| 2002-03-26 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | SBC = STANDARD BUILDING CODE 1997 |
| | SBC*= STANDARD BUILD'G CODE (CITY AMEND) |
| | FL ENERGY CODE = FLORIDA ENERGY |
| | EFFICIENCY CODE FOR BUILD'G CONSTR'N |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) FL ENERGY CODE 103.0COMPLIANCE |
| | SHALL BE DEMONSTRATED BY SUBMITTAL OF |
| | APPROPRIATE ENERGY CODE COMPLIANCE FORMS |
| | FOR THE ADDITION |
| | (REF: FL ENERGY CODE 600.2.A.3) |
| | |
| | 4) SBC* 1606.4BUCK CONNECTIONS FOR |
| | EXTERNAL DOORS AND WINDOWS.SUBMIT |
| | PRODUCT APPROVALS. |
| | |
| | 5) SBC 1606.3.2ROOF COVERING FOR THE |
| | FLAT AND PITCHED ROOFS.SUBMIT PRODUCT |
| | APPROVALS OR A SEPARATE ROOFING PERMIT |
| | APPLICATION WILL BE REQUIRED. |
| | |
| | 6) SBC 2303.2SHEET 2, TYPICAL SECTION. |
| | THE CMU BOND BEAM IS NOT ADEQUATELY |
| | ANCHORED.IT SHALL BE TIED TO THE |
| | FOUNDATION USING #5 STEM WALL |
| | REINFORCEMENT AT MAX 8'-0" O.C. IN A |
| | GROUTED CELL, WITH A STANDARD HOOK INTO |
| | THE BOND BEAM (REF: SSTD 10-99, FIGURES |
| | 303A AND 303B). |
| | |
| | 7) SBC 2306SHEET 2, TYPICAL SECTION |
| | AND SHEET 1, GENERAL NOTE 10.THE |
| | PROPOSED LSTA 18 STRAP ON THE RAFTER HAS |
| | 6-10D NAILS TO EACH EXTERIOR WALL STUD |
| | AND THE PROPOSED HETA 20 CONNECTOR CAST |
| | INTO THE CMU BOND BEAM HAS 4-10D NAILS |
| | INTO EACH EXTERIOR WALL STUD.WITH |
| | REFERENCE TO THE MANUFACTURER'S DATA, IT |
| | IS CONSIDERED THAT NEITHER OF THESE |
| | NAILING ARRANGEMENTS WILL GIVE THE |
| | UPLIFT CAPACITY THAT WOULD BE REQUIRED |
| | BY SSTD 10-99 TABLE 305F1.EITHER SHOW |
| | THE DERIVED UPLIFT ON THE PLANS OR |
| | REVISE THE DETAILS TO GIVE GREATER |
| | UPLIFT CAPACITY. |
| | |
| | 8) SBC 2304.3THE CRAWL SPACE |
| | VENTILATION FOR THE EXISTING BUILDING |
| | SHALL BE RETAINED. |
| | |
| | 9) FBC 2405.2THE SHOWER WINDOW GLASS |
| | IS IN A 'HAZARDOUS LOCATION' AND IS |
| | REQUIRED TO BE SAFETY GLASS SATISFYING |
| | THE REQUIREMENTS OF THE CONSUMER PRODUCT |
| | SAFETY COMMISSION 16, CODE OF FEDERAL |
| | REGULATIONS, PART 1201 (CPSC 16-CFR, |
| | PART 1201).AMEND THE WINDOW SCHEDULE |
| | TO DEMONSTRATE COMPLIANCE. |
| | |
| | 10) SBC 1007.3.1STAIRWAYS.ANNOTATE |
| | THE PLANS TO SHOW THAT THE RISER HEIGHT |
| | (R) DOES NOT EXCEED 7-3/4", THE TREAD |
| | DEPTH (T) IS NOT LESS THAN 9" AND THE |
| | RELATIONSHIP 2R+T IS NOT LESS THAN 24" |
| | NOR MORE THAN 25". |
| | |
| | 11) SHEET 1, FLOOR PLAN. THE SECTION A-A |
| | MARKER SHOULD READ B-B AND VICE VERSA TO |
| | CORRESPOND WITH THE CORRECT DETAILS ON |
| | SHEET 2. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |