Plan Review Details - Permit 02021641
Plan Review Stops For Permit 02021641
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-04 Cont ID  
Sent By rbrown Date 2002-04-04 Time 16:53 Rev Time 0.00
Received By rbrown Date 2002-04-04 Time 16:52 Sent To  
Notes
2002-04-04 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FOR PERMIT APPLICATIONS RECIEVED BEFORE
 MARCH 1, 2002 EITHER STANDARD BUILDING
 CODE 1997 OR FLORIDA BUILDING CODE 2001
 MAY BE USED.AS SHEET S14, GENERAL
 NOTES REFERS TO STANDARD BUILDING CODE
 1997 THE PLANS HAVE BEEN REVIEWED FOR
 COMPLIANCE WITH THAT CODE.
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE PLANS SHALL BE ASSESSED BY PALM
 BEACH COUNTY BUILDING DIVISION FOR
 IMPACT FEES, PLANS STAMPED BY THEM AND A
 COPY OF THE RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) THE ELECTRICAL PLAN REVIEW COMMENT #9
 SHALL BE ADDRESSED IN RESPECT OF THE
 VALUE AND SCOPE OF WORK.
  
 4) ARCHITECTURAL SPECIFICATION.ALL
 REFERENCES TO 1991 STANDARD BUILDING
 CODE SHALL BE AMENDED TO READ
 1997 STANDARD BUILDING CODE. FOR EXAMPLE
 SECTION 03450 PART 1.03C, SECTION 03455
 PART 1.04A AND SECTION 07241 PART 1.03D
  
 5) SBC* 1804.2.2SHEET S14, FOUNDATION
 NOTES.SUBMIT A SOIL REPORT TO VERIFY
 THE ASSUMED BEARING PRESSURE OF 3000 PSF
  
 6) SBC* 1606.4DOOR PRODUCT APPROVAL.
 THE SUBMITTED MIAMI-DADE NOTICE OF
 ACCEPTANCE NO 97/0903.12 EXPIRED ON
 12/31/2001 AND INCLUDES SHEET 1 ONLY.
 SUBMIT COMPLETE AND VALID PRODUCT
 APPROVALS FOR THE NEW EXTERNAL DOORS.
  
 7) SBC* 1606.4SHEET A-5 AND SPECIF'N
 SECTION 07810 - SKYLIGHT RENOVATION.
 THE REPLACEMENT GLAZING SHALL BE
 DESIGNED AND TESTED IN ACCORDANCE WITH
 SBCCI SSTD 12-99, TEST STANDARD FOR
 DETERMINING IMPACT RESISTANCE FROM
 WINDBORNE DEBRIS.SUBMIT DETAILS TO
 DEMONSTRATE COMPLIANCE.
  
 8) SBC 1007.3STAIR TREADS AND RISERS.
 DETAILS 3/S9 AND 10/A11.THE HEIGHT OF
 THE RISERS (R) SHALL NOT EXCEED 7-3/4"
 (TREAD (T) EXCEEDS 9", AND IS COMPLIANT)
 ALSO, THE RELATIONSHIP 2R+T SHALL NOT BE
 LESS THAN 24" OR MORE THAN 25". ANNOTATE
 THE PLANS TO DEMONSTRATE COMPLIANCE.
  
 9) FL ACC CODE 4.32.4FRONT DESK
 (SHEET 1D.11).THE HEIGHT OF THE NEW
 FRONT DESK SHALL BE BETWEEN 28" TO 34"
 ABOVE FINISH FLOOR LEVEL.
  
 10) FL ACC CODE 4.17.6GRAB BARS.
 ANNOTATE SHEET ID.16 TO DEMONSTRATE
 COMPLIANCE WITH THE GRAB BAR LENGTH AND
 POSITIONING REQUIREMENTS AS SHOWN IN
 FIGURE 30.
  
 11) FL ACC CODE 4.15DRINKING FOUNTAINS
 SHEET ID.2.THE NEW WATER (DRINKING)
 FOUNTAINS SHALL HAVE CLEARANCES AND
 SPOUT HEIGHT IN ACCORDANCE WITH FIG. 27.
 ANNOTATE THE PLANS TO DEMONSTRATE
 COMPLIANCE.
  
 12) FL ACC CODE 4.8.5(2)NEW RAMP
 ADJACENT THE RESTAURANT AND NEW RAMP IN
 CORRIDOR 116 (SHEET ID.17).THE RAMP
 HANDRAILS SHALL EXTEND NOT LESS THAN 18"
 BEYOND THE SLOPED SECTION AT BOTH THE
 TOP AND BOTTOM OF THE RAMP (REF FIG. 17)
  
 13) FL ACC CODE 4.9.4(2)SHEET ID.17.
 THE BOTTOM OF THE STAIR HANDRAIL SHALL
 CONTINUE TO SLOPE, BEYOND THE LEADING
 EDGE OF THE BOTTOM RISER, FOR A DISTANCE
 EQUAL TO THE DEPTH OF ONE TREAD AND THEN
 EXTEND HORIZONTALLY FOR A FURTHER 12".
 (REF FIG. 19C)
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-13 Cont ID  
Sent By dpalmer Date 2002-03-13 Time 06:50 Rev Time 0.00
Received By dpalmer Date 2002-03-12 Time 18:50 Sent To  
Notes
2002-03-13 00:00:00*************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE E-9 NEEDS TO SHOW
 CIRCUITING AND TO WHAT PANELS THESE
 FIXTURES WILL BE GOING TO?
 VOLTAGE/ LOADING OF CIRCUITS.
  
 2)NOTE: PLEASE SEE ANY FIRE REVIEW
 COMMENTS THAT MAY AFFECT ELECTRICAL
 PLANS FOR EXIT LIGHTING.
  
 3)NOTE: PLEASE NOTE THAT NOT ENOUGH
 INFORMATION IS PROVIDED FOR "PART PLAN
 RISER" SHOWN ON E-3.
 PLEASE NOTE THAT NOTE FOR TAPPING
 MENTIONS, W/ 4#-. ? WHAT SIZE WIRE?
 PLEASE ALSO NOTE, DETAIL FOR 3-2/0`S??
 PLEASE CORRELATE. CLARIFY CONDUCTORS.
  
 4)NOTE: PLEASE NOTE NO LOAD CALCULATIONS
 FORFOR PANEL "UPP"?? E-6 SHOWS EXSIT-
 -ING AND E-3 SHOWS PART OF NEW RISER?
 PLEASE CALRIFY.
  
 5)NOTE: PLEASE NOTE THAT RISER NOTE ON
 E-3 MENTIONS, RISER IN "MAIDS CLOSET"???
 PLEASE SEE 384-7 AND 110-26 FOR
 EQUIPMENT BEING INSTALLED THESE LOCATION
 -S. PLEASE NOTE DEDICATED ELECTRICAL
 SPACE AND IGNITIBLE STORAGE.
  
 6)NOTE: PLEASE SHOW LOCATION OF THIS
 ROOM ON PLAN. PLEASE SHOW LOCATION AND
 MOUNTING DETAIL FOR TRANSFORMER.
 SEE 450-9,4502-13,450-21.
  
 7)NOTE: PLEASE CLARIFY PANEL "UPP".
 MAIN BRKR? MLO? PLEASE NOTE LIGHTING
 PANEL HAVING MAIN BRKR REQ`D FROM
 TRANSFORMER.
  
 8)NOTE: PLEASE NOTE THAT ALL CONTINUOUS
 LOADS ARE TO BE SHOWN AT 125%.
  
 9)NOTE: PLEASE PROVIDE A COPY OF
 CONTRACT TO VERIFY VALUE FOR COMPLET
 SCOPE OF WORK. PLEASE NOTE ALL LABOR
 AND MATERIALS ARE TO BE INCLUDED FOR
 PERMIT VALUATION. 104.6.5 FBCAC
 CITY OF WEST PALM BEACH LOCAL ADMIN
 AMENDMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-02-27 Cont ID  
Sent By mcarsill Date 2002-02-27 Time 15:15 Rev Time 0.00
Received By mcarsill Date 2002-02-27 Time 15:15 Sent To  
Notes
2002-02-27 00:00:00A) NO FIRE HYDRANT LOCATIONS IDENTIFIED
 ON SITE PLAN.
 B) PANIC HARDWARE REQUIRED ON EXIT
 DOORS SUBJECT TO AN OCCUPANCY OF 100
 OR MORE PERSONS.
 C) PLEASE INDICATE USE OF TERRACE.
 D) PLEASE INDICATE LOCATIONS OF FIRE
 ALARM EQUIPMENT IN NEW AREAS.
 E) IT WAS NOTED THAT EXITING FROM A
 BALLROOM ENTERS A RECEIVING ROOM. EXIT
 ACCESS IS NOT PERMITTED THROUGH STORAGE
 ROOMS.
 F) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 G) PLEASE PROVIDE A FURNITURE PLAN FOR
 NEW ROOMS OR AREAS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-03-11 Cont ID  
Sent By pkrauss Date 2002-03-11 Time 11:12 Rev Time 1.00
Received By pkrauss Date 2002-03-11 Time 09:48 Sent To  
Notes
2002-03-11 00:00:00 
 PROVISO:
  
 PRIOR TO CONNECTING TO ANY EXISTING
 DUCTWORK, CALL FOR AN INSPECTION.
  
 TERMINATION OF EXHAUST FAN #33 SHALL BE
 A MINIMUM OF 10' FROM ANY DOOR, WINDOW
 OR FRESH AIR INTAKE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT.

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-03-12 Cont ID  
Sent By kstevens Date 2002-03-12 Time 13:41 Rev Time 4.00
Received By kstevens Date 2002-03-12 Time 13:41 Sent To  
Notes
2002-03-12 00:00:00DENIED
 REFERENCE: SPC-94 - FACBC-97
  
 1) SHT A-4 ROOF PLAN "A" - SUBMIT ROOF
 DRAIN CALCULATIONS FOR NEW ROOF AREAS.
 SHOW DETAILS FOR SECONDARY DRAINS FOR
 NEW TERRACE ROOF, NEW ROOF INTERIOR ADD.
 NEW CURVED BALCONY ROOF.
 2) SHT A-4 ROOF PLAN "A" - "REMOVE AND
 PATCH EXIST. SCUPPERS @ PERIMETER WALL",
 EXPLAIN HOW SCUPPERS CAN BE REMOVED AND
 PATCHED WHEN THEY ARE THE SECONDARY
 DRAINS FOR THIS ROOF.
 3) SHT A-4 ROOF PLAN "A" - PLEASE PRO-
 VIDE ROOF DRAIN CALCULATIONS FOR EXIST.
 ROOF. ADD AREAS OF NEW ROOFS BEING ADDED
 TO AREA OF ROOF. (ROOFS ADDED - STAIR
 TOWERS #'S 1 & 3, SERVICE AND PASSENGER
 ELEVATORS, AND ROOF WEST OF SERV. ELEV.)
 SHOW DETAILS FOR ALL SECONDARY DRAINS.
 GIVE LOCATIONS ON ROOF PLAN FOR PRIMARY
 AND SECONDARY DRAINS EXISTING.
 4) SHT A-4 ROOF PLAN "A" - PLEASE SHOW
 DETAILS FOR REACTIVATING SCUPPERS AS RE-
 FERED TO IN NOTE. (ALSO NOTED ON SHT P-6
 5) SHT A-5 ROOF PLAN "B" - PLEASE SUBMIT
 CALCULATIONS FOR EXISTING ROOF DRAIN.
 SHOW PRIMARY AND SECONDARY DRAIN LOCAT-
 IONS. GIVE SQ FOOT AREAS FOR EACH DRAIN
 AND DRAIN SIZE.
 6) SHT A-5 ROOF PLAN "B" - PLEASE SUBMIT
 DETAILS ON HOW THE SECONDARY ROOF DRAINS
 (SCUPPERS) CAN BE REMOVED AND PATCHED,
 AND ONE OVERSIZED SECONDARY DRAIN WILL
 WORK ON A FLAT ROOF.
 7) PLEASE SUBMIT A STORM RISER DIAGRAM
 FOR ALL NEW ROOFS. SHOW AREA FOR EACH
 DRAIN, PIPE SIZE, PITCH FOR PIPE, AND
 SHOW ACCUMULATION OF SQUARE FOOTAGE FOR
 PIPE AS EACH DRAIN IS ADDED. SHT P-6
 SHOWS EXISTING ROOF DRAIN BEING REMOVED.
 8) SHT A-4 STAIRWAY #3, PLEASE SUBMIT
 DETAILS FOR FLUE EXTENTION. INDICATE
 WHAT FIXTURE THE FLUE IS VENTING. SUBMIT
 A DETAIL SHOWING SIZE, LENGTH OF FLUE &
 GIVE TOTAL BTU'S OF FIXTURE.
 9) SHT ID.2 HDCP STALLS IN ROOMS 110 &
 111 DO NOT MEET FACBC-97 CODE. LAV REQD.
 IN HDCP STALLS. SEC 4.1.7.3 FIG 30(E).
 10) SHT ID.11 FOUNTAIN. PLEASE SUBMIT
 PLUMBING DETAIL FOR FOUNTAIN. SHOW PIP-
 ING, BACKFLOW FOR WATER SERVICE, PUMPING
 FILTER ECT. SEPARATE PERMITS REQUIRED
 FOR FOUNTAIN.
 11) SHT P-1 GENERAL NOTES #16 AIR CHAMB-
 ERS. AIR CHAMBERS ARE A QUICK FIX AND
 REQUIRED AN ACCESS PANEL AND SHALL BE RE
 CHARGABLE. APPROVED WATER HAMMER ARREST-
 ORS DO NOT REQUIRE ACCESS PANELS.
 12) SHT P-1 PLUMBING SPECIFICATIONS #1
 CODE IN EFFECT IS SPC-94 NOT SOUTH FLA
 BLDG CODE.
 13) SHT P-1 PLUMBING SPECIFICATIONS #19-
 (C) DIELECTRIC UNIONS NOT APPROVED FOR
 WATER USAGE. GAS FITTING ONLY.
 14) SHT P-2 PART DOMESTIC WATER PUBLIC
 TOILETS RISER DIAGRAM. SEE PLAN REVIEW
 NOTE #11 AIR CHAMBERS. 1/2" TRAP PRIMERS
 ARE FEEDING WATER CLOSETS NOT TRAP PRIM-
 ERS.
 15) SHT P-2 SANITARY RISER DIAGRAM,
 1-1/2" TO URNAL NOT APPROVED. MINIMUM 2"
 WASTE TO URNAL. SPC TABLE 713.2
 16) SHT P-2 SANT. RISER DIAGRAM, FLOOR
 DRAINS NOT VENTED PROPERLY.
 17) SHT P-3 COMBINATION WASTE AND VENT
 SYSTEM FOR FLOOR SINKS REQUIRED ONE VENT
 BEFORE FIRST FIXTURE. SPC SEC 921.4.2
 18) SHT P-3 POND, INDIRECT WASTE FROM
 POND SHALL NOT DRAIN INTO MOP SINK AS
 INDICATED. POND SHALL DRAIN INTO AN IN-
 DIRECT WASTE RECEPTOR THAT IS APPROVED.
 (FLOOR SINK)SHOW DETAILS.
 19) SHT P-3 POND, BACKFLOW IS REQUIRED
 FOR WATER SUPPLY TO POND. PLEASE PROVIDE
 DETAIL.
 20) SHT P-8 SEE REVIEW COMMENTS #14 - 15
 -&-16. THESE COMMENTS APPLY TO SHT P-8
 AS WELL AS RISER DIAGRAMS ON SHT P-8.
 PLEASE SHOW DETAILS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377