Plan Review Details - Permit 02021651
Plan Review Stops For Permit 02021651
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-03-29 Cont ID  
Sent By rbrown Date 2002-03-29 Time 13:39 Rev Time 0.00
Received By rbrown Date 2002-03-29 Time 13:39 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-03-14 Cont ID  
Sent By rbrown Date 2002-03-14 Time 08:46 Rev Time 0.00
Received By rbrown Date 2002-03-14 Time 08:45 Sent To  
Notes
2002-03-14 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SBC* 104.2.2SHEET D-1, DEMOLITION
 PLAN.STATE THE TYPE OF CONSTRUCTION OF
 THE EXISTING WALLS WHICH ARE TO BE
 DEMOLISHED.ARE THEY LOADBEARING?
  
 3) SBC TABLE 704.2.4FOR GROUP R1
 (HOTEL/MOTEL) OCCUPANCY, EXIT ACCESS
 CORRIDORS SHALL HAVE A FIRE RESISTANCE
 RATING OF 1 HOUR IF NON-SPRINKLERED OR
 1/2 HOUR IF SPRINKLERED.THE PROPOSAL
 IS FOR REPLACEMENT OF THE EXISTING
 CORRIDOR WALLS WITH 3 FEET HIGH
 PARTITIONS.REINSTATE THE CORRIDORS OR
 SUBMIT LIFE SAFETY PLANS TO SHOW ALL
 AREAS WITH MEANS OF EGRESS VIA THESE
 CORRIDORS.
 ***FOLLOW-UP:
 LIFE SAFETY PLAN REVIEWED ON 3/21/02.
 EITHER ENCLOSE THE PROPOSED DINING WITH
 1/2 HOUR FIRE RATED WALLS/GLAZING AND
 FIRE DOORS OR LEAVE PROPOSED DINING OPEN
 AND INSTALL SMOKE CONTROL FIRE DOORS
 ACROSS THE CORRIDOR IN TWO LOCATIONS AS
 MARKED ON THE ATTACHED PLAN.THE DOORS
 SHALL BE DOUBLE DOORS WITH PAIRED LEAFS
 OPENING IN OPPOSITE DIRECTIONS.THE
 DOORS SHALL NORMALLY BE HELD OPEN BY
 DEVICES CONNECTED TO THE FIRE ALARM SUCH
 THAT THEY CLOSE UPON A FIRE ALARM
 ORIGINATING FROM ANYWHERE IN THE
 BUILDING.THERE SHALL BE A SMOKE
 DETECTOR ON EACH SIDE OF BOTH DOORSETS
 (4 HEADS IN TOTAL) AND ADDITIONAL EXIT
 SIGNAGE SHALL BE INSTALLED TO DIRECT
 OCCUPANTS TO EXITS BEYOND THE DOORS,
 AFTER THEY HAVE CLOSED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-03-05 Cont ID  
Sent By dpalmer Date 2002-03-05 Time 10:30 Rev Time 0.00
Received By dpalmer Date 2002-03-05 Time 10:30 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2002-03-01 Cont ID  
Sent By mcarsill Date 2002-03-01 Time 12:17 Rev Time 0.00
Received By mcarsill Date 2002-03-01 Time 12:17 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-04-09 Cont ID  
Sent By pkrauss Date 2002-04-09 Time 09:23 Rev Time 0.20
Received By pkrauss Date 2002-04-09 Time 09:23 Sent To  
Notes
2002-04-09 00:00:00 
 SUBMITTAL LETTER FOR O.A FROM THE
 ARCHITECT.USING THE SAME A/C ADJUSTING
 O.A. ACCORDINGLY.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-03-28 Cont ID  
Sent By pkrauss Date 2002-03-01 Time 16:35 Rev Time 0.25
Received By pkrauss Date 2002-03-01 Time 16:35 Sent To  
Notes
2002-03-01 00:00:00 
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 PLEASE PROVIDE OUTSIDE AIR CALCULATIONS
 AS PER ASHRAE 62-89.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-03-04 Cont ID  
Sent By kstevens Date 2002-03-04 Time 15:43 Rev Time 0.50
Received By kstevens Date 2002-03-04 Time 15:43 Sent To  
Notes
2002-03-04 00:00:00PASSED - PERMIT REQUIRED FOR PLUMBING
 DEMO WORK - NO NEW PLUMBING SHOWN ON
 PLANS.KSTEVENS