops For Permit 02022214
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-05-23 Cont ID  
Sent By hpiskura Date 2002-05-23 Time 14:43 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-05-23 00:00:00SHEET M1 REVISION DATE 4/15/02.THE
 DUCT WORK SHOWN AS "EXISTING" IN THE
 PARTIAL 2ND 3RD FLOOR PLAN AT STAIR #3
 IS A CODE VIOLATION AS NOTED
 PREVIOUSLY, AND WOULD HAVE BEEN A CODE
 VIOLATION AT THE TIME IT WAS
 CONSTRUCTED.SEE SBC 104.6.1 AND SBC
 1006.1.3.
  
 THIS PERMIT IS BEING ISSUED WITH THE
 PROVISO THAT ANOTHER PERMIT BE TAKEN TO
 CORRECT THE ABOVE CODE VIOLATIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-03-19 Cont ID  
Sent By hpiskura Date 2002-03-19 Time 09:35 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-03-19 00:00:00SHEETS M1 AND E1, SBC 1006.1.3 PROHIBITS
 THE USE OF STAIR ENCLOSURES FOR
 PURPOSES OTHER THAN MEANS OF EGRESS.
 PLEASE REVISE AS NECESSARY.
  
 PLEASEPROVIDE ENERGY CODE CALCULATIONS

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-05 Cont ID  
Sent By dpalmer Date 2002-03-05 Time 11:09 Rev Time 0.00
Received By dpalmer Date 2002-03-05 Time 11:09 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-05-22 Cont ID  
Sent By mcarsill Date 2002-05-22 Time 10:52 Rev Time 0.00
Received By mcarsill Date 2002-05-22 Time 10:52 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-03-01 Cont ID  
Sent By mcarsill Date 2002-03-01 Time 16:17 Rev Time 0.00
Received By mcarsill Date 2002-03-01 Time 16:17 Sent To  
Notes
2002-03-01 00:00:00A) IT WAS NOTED THAT EQUIPMENT APPEARS
 TO BE RUNNING THROUGH EXIT(S). PLEASE
 BE ADVISED THAT THE ONLY PENETRATIONS
 ALLOWED ARE: ELECTRICAL CONDUIT SERVING
 THE STAIRWAY, REQUIRED EXIT DOORS,
 DUCTWORK AND EQUIPMENT NECESSARY FOR
 INDEPENDENT STAIR PRESSURIZATION, WATER
 OR STEAM PIPING FOR HEATING AND COOLING
 OF THE EXIT ENCLOSURE, SPRINKLER
 PIPING, STANDPIPES. RE: NFPA 101,
 THE LIFE SAFETY CODE, 2000 EDITION,
 SECTION 7.1.3.2.1 (E).
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-05-22 Cont ID  
Sent By pkrauss Date 2002-05-22 Time 12:07 Rev Time 0.40
Received By pkrauss Date 2002-05-22 Time 12:07 Sent To  
Notes
2002-05-22 00:00:00PERMIT IS FOR CLOUDED AREAS ONLY.
 MECHANICAL PERMIT 02022216

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-03-04 Cont ID  
Sent By pkrauss Date 2002-03-04 Time 13:17 Rev Time 0.40
Received By pkrauss Date 2002-03-04 Time 13:01 Sent To  
Notes
2002-03-04 00:00:00*******************DENIED***************
  
 AS PER 1997 SBC 1006.1.3.1,
 PENETRATIONS INTO AND OPENINGS THROUGH A
 STAIRWAY ENCLOSURE ARE PROHIBITED.
  
 AS PER NFPA 90A 3-3.4.3, SHAFTS THAN
 ENCLOSE AIR DUCTS SHALL NOT ENCLOSE:
 (F) PIPING.
  
 CONDENSER UNIT - EQUIPMENT RAILS -
 18" MINIMUM BETWEEN THE ROOF SURFACE AND
 THE BOTTOM OF THE SUPPORT RAIL AS PER
 COUNTYWIDE AMENDMENTS 1997 SMC 304.2.5
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.