Plan Review Details - Permit 02021913
Plan Review Stops For Permit 02021913
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-07-18 Cont ID  
Sent By rbrown Date 2002-07-18 Time 15:04 Rev Time 0.00
Received By rbrown Date 2002-07-18 Time 15:04 Sent To  
Notes
2002-07-18 00:00:00BUILDING PLAN REVIEW
 *******PROVISO******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 --PROVISO--
 IMPACT FEES SHALL BE PAID TO PALM BEACH
 COUNTY (FOR INFO, TEL: 561 233 5115)
  
 --PROVISO--
 A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT SHALL BE SUBMITTED.
  
 --PROVISO--
 FL ENERGY CODE 103.0THE SUBMITTED
 ENERGY CODE COMPLIANCE FORM SHALL BE
 COMPLETED BY ENTERING THE FOLLOWING INFO
 PERMITTING OFFICE: WEST PALM BEACH
 JURISDICTION NO.: 604700
 THE CORRECT PERMIT NUMBER IS 02021913
  
 --PROVISO--
 SBC* 1606.4SUBMIT PRODUCT APPROVALS
 FOR THE EXTERNAL DOORS AND WINDOWS.
  
 --PROVISO--
 SUBMIT PRODUCT APPROVALS FOR THE ROOFING
 MATERIALS.NO PRODUCT APPROVAL HAS BEEN
 SUBMITTED FOR THE ASPHALT SHINGLES
 PROPOSED FOR THE PITCHED ROOF.ALSO,
 THE SUBMITTED BUILT-UP ROOFING PRODUCT
 APPROVAL FOR THE FLAT ROOF IS INCOMPLETE
 SUBMIT ALL OF THE SHEETS (STAMPED BY THE
 MIAMI-DADE PRODUCT EXAMINER) APPLICABLE
 TO THIS INSTALLATION.
  
 --PROVISO--
 SHEET 2, TYPICAL SECTION, HAS BEEN
 RED-LINED TO SHOW A GROUTED CELL AT EACH
 STEM WALL REINFORCEMENT LOCATION AND TO
 SHOW THE STEM WALL REINFORCEMENT AS
 HAVING THE REQUIRED STANDARD HOOK INTO
 THE CMU BOND BEAM.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-03-26 Cont ID  
Sent By pkrauss Date 2002-03-14 Time 16:31 Rev Time 0.00
Received By rbrown Date 2002-03-26 Time 10:13 Sent To  
Notes
2002-03-26 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
 FL ENERGY CODE = FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILD'G CONSTR'N
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) FL ENERGY CODE 103.0COMPLIANCE
 SHALL BE DEMONSTRATED BY SUBMITTAL OF
 APPROPRIATE ENERGY CODE COMPLIANCE FORMS
 FOR THE ADDITION
 (REF: FL ENERGY CODE 600.2.A.3)
  
 4) SBC* 1606.4BUCK CONNECTIONS FOR
 EXTERNAL DOORS AND WINDOWS.SUBMIT
 PRODUCT APPROVALS.
  
 5) SBC 1606.3.2ROOF COVERING FOR THE
 FLAT AND PITCHED ROOFS.SUBMIT PRODUCT
 APPROVALS OR A SEPARATE ROOFING PERMIT
 APPLICATION WILL BE REQUIRED.
  
 6) SBC 2303.2SHEET 2, TYPICAL SECTION.
 THE CMU BOND BEAM IS NOT ADEQUATELY
 ANCHORED.IT SHALL BE TIED TO THE
 FOUNDATION USING #5 STEM WALL
 REINFORCEMENT AT MAX 8'-0" O.C. IN A
 GROUTED CELL, WITH A STANDARD HOOK INTO
 THE BOND BEAM (REF: SSTD 10-99, FIGURES
 303A AND 303B).
  
 7) SBC 2306SHEET 2, TYPICAL SECTION
 AND SHEET 1, GENERAL NOTE 10.THE
 PROPOSED LSTA 18 STRAP ON THE RAFTER HAS
 6-10D NAILS TO EACH EXTERIOR WALL STUD
 AND THE PROPOSED HETA 20 CONNECTOR CAST
 INTO THE CMU BOND BEAM HAS 4-10D NAILS
 INTO EACH EXTERIOR WALL STUD.WITH
 REFERENCE TO THE MANUFACTURER'S DATA, IT
 IS CONSIDERED THAT NEITHER OF THESE
 NAILING ARRANGEMENTS WILL GIVE THE
 UPLIFT CAPACITY THAT WOULD BE REQUIRED
 BY SSTD 10-99 TABLE 305F1.EITHER SHOW
 THE DERIVED UPLIFT ON THE PLANS OR
 REVISE THE DETAILS TO GIVE GREATER
 UPLIFT CAPACITY.
  
 8) SBC 2304.3THE CRAWL SPACE
 VENTILATION FOR THE EXISTING BUILDING
 SHALL BE RETAINED.
  
 9) FBC 2405.2THE SHOWER WINDOW GLASS
 IS IN A 'HAZARDOUS LOCATION' AND IS
 REQUIRED TO BE SAFETY GLASS SATISFYING
 THE REQUIREMENTS OF THE CONSUMER PRODUCT
 SAFETY COMMISSION 16, CODE OF FEDERAL
 REGULATIONS, PART 1201 (CPSC 16-CFR,
 PART 1201).AMEND THE WINDOW SCHEDULE
 TO DEMONSTRATE COMPLIANCE.
  
 10) SBC 1007.3.1STAIRWAYS.ANNOTATE
 THE PLANS TO SHOW THAT THE RISER HEIGHT
 (R) DOES NOT EXCEED 7-3/4", THE TREAD
 DEPTH (T) IS NOT LESS THAN 9" AND THE
 RELATIONSHIP 2R+T IS NOT LESS THAN 24"
 NOR MORE THAN 25".
  
 11) SHEET 1, FLOOR PLAN. THE SECTION A-A
 MARKER SHOULD READ B-B AND VICE VERSA TO
 CORRESPOND WITH THE CORRECT DETAILS ON
 SHEET 2.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-07-18 Cont ID  
Sent By dpalmer Date 2002-07-18 Time 13:52 Rev Time 0.00
Received By dpalmer Date 2002-07-18 Time 13:52 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-06 Cont ID  
Sent By dpalmer Date 2002-03-06 Time 06:37 Rev Time 0.00
Received By dpalmer Date 2002-03-06 Time 06:37 Sent To P
Notes
2002-03-06 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE CLARIFY, PLANS ARE SHOW-
 -ING A NEW PANEL IN HALL? PLEASE SHOW/
 OR PROVIDE DETAIL WHERE/HOW THIS PANEL
 IS BEING FED.
  
 2)NOTE: PLEASE NOTE THAT PLANS SHOW
 NEW WASHER/DRYER/WATER HEATER, PLEASE
 CLARIFY IF THESE ARE NEW ADDED LOADS TO
 EXISITNG SERVICE OR ARE THESE BEING
 MOVED FROM EXSITING LOCATION?
 IF NEW/ADDED, PLEASE PROVIDE LOAD CALCU-
 -LATIONS FOR SERVICE AND SHOW SIZE OF
 SERVICE.
  
 3) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 4)NOTE: PLEASE NOTE, A SMOKE DETECTOR IS
 REQ`D. THIS IS AN ADAPTABLE BEDROOM W/
 THE CLOSET AND OR BATH ATTACHED.
  
 5)NOTE: PLEASE ALSO NOTE THAT PLANS
 SHOW A J.B. IN THE MIDDLE OF THE FAM RM,
 PLEASE NOTE A LT FIXTURE IS REQ`D FOR
 EGRESS. 210-70
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-03-14 Cont ID  
Sent By kstevens Date 2002-03-13 Time 10:32 Rev Time 0.30
Received By pkrauss Date 2002-03-14 Time 16:24 Sent To B
Notes
2002-03-14 00:00:00 
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-07-23 Cont ID  
Sent By kstevens Date 2002-07-23 Time 08:20 Rev Time 0.00
Received By kstevens Date 2002-07-23 Time 08:20 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-03-13 Cont ID  
Sent By dpalmer Date 2002-03-19 Time 19:24 Rev Time 0.50
Received By kstevens Date 2002-03-13 Time 10:17 Sent To M
Notes
2002-03-13 00:00:00DENIED
 REFERENCE: SPC-94 - SBC-97
  
 1) SANITARY RISER DIAGRAM REQUIRED.
 SPC SEC 104.2.1
 2) ALL SHOWER COMPARTMENTS SHALL HAVE A
 MINIMUM OF 900 SQUARE INCHES OF INTERIOR
 CROSS-SECTIONAL AREA. SHOWER COMPARTMENT
 SHALL NOT BE LESS THAN 30" IN MINIMUM
 DIMENSION MEASURED FROM THE FINISHED
 DIMENSION FROM CURB TO WALL SIDE TO SIDE
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-01 Cont ID  
Sent By sgraham Date 2002-03-01 Time 11:51 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***