Plan Review Details - Permit 02022186
Plan Review Stops For Permit 02022186
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-05-17 Cont ID  
Sent By pkrauss Date 2002-05-15 Time 11:18 Rev Time 0.00
Received By rbrown Date 2002-05-17 Time 14:03 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-03-27 Cont ID  
Sent By rbrown Date 2002-03-27 Time 18:00 Rev Time 0.00
Received By rbrown Date 2002-03-27 Time 18:00 Sent To  
Notes
2002-03-27 00:00:00BUILDING PLAN REVIEW
 ******PROVISO*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 --PROVISO--
 FBC 11-7.2(1)THE HEIGHT OF THE SALES
 COUNTER IS NOT SHOWN.AT LEAST A 36"
 LENGTH OF COUNTER SHALL HAVE A MAXIMUM
 HEIGHT OF 36" ABOVE FINISHED FLOOR LEVEL
 TO SATISFY THE REQUIREMENT FOR AN
 ACCESSIBLE SALES COUNTER.
  
 --PROVISO--
 THE APPLICANT'S NOTE ON THE PERMIT
 APPLICATION FORM REQUESTS THAT THE PLANS
 BE REVIEWED FOR COMPLIANCE WITH THE
 FLORIDA BUILDING CODE.THEREFOR,
 SHEET A-1, 'CODE CLASSIFICATION', MUST
 BE AMENDED TO REFER TO THE FLORIDA
 BULDING CODE 2001, BUILDING VOLUME,
 FUEL GAS VOLUME, MECHANICAL VOLUME AND
 PLUMBING VOLUME.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-06 Cont ID  
Sent By dpalmer Date 2002-05-06 Time 19:10 Rev Time 0.00
Received By dpalmer Date 2002-05-06 Time 19:09 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-12 Cont ID  
Sent By dpalmer Date 2002-03-12 Time 06:31 Rev Time 0.00
Received By dpalmer Date 2002-03-12 Time 06:31 Sent To  
Notes
2002-03-12 00:00:00**************** UNSAT ****************
  
 1)NOTE: PLEASE NOTE A COMPLETELY
 DIFFERENT ELECTRICAL PLAN IS NOW SUBMITT
 -ED?? THE RESPONSE SHEET FROM ARCH? SAYS
 COMMENTS WERE ADDRESSED?
  
 2)NOTE: PLEASE NOTE NO LOAD CALCUALTIONS
 , PANEL SIZE, PANEL SCHEDULE, RISER
 DIAGRAM,,,,, NEC 215-5, NEC 220.
  
 3)NOTE: PLEASE NOTE THAT ALL CIRCUIT #`S
 ARE TO BE SHOWN ON PLANS AND CORRELATE
 WITH A SUBMITTED PANEL SCHEDULE.
  
 4)NOTE: PLEASE SUBMIT AN EQUIPMENT
 SCHEDULE.
  
 5)NOTE: PLEASE NOTE THAT COVER SHEET
 REFERENCES THE 1997 NEC?? PLEASE NOTE
 THERE IS NO "97" NEC. PLEASE ALSO NOTE
 THAT WE ARE UNDER THE "99" NEC. PLEASE
 CORRECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
 PLEASE ADDRESS ANY FIRE REVIEW COMMENTS
 THAT MAY AFFECT ELECTRICAL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-03-18 Cont ID  
Sent By drunnels Date 2002-03-18 Time 15:25 Rev Time 0.00
Received By drunnels Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-07-30 Cont ID  
Sent By mcarsill Date 2002-07-30 Time 17:00 Rev Time 0.00
Received By mcarsill Date 2002-07-30 Time 17:00 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-05-08 Cont ID  
Sent By mcarsill Date 2002-05-08 Time 12:56 Rev Time 0.00
Received By mcarsill Date 2002-05-08 Time 12:56 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-03-06 Cont ID  
Sent By mcarsill Date 2002-03-06 Time 10:39 Rev Time 0.00
Received By mcarsill Date 2002-03-06 Time 10:39 Sent To  
Notes
2002-03-06 00:00:00A) WRONG LIFE SAFETY CODE REFERENCED.
 SHOULD READ 2000 EDITION OF THE LIFE
 SAFETY CODE, NOT 1997 EDITION.
 B) ANY FURNITURE PLANNED FOR THE WAITING
 ROOM.
 C) PLEASE IDENTIFY RATING OF TENANT
 DEMISING WALLS.
 D) PRODUCT APPROVAL WILL BE REQUIRED FOR
 FIREWRAP MATERIAL WHEN THE SEPARATE
 PLANS AND PERMITS ARE SUBMITTED FOR
 THE HOOD,DUCT,AND EXTINGUISHING SYSTEM.
 E) INTERIOR FINISH CLASSIFICATION
 INFORMATION NEEDS TO BE FURTHER DEFINED.
 F) PLANS DO NOT INDICATE IF FIRE
 SPRINKLERS ARE PRESENT.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-05-15 Cont ID  
Sent By pkrauss Date 2002-05-15 Time 11:17 Rev Time 0.35
Received By pkrauss Date 2002-05-15 Time 11:17 Sent To B
Notes
2002-05-15 00:00:00APPROVED 5-10-02

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-03-20 Cont ID  
Sent By pkrauss Date 2002-03-20 Time 07:11 Rev Time 0.45
Received By pkrauss Date 2002-03-20 Time 07:08 Sent To  
Notes
2002-03-20 00:00:00********************DENIED**************
  
 PLANS REVIEWED UNDER THE 2001 FBC, MECH.
  
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER 2001 FBC, MECHANICAL 403.3.
  
 2.PROVIDE AIR BALANCE SCHEDULE SHOWING
 COMPLIANCE WITH 502.1.
  
 3.PROVIDE EQUIPMENT INFORMATION FOR
 THE HVAC SYSTEM, FAN SCHEDULE FOR
 ANY EXHAUST/AIR MAKE-UP.
  
 4.INDICATE DUCT LAYOUT, MATERIAL, SIZE
 AND CFM DISTRIBUTION.
  
 ADDITIONAL PERMITS REQUIRED FOR HOOD,
 FIRE SUPRESSION, GAS, AND WALK-IN
 COOLERS/FREEZERS.PLEASE PROVIDE PLANS
 AND MANUFACTURERS SUBMITTAL
 DATA/PRODUCT APPROVALS WITH PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESITONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-05-24 Cont ID  
Sent By kstevens Date 2002-05-24 Time 16:26 Rev Time 0.00
Received By kstevens Date 2002-05-24 Time 16:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-05-17 Cont ID  
Sent By kstevens Date 2002-05-17 Time 16:17 Rev Time 0.00
Received By kstevens Date 2002-05-17 Time 16:17 Sent To  
Notes
2002-05-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 FUEL GAS
 FBC-2001 CHAPTER 11 FACBC
  
 1) FROM PREVIOUS REVIEW, PLEASE CONTACT
 RONDEY COMPO, ENVIRONMENTAL CONPLIANCE
 TO SIZE GREASE TRAP. (561) 837-4074.
 UTILITY ORDINANCE #2938-96
 2) TABLE 403.1 REQUIRED A DRINKING
 FOUNTAIN. ALSO SEE SECTION 410.1, IF A
 DRINKING COOLER IS USED IT SHALL COMPLY
 WITH ARI-1010. PLEASE SUBMIT MANUFACTURE
 INFORMATION SHEETS SHOWING COMPLIANCE.
 3) 140 DEGREE WATER REQUIRED FOR THREE
 COMPARTMENT SINK AND JANITOR MOP SINK.
 PLEASE PROVIDE TO THESE FIXTURES BEFORE
 TEMPERING WATER FOR OTHER FIXTURES.
 4) PLEASE REROUTE NEW PLANS TO DEPART-
 MENT OF BUSINESS REGULATION HOTEL AND
 RESTURANT DIVISION TO BE STAMPED BEFORE
 RESUBMITTING FOR PLAN REVIEW.
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND FBC-2001
 FUEL GAS CODE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-03-19 Cont ID  
Sent By kstevens Date 2002-03-19 Time 10:57 Rev Time 2.00
Received By kstevens Date 2002-03-19 Time 10:57 Sent To  
Notes
2002-03-19 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SHT A1 (1 OF 2) CODE CLASSIFICATION
 #3 STANDARD PLUMBING CODE 1994 IN EFFECT
 NOT 1997. PLEASE CHANGE TO REFLECT PRO-
 PER CODE.
 2) SHT A1 (1 OF 2) SPC TABLE 407 REQUIR-
 ES THAT 2 TOILET ROOMS, 1 FOR MALE AND
 1 FOR FEMALE BE PROVIDED.
 3) SHT A1 (1 OF 2) PLUMBING RISER - HUB
 DRAIN AT STEAM TABLE NOT APPROVED. ALL
 INDIRECT WASTE TO DRAIN TO FLOOR SINK.
 SPC SEC 804.1
 4) SHT A1 (1 OF 2) PLUMBING RISER -
 FLOOR SINK REQUIRED FOR WOK SINK SHALL
 HAVE A TRAP. (NOT SHOWN)
 5) SHT A1 (1 OF 2) FLOOR DRAIN IN TOILET
 ROOMS SHALL HAVE TRAP PRIMER. SPC SEC
 409.4.1.1 - ALL OTHER TRAPS SEALS SUB-
 JECT TO EVAPORATION SHALL BE OF THE DEEP
 SEAL TYPE NOT LESS THAN 4" WATER SEAL OR
 SHALL BE FED FROM A TRAP PRIMER.
 6) SHT A2 (2 OF 2) MINIMUM GREASE TRAP
 750 GALS. PLEASE CONTACT RODNEY COMPO,
 ENVRONMENTAL COMPLIANCE, (561) 837-4074
 FOR GREASE TRAP SIZE. WASTE ORD #2938-96
 7) SHT A2 (2 OF 2) GREASE TRAPS INSIDE
 KITCHEN AREA NOT APPROVED. PLEASE REMOVE
 8) SHT A2 (2 OF 2) SEPARATE SANITARY AND
 GREASE LINES REQUIRED.
 9) SHT A2 (2 OF 2) WATER RISER DIAGRAM
 REQUIRED. SPC SEC 104.2.1 - AIR CHAMBERS
 ARE A QUICK FIX AND DO NOT WORK. IF
 WATER HAMMER ARRESTORS ARE USED THEY
 SHALL BE LOCATED NEAR THE FIXTURES IN AN
 EFFECTIVE RANGE AND NOT AT TOP OF DROPS.
 10 SHT A2 (2 OF 2) SEPARATE GAS PERMIT
 REQUIRED. SEE FOLLOWING GAS PERMIT
 APPLICATION REQUIREMENTS.
 11 SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER STANDARD
 GAS CODE.
 12 BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE STANDARD GAS CODE SECS. 305.2 THRU
 305.4 AND TABLES 305.4(A) THRU 305.4(E).
 13 SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 THE STANDARD GAS CODE SEC. 305.4(I).
 14 INDICATE THE DELIVERY PRESSURE (PSI)
 PER STANDARD GAS CODE SEC. 305.2. IF
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 15 SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER THE STANDARD GAS CODE SECS
 602 THRU 612.
 16 SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 STANDARD GAS CODE SEC. 402.
 17. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-05 Cont ID  
Sent By gjoyce Date 2002-03-05 Time 10:03 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
***NONE***