Plan Review Details - Permit 02022196
Plan Review Stops For Permit 02022196
Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-09-26 Cont ID  
Sent By mcarsill Date 2002-09-26 Time 13:35 Rev Time 0.00
Received By mcarsill Date 2002-09-26 Time 13:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-02-28 Cont ID  
Sent By mcarsill Date 2002-02-28 Time 12:45 Rev Time 0.00
Received By mcarsill Date 2002-02-28 Time 12:45 Sent To  
Notes
2002-02-28 00:00:00A) PLEASE INDICATE WHAT THE VOICE
 EVACUATION MESSAGE PORTION OF THE
 FIRE ALARM SYSTEM WILL SAY. THIS
 INFORMATION SHOULD BE PLACED ON THE
 PLANS.
 B) PLEASE PROVIDE A SIGNED CONTRACT FOR
 THE INSTALLATION OF THE FIRE ALARM
 SYSTEM. THE VALUE LISTED ON THE PERMIT
 APPLICATION SEEMS TOO LOW.
 C) PLEASE INDICATE ELEVATOR OPERATION
 WHEN THE FIRE ALARM SYSTEM ACTIVATES.
 D) THE FIRE ALARM SPEAKER IN KITCHEN
 B14 NOT CONNECTED.
 E) SOME DEVICES IN CONGESTED AREAS
 ON THE PLANS ARE DIFFICULT TO
 SEPARATE FROM OTHER DEVICES.
 F) PLEASE INDICATE WHAT SERVICE ROOMS
 WITHIN THE BUILDING ARE EQUIPPED WITH
 SMOKE OR HEAT DETECTORS.
 G) WHEN THE BUILDING FIRE ALARM SYSTEM
 ACTIVATES, DOES THE ENTIRE BUILDING GO
 INTO FIRE ALARM MODE OR IS IT THE
 FLOOR OF INCIDENT, FLOOR ABOVE AND FLOOR
 BELOW.
 H) PLEASE EXPLAIN HOW PENETRATIONS
 ARE GOING TO BE SEALED FOR RATED FLOORS
 AND WALLS.
  
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910