| Plan Review Stops For Permit 02021837 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2003-03-17 |
|
|
Cont ID |
|
| Sent By |
lsmith |
Date |
2003-03-17 |
Time |
16:45 |
Rev Time |
0.20 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-05-28 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-14 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
lsmith |
Date |
2003-03-17 |
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2002-05-28 00:00:00 | REVISION #1 VARIOUS DATES IN MAY |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2002-04-01 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-04-01 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2002-10-25 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-11-07 |
Time |
08:06 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2002-10-25 |
Time |
10:37 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-10-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-10-24 |
Time |
16:59 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2002-10-24 |
Time |
16:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-05-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-05-29 |
Time |
19:43 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-05-29 |
Time |
19:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-03-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-14 |
Time |
12:20 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-03-14 |
Time |
08:34 |
Sent To |
|
|
| Notes |
| 2002-03-14 00:00:00 | ******************* UNSAT ************** | | | | | | | | | 1)NOTE: PLEASE NOTE, THAT PER LOCAL | | | AMENDMENTS.230-70A. NO MORETHAN 8' OF | | | UNPROTECTED CONDUCTORS INSIDE THE BLDG. | | | | | | 2)NOTE: PLEASE SHOW LOAD CALCULATIONS, | | | PLEASE SEE NEC 220-3,220-10,220-11, | | | 220-13 AND ALL CONTINUOUS LOADS PER | | | 230-42,215-2,3. | | | | | | 3)NOTE: PLEASE SEE 230-76, 230-79 FOR | | | MANUAL MEANS OF DISC AND RATING OF | | | SERVICE MAIN TO CLARIFY SHUNT TRIP. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | PLEASE SEE FIRE REVIEW FOR ANY COMMENTS | | | THAT MAY AFFECT ELECTRICAL PLANS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2002-03-14 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2002-03-14 |
Time |
15:04 |
Rev Time |
1.00 |
| Received By |
mamini |
Date |
2002-03-14 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2002-03-14 00:00:00 | PASSED WITH PROVISOS: | | | 1. DRIVEWAYS APPR. MUST BE PER CITY OF | | | WPB' STANDARD IF IN CITY'S R.O.W AND PER | | | FDOT'S STANDARD IF IN STATE ROAD R.O.W. | | | 2. ALL OFF-STREET PARKING MUST BE | | | PAINTED WITH DOUBLE 4" WHITE FOR REGULAR | | | AND BLUE FOR H.C. | | | 3. COVER FOR PNEUMATIC CULVERT MANHOLE | | | MUST BE TRAFFIC RATED. | | | IF ANY QUESTIONS PLEASE CONTACT 659-8096 | | | EXT. 8492 MOHAMMAD R. AMINI |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-05-31 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-05-31 |
Time |
12:32 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-05-31 |
Time |
12:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-03-26 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-03-26 |
Time |
12:45 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-03-26 |
Time |
12:45 |
Sent To |
|
|
| Notes |
| 2002-03-26 00:00:00 | A) BUILDING ADDRESS REQUIRED. | | | B) WRONG LIFE SAFETY CODE REFERENCED | | | ON PLANS. SHOULD READ THE FLORIDA | | | FIRE PREVENTION CODE, 2000 EDITION OF | | | THE LIFE SAFETY CODE. | | | C) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR WALLS | | | AND CEILINGS. | | | D) STORAGE ROOM 117,AND | | | STORAGE/MECHANICAL ROOM 104 ARE TO BE | | | AT LEAST ONE HOUR FIRE RATED AND BE | | | EQUIPPED WITH AT LEAST C LABELED FIRE | | | DOORS, SINCE NO FIRE SPRINKLERS ARE | | | PLANNED. | | | E) DOOR 122 FOR THE JANITOR'S ROOM | | | IS NOT FIRE RATED LIKE THE ROOM IS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-03-26 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-26 |
Time |
14:19 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-26 |
Time |
14:19 |
Sent To |
M |
|
| Notes |
| 2003-03-26 00:00:00 | REVISION TO MECH BOX |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-03-14 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-14 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
sthyng |
Date |
2003-03-14 |
Time |
10:21 |
Sent To |
B |
|
| Notes |
| 2003-03-14 00:00:00 | TO HP DESK |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2003-03-31 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-03-31 |
Time |
14:17 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2003-03-31 |
Time |
14:17 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-04-02 |
|
|
Cont ID |
|
| Sent By |
sthyng |
Date |
2003-03-26 |
Time |
14:25 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-03-20 |
Time |
12:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-06-06 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-06-06 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-06-06 |
Time |
10:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-04-02 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2002-04-02 |
Time |
15:01 |
Rev Time |
1.50 |
| Received By |
jleech |
Date |
2002-04-02 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2002-04-02 00:00:00 | DENIED; | | | 1.WATER HEATER SHALL BE READLY ACCESS- | | | ABLE PER 94 SPC SEC. 501.7. INSTALL | | | WATER HEATER ON FLOOR OR OTHER READLY | | | ACCESSABLE LOCATION. | | | 2.DRINFING FOUNTAIN SHALL ACCOMMODATE | | | PEOPLE WHO HAVE DIFFICULTY BENDING AND | | | PEOPLE IN WHEEL CHAIRS. SEE 97 FACBC | | | SEC 4.1.3 (10). | | | 3.APPROVED ENGINEERED MECHANICAL HAMMER | | | ARRESTERS SHALL BE SIZED BY THE | | | ENGINEER AND INSTALLED PER MANUFACTORS | | | RECOMENDATIONS. SEC 607.8.2. PAGE P-1 | | | WATER RISER DIAGRAM, DELLETE AIR | | | CHAMBER FROM DRAWING AND SHOW LOCATION | | | OF REQUITED MHA'S. | | | 4.PAGE P-1 DRY WELL DETAIL. INSTALL A | | | TEE IN CONDENSATE PIPE BEFORE THE | | | DRY WELL EXTEND TEE ABOVE GROUND AND | | | PUT A "U' BEND ONPIPE. THIS SERVICE | | | AS A VENT AND AN OVERFLOW OUTLET. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT 8369 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2002-12-18 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-12-18 |
Time |
09:49 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-03-13 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-03-13 |
Time |
10:32 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|