Plan Review Details - Permit 02021514
Plan Review Stops For Permit 02021514
Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-03-08 Cont ID  
Sent By mcarsill Date 2002-03-08 Time 09:28 Rev Time 0.00
Received By mcarsill Date 2002-03-08 Time 09:28 Sent To  
Notes
***NONE***

Review Stop FS  
Rev No 2 Status P Date 2002-03-08 Cont ID  
Sent By mcarsill Date 2002-03-08 Time 09:28 Rev Time 0.00
Received By mcarsill Date 2002-03-08 Time 09:28 Sent To  
Notes
2002-03-08 00:00:00A) ACCORDING TO NFPA 13, 1999 EDITION,
 SECTION 5-13.6.1 "SIDEWALL SPRAY
 SPRINKLERS SHALL BE INSTALLED AT THE
 BOTTOM OF EACH ELEVATOR HOISTWAY NOT
 MORE THAN 2 FEET ABOVE THE FLOOR OF THE
 PIT". THE ONLY EXCEPTION TO THIS IS IF
 THE ELEVATOR SHAFT DOES NOT CONTAIN
 COMBUSTIBLE HYDRAULIC FLUIDS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop FS  
Rev No 1 Status F Date 2002-02-26 Cont ID  
Sent By mcarsill Date 2002-02-26 Time 11:27 Rev Time 0.00
Received By mcarsill Date 2002-02-26 Time 11:27 Sent To  
Notes
2002-02-26 00:00:00A) PLANS INDICATE THE WRONG ADDRESS.
 ALSO THE PLANS DO NOT APPEAR TO
 REFLECT THE FIRST FLOOR OF 215 SOUTH
 OLIVE AVENUE WHICH IS THE WAGG
 BUILDING.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-03-08 Cont ID  
Sent By mcarsill Date 2002-03-08 Time 09:28 Rev Time 0.00
Received By mcarsill Date 2002-03-08 Time 09:28 Sent To  
Notes
***NONE***