|
 |
 |
 |
 |
 |
Plan Review Details - Permit 02021836
| Plan Review Stops For Permit 02021836 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-03-28 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-03-28 |
Time |
07:58 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-03-04 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-03-04 |
Time |
13:04 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-04 00:00:00 | PROVIDE A DETAIL FOR CUTTING THE SECOND | | | FLOOR, AND THE ROOF.ALSO, SHOW THE | | | FIRE RATED SHAFT REQUIRED BY SBC 705.6. | | | INCLUDE PENETRATIONS FOR THE ELECTRICAL. | | | | | | WILL THE DEMISING WALL BE CONSTRUCTED | | | COMPLETELY?PLANS SHOW DRY WALL TO BE | | | INSTALLED AT A LATER DATE. | | | | | | SHOW THE MEANS OF EGRESS FROM THE NEWLY | | | DEMISED SPACES SHOWN AS R1 AND R1A. | | | | | | IF THE NEW DOOR ON THE NORTH END OF | | | SPACE R1A DISCHARGES TO AN EXIT COURT | | | OR SIMILAR, THAN THE LOUVER ABOVE MUST | | | BE FIRE PROTECTED AS WELL.SEE SBC | | | 1010.2 & SBC 1010.3. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
N |
Date |
2002-03-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-05 |
Time |
09:51 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
2002-03-05 |
Time |
09:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2002-03-01 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-03-01 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-03-01 |
Time |
10:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2002-03-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-04 |
Time |
09:25 |
Rev Time |
0.30 |
| Received By |
hpiskura |
Date |
2002-03-04 |
Time |
09:25 |
Sent To |
|
|
| Notes |
| 2002-03-04 00:00:00 | | | | PROVISO:MECHANICAL PERMIT 02021838 | | | | | | PERMIT IS FOR EXHAUST DUCTWORK & FIRE | | | DAMPER. (NO HVAC) | | | | | | PROVIDE MANUFACTURER SUBMITTAL DATA FOR | | | FIRE DAMPER PRIOR TO INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2002-03-28 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-03-28 |
Time |
08:02 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |