| Plan Review Stops For Permit 02021544 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2004-02-26 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-02-26 |
Time |
08:45 |
Rev Time |
1.25 |
| Received By |
jwitmer |
Date |
2004-02-26 |
Time |
08:39 |
Sent To |
|
|
| Notes |
| 2004-02-26 00:00:00 | REV 12/12/02OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
N |
Date |
2003-12-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-02-05 |
Time |
14:22 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2003-12-29 |
Time |
13:11 |
Sent To |
Z |
|
| Notes |
| 2003-12-29 00:00:00 | DRIVEWAY REVISIONS & A/C CONDENSOR RE- | | | LOCATIONJW 12/29/03 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2002-12-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-12-22 |
Time |
16:13 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2002-12-30 |
Time |
16:30 |
Sent To |
|
|
| Notes |
| 2002-12-30 00:00:00 | REVISIONS: DATED 12-12-02OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-07-01 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-20 |
Time |
18:46 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-04-08 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-04-08 |
Time |
10:12 |
Rev Time |
3.50 |
| Received By |
jwitmer |
Date |
2002-04-08 |
Time |
07:36 |
Sent To |
|
|
| Notes |
| 2002-04-08 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 02021544 | | | 141 GREGORY PLACE | | | O/B MICHAEL SAINT JOHN | | | H 586-0484 | | | B 874-8610 BEEPER | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | SBC*= AMENDMENTS STANDARD BUILDING CODE | | | | | | 1)- MISSING PRODUCT APPROVALS: | | | A) WINDOW MULLION REPORT | | | B) GARAGE SIDE DOOR ENTRY | | | C) OVERHEAD GARAGE DOOR | | | D) GLASS BLOCK ALSO WALL THICKNESS OF | | | THE GLASS BLOCK? | | | 2) FIXED WINDOWS REPORT MISSING THE | | | TECH. DRAWINGS AND PRESSURES +/-. | | | 3)- 2ND FLOOR LIVING ROOM REAR ELEVATION | | | INDICATES (3) FIXEDWINDOWS VS. FLOOR | | | PLAN, A-2, 2ND FLOOR PLAN INDICATES | | | (3)25 SH WINDOWS ? | | | 4)- SHEET S-2 INDICATES HUGHES CONNECTIO | | | NS ON PLAN, THEY ARE NO LONGER IN BUSI- | | | NES. | | | 5)- SHEET S-3 CONN SCHEDULE HETAL-16, | | | SCHEDULE INDICATES 1365 LBS UPLIFT, | | | IS THIS A TYPE-O? SIMPON @ 160% INDI- | | | CATES 1635? CONNECTION #1 ON PLAN INDI- | | | CATES 1653 WITH 1 CONNECTION? | | | SHEET S-4 INDICATES STUCCO SOFFIT, NO | | | SPEC AS TO WIRE LATH OR NAILING FOR | | | HORIZONTAL SURFACES? SEE ASTM 1063 | | | 7.10.2.3. EXPANED 3/8" RIB LATH AND | | | SHEET LATH SHALL BE ATTACHED TO HORIZON- | | | TAL WOOD SUPPORTS.7.10.1.1 FOR 3/8 RIB | | | LATH SHALL BE ATTACHED AT EACH RIB (4"). | | | 6)- THE CONTRACTOR SHALL SUBMIT THE | | | PLANS TO PALMBEACH COUNTY BUILD. DEPT | | | FOR IMPACT FEE ASSESSMENT BEFORE THE | | | ISSUANCE OF PERMIT. | | | 7)- PAY STATE RADON FEES TO CITY. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561)659-8096 X 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2003-12-17 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-12-17 |
Time |
13:36 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2003-12-17 |
Time |
12:50 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-12-30 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-10 |
Time |
16:04 |
Rev Time |
0.50 |
| Received By |
btrobaug |
Date |
2002-12-30 |
Time |
17:35 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2002-03-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-03-13 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-03-13 |
Time |
06:42 |
Sent To |
R |
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2004-01-27 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-01-27 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2004-01-27 |
Time |
10:13 |
Sent To |
M |
|
| Notes |
| 2004-01-27 00:00:00 | TO PK BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2003-12-10 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-12-10 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-12-10 |
Time |
16:03 |
Sent To |
E |
|
| Notes |
| 2003-12-10 00:00:00 | TO BT DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2002-12-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-12-20 |
Time |
18:46 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-12-20 |
Time |
18:46 |
Sent To |
B |
|
| Notes |
| 2002-12-20 00:00:00 | TO JIM W./WRT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2004-02-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2004-02-05 |
Time |
13:42 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2004-02-05 |
Time |
12:21 |
Sent To |
B |
|
| Notes |
| 2004-02-05 00:00:00 | PROVISO: | | | 1.CONDENSING UNITS SHALL HAVE | | | SUFFICIENT CLEARANCE FOR SERVICE, | | | REPAIR, AND INSPECTION.2001 FBC(M) | | | 306.1. | | | | | | 2.EQUIPMENT INSTALLED AT A HEIGHT | | | GREATER THAN 16 FT, SHALL HAVE A | | | PERMENANT MEANS OF ACCESS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2003-12-22 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2004-01-27 |
Time |
10:13 |
Rev Time |
0.05 |
| Received By |
pkrauss |
Date |
2003-12-22 |
Time |
16:11 |
Sent To |
B |
|
| Notes |
| 2003-12-22 00:00:00 | NO MECHANICAL REVISION SUBMITTED FOR | | | REVIEW. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-06-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-12-18 |
Time |
17:54 |
Rev Time |
0.50 |
| Received By |
hmoser |
Date |
2002-06-20 |
Time |
18:57 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-03-07 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2002-03-07 |
Time |
17:24 |
Rev Time |
0.50 |
| Received By |
hmoser |
Date |
2002-03-07 |
Time |
17:23 |
Sent To |
|
|
| Notes |
| 2002-03-07 00:00:00 | PLAN DENIED | | | PLANS DO NOT MATCH ENERGY CALCS. | | | PLANS SHOW THREE A/C UNITS | | | ENERGY CALCS SHOW ONE A/C UNIOT | | | PLAN REVIEW BY HAROLD MOSER | | | [561]659-8096 EXT 8390 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2003-12-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-12-18 |
Time |
17:54 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-12-18 |
Time |
17:54 |
Sent To |
M |
|
| Notes |
| 2003-12-18 00:00:00 | REVISION OK - DELETED 2ND FLOOR W/M AND | | | ASSOCIATED FLOOR DRAIN |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-06-15 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-12-17 |
Time |
13:36 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2002-06-15 |
Time |
06:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-03-02 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2002-03-02 |
Time |
09:40 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2002-03-02 |
Time |
09:40 |
Sent To |
|
|
| Notes |
| 2002-03-02 00:00:00 | DENIED; | | | SANITARY RISER DIAGRAM; | | | 1.MASTER BATH BIDET NOT VENTED. | | | 2.POWDER BATH UNVENTED (NO VENT ON LAV) | | | 3.SECOND FLOOR BATH 3 W/C UNVENTED. | | | 4.NO MORE THAN 2 W/C ON 3" HORIZONTAL | | | BRANCH 94 SPC TABLE 714.1 NOTE 3. | | | 5.BATH 4 TUB NOT VENTED. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT 8369 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2002-04-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-03-13 |
Time |
14:46 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2004-02-26 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-02-26 |
Time |
08:45 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-02-26 |
Time |
08:45 |
Sent To |
B |
|
| Notes |
| 2004-02-26 00:00:00 | DENIED, NEED TO PROVIDE DIMENSION FOR | | | DRIVEWAY (LENTH WIDTH) AND DIMENSION OF | | | LOT. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2004-01-06 |
|
|
Cont ID |
|
| Sent By |
mmclean |
Date |
2004-01-06 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
mmclean |
Date |
2004-01-06 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2004-01-06 00:00:00 | DENIED, NEED 2 COPY OF SURVEY SHOWING | | | WORK WITH DIMENSION (LENGTH & WIDTH OF | | | DRIVEWAY) NEED TO MEET THE 1000SQ FT OR | | | 75% OF LANDSCAPE WHICHEVER IS LESS | | | TRIED CALLING OWNER BAD NUMBER FILE M MM |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-02-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2003-12-29 |
Time |
13:12 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|