| Plan Review Stops For Permit 02021497 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2003-02-28 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2003-02-28 |
Time |
12:51 |
Rev Time |
1.00 |
| Received By |
lmartine |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2003-02-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-19 |
Time |
06:54 |
Rev Time |
3.00 |
| Received By |
jgomez |
Date |
2003-02-18 |
Time |
16:46 |
Sent To |
|
|
| Notes |
| 2003-02-18 00:00:00 | 1-NEED ENERGY CALCULATIONS. INFORMATION | | | SUBMITTED ARE MANUAL J CALCULATIONS | | | AND THOSE ARE FOR A/C EQUIPMENT. NEED | | | ENERGY CALCULATIONS, FORM 600A-97 | | | SINCE THIS PERMIT APPLICATION AND | | | DRAWINGS ARE BASED ON THE SBC 1997. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-11-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-12 |
Time |
14:09 |
Rev Time |
2.00 |
| Received By |
jgomez |
Date |
2002-11-14 |
Time |
10:39 |
Sent To |
M |
|
| Notes |
| 2002-11-14 00:00:00 | SECOND CHECKLIST: | | | 1-NEED RECORDED NOTICE OF COMMENCEMENT. | | | 2-PROVIDE ENERGY CACULATIONS AS REQUIRED | | | BY FLORIDA ENERGY EFFICIENCY CODE FOR | | | BUILDING CONSTRUCTION, 1997 ED. | | | 3-PROVIDE SOIL TEST REPORT. SECTION | | | 1804.2.7.2 CITY AMENDMENTS TO SBC 1997 | | | 4-PROVIDE COMPLETE SECTION/DETAILS AND | | | SPECS THRU CONCRETE BLOCK COLUMNS AT | | | REAR PORCH. SPECIFY ATTACHMENT OF | | | VERTICAL REINFORCEMENT TO LINTELS. | | | **NOTE: PROVIDE COMPLETE STRUCTURAL | | | SPECIFICATIONS FOR LINTELS TO BE USED. | | | SEC. 104.2.1.2 CITY AMENDMENTS TO SBC. | | | 5-SPECIFY SPECIFIC LOCATION OF STORAGE | | | SHED FOR ZONING REVIEW. | | | 6-NEED COMPLETE INFORMATION (2 COPIES) | | | FOR STORM PANELS AND: | | | A)KEY PLAN AND COMPLETE INSTALLATION | | | SCHEDULE. SEE CITY SAMPLE. | | | B)CLEARLY INDICATE ON DRAWINGS SPECIFIC | | | MOUNTING CONDITIONS AND ANCHOR TYPE & | | | SPACING TO BE USED ACCORDING TO THE | | | DESIGN PRESSURES, PANEL SPAN, EDGE | | | DISTANCE, MEAN ROOF HEIGHT, CONNECTION | | | TYPE AND STRUCTURE TO BE ATTACHED TO. | | | 7-CLARIFY FINISH ROOF MATERIAL. DRAWINGS | | | CALL FOR CEMENT TILE, BUT PRODUCT | | | APPROVAL SUBMITTED IS FOR SHINGLES. | | | 8-DECLARED CONTRUCTION VALUE IS TOO LOW. | | | OWES $642.96 FOR UPDATED VALUE AND | | | RADON FEES. | | | | | | NOTE: ALL THESE COMMENTS WERE WRITTEN ON | | | FIRST REVIEW BUT THEY WERE NOT | | | ADDRESSED. ADDITIONAL FEES WILL | | | BE CHARGED FOR RE-SUBMITTALS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-03-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-05 |
Time |
09:37 |
Rev Time |
2.50 |
| Received By |
jgomez |
Date |
2002-03-08 |
Time |
19:40 |
Sent To |
|
|
| Notes |
| 2002-03-08 00:00:00 | CHECKLIST: | | | 1-NEED RECORDED NOTICE OF COMMENCEMENT. | | | 2-BRING DRAWINGS TO PALM BEACH COUNTY TO | | | PAY IMPACT FEES. BRING BACK STAMPED | | | DAWINGS AND PAID RECEIPT. | | | 3-PROVIDE ENERGY CALCULATIONS AS REQ'D | | | BY FLORIDA ENERGY EFFICIENCY CODE FOR | | | BUILDING CONSTRUCTION, 1997 ED. | | | 4-PROVIDE SOIL TEST REPORT. SECTION | | | 1804.2.7.2 CITY AMENDMENTS TO SBC 1997 | | | 5-PROVIDE COMPLETE SECTION/DETAILS AND | | | SPECS THRU CONCRETE BLOCK COLUMNS AT | | | REAR PORC. SPECIFY ATTACHMENT OF STEEL | | | VERTICAL REINFORCEMENT TO LINTEL. | | | SEC. 104.2.2 CITY AMENDMENTS TO SBC/97 | | | 6-SPECIFY EXACT LOCATION OF SHED FOR | | | ZONING REVIEW. | | | 7-PROVIDE ATTIC ACCESS AT NEW ROOF. | | | SEC. 2309.6 SBC 1997. | | | 8-NEED COMPLETE INFORMATION (2 COPIES) | | | FOR STORM PANELS AND: | | | A)KEY PLAN AND COMPLETE INSTALLATION | | | SCHEDULE. SEE CITY SAMPLE ATTACHED. | | | B)CLEARLY INDICATE ON DRAWINGS SPECIFIC | | | MOUNTING CONDITIONS AND ANCHOR TYPE & | | | SPACING TO BE USED ACCORDING TO THE | | | MEAN ROOF HEIGHT, DESIGN PRESSURES, | | | PANEL SPAN, EDGE DISTANCE, CONNECTION | | | TYPE AND STRUCTURE TO BE ATTACHED TO | | | (CONCRETE BLOCK). | | | | | | 9-CLARIFY IF FINISH ROOF IS GOING TO BE | | | SHINGLES OR CONCRETE TILE. DRAWINGS | | | CALL FOR CONCRETE TILE. PRODUCT | | | APPROVAL SUBMITTED IS FOR SHINGLES. | | | 10-CONSTRUCTION VALUE DECLARED WAS TOO | | | LOW. OWES $642.96 FOR UPDATED VALUE | | | AND RADON FEES. | | | | | | NOTE: SEE ELECTRICAL, PLUMBING AND | | | MECHANICAL COMMENTS ATTACHED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2003-02-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-19 |
Time |
06:54 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-02-19 |
Time |
06:54 |
Sent To |
B |
|
| Notes |
| 2003-02-19 00:00:00 | ************** PROVISO/NOTES ********** | | | | | | 1)NOTE: PLEASE SEE LOAD CALCUALTIONS | | | DONE BY ENGINEER AND ELECTRICAL | | | CONTRACTOR. PLEASE NOTE, AHU HEAT IS | | | DERATED AT 65% AND THEN AGAIN @ 40%?? | | | PLEASE SEE NEC 220 FOR LOAD CALCS FOR | | | DERATING. CAN NOT BE DERATED TWICE. | | | PLEASE ALSO SEE LOAD CALCS DONE BY | | | ELECTRICAL CONTRACTOR. PLEASE NOTE, | | | AHU HEAT IS DERATED @40%.? CAN BE DONE | | | AT 100% OR DERATED AT 65%. PLEASE ALSO | | | SEE 3WATTS PER SQ FT BY ENGINEER AND | | | CONT., PLEASE RECONFIGURE LOAD CALCS. | | | ADDITION IS SHOWN AS BEING AS LARGE | | | AS EXISTING RES? | | | | | | 2)NOTE: PLEASE LIST THE REQ'D ARC FAULT | | | PROTECTED CIRCUITS ON PANEL SCHEDULE | | | PER 210-12. | | | | | | PLEASE REVISE AND SUBMIT THE ABOVE | | | INFORMATION FOR REVEIW BEFORE ANY | | | ROUGH ELECTRICAL INSPECTION OS CALLED | | | IN. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-6659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2003-02-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-12 |
Time |
13:36 |
Rev Time |
0.33 |
| Received By |
dpalmer |
Date |
2003-02-12 |
Time |
13:36 |
Sent To |
B |
|
| Notes |
| 2003-02-12 00:00:00 | *************** UNSAT *************** | | | | | | PLEASE SEE THE SAME PLANS WERE SUBMITTED | | | WITH NO CHANGES. PLEASE SEE COMMENTS | | | FROM FIRST TWO REVIEWS. | | | | | | PLEASE SUBMIT THE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | PLEASE TAKE OUT ALL OLD SHEETS AND | | | INSERT NEW SHEETS INTO TWO NEW COMPLETE | | | SETS FOR STAMPING AND REVIEW. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2002-10-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-06 |
Time |
16:56 |
Rev Time |
0.25 |
| Received By |
dpalmer |
Date |
2002-10-29 |
Time |
06:01 |
Sent To |
P |
|
| Notes |
| 2002-10-29 00:00:00 | ****************** UNSAT ********** | | | | | | 1)NOTE: PLEASE NOTE, FIRST TWO NOTES | | | FROM FIRST REVIEW WERE NOT ADDRESSED? | | | PLEASE SUBMIT A COMPLETED LOAD CALCULAT- | | | ION FOR NEW AS-WELL AS EXISTING PER | | | 220-3-C-1. PANEL SHOWN, SHOWS NEW A/C | | | SYSTEM AND NEW CIRCUIT W/OUT SHOWING | | | SIZE OF EXISTING SERVICE? | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-02-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-02-28 |
Time |
07:57 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-02-28 |
Time |
07:57 |
Sent To |
P |
|
| Notes |
| 2002-02-28 00:00:00 | ************* UNSAT ******************* | | | | | | 1)NOTE: PLEASE NOTE, LOAD CALCULATIONS | | | ARE NOT COMPLETE. PLEASE SEE 220-3-C-1 | | | PLEASE SHOW EXSITING AS WELL AS NEW. | | | | | | 2)NOTE: PLEASE NOTE NO "EXISTING" RISER | | | DIAGRAM WAS SUBMITTED. PLEASE CALRIFY | | | SIZE OF EXSITING SERVICE AND LOADS. | | | | | | 3) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | | | | 4) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 5)NOTE : PLEASE CLARIFY IF WASHER/DRYER | | | SHOWN AND WHAT APPEARS TO BE HWH IS | | | EXISTING AND JUST BEING MOVED TO NEW | | | LOCATION OR ARE THEY NEW? NOT SHOWN ON | | | PANEL SCHEDULE. | | | | | | 6)NOTE: PLEASE NOTE MISSING EGRESS | | | LIGHTING? PLEASE CLARIFY IF FANS SHOWN | | | ARE FAN/LT COMBO. 210-70 | | | | | | 7)NOTE: PLEASE NOTE MISSING GFI OUTLET | | | FOR A/C CU. PER 309.2 OF THE MECH CODE. | | | | | | 8)NOTE: PLEASE NOTE MISSING OUTLET FOR | | | AHU IN ATTIC. PER 210-63 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-02-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-06 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2003-02-06 |
Time |
16:53 |
Sent To |
E |
|
| Notes |
| 2003-02-06 00:00:00 | TO ELEC INBOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2003-01-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-06 |
Time |
16:53 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2003-01-10 |
Time |
13:29 |
Sent To |
E |
|
| Notes |
| 2003-01-10 00:00:00 | CALLED CONTRACTOR - CANNOT READ THE | | | DUCT LAYOUT OR GRILLE SIZES ON THE PLAN. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2002-11-18 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-11-18 |
Time |
13:11 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-11-18 |
Time |
13:10 |
Sent To |
|
|
| Notes |
| 2002-11-18 00:00:00 | DENIED: | | | | | | ONLY ONE COPY OF MECHANICAL PLAN AND | | | MANUAL J CALCS SUBMITTED (2 COPIES ARE | | | REQUIRED).PLEASE NOTE MECHANICAL | | | LAYOUT DONE IN PENCIL.MARKINGS SHALL | | | BE PERMANENT. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2002-03-05 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2002-11-14 |
Time |
10:58 |
Rev Time |
0.25 |
| Received By |
pkrauss |
Date |
2002-03-05 |
Time |
09:35 |
Sent To |
B |
|
| Notes |
| 2002-03-05 00:00:00 | | | | NO MECHANICAL PLANS SUBMITTED FOR | | | REVIEW.PLEASE PROVIDE PLANS WITH | | | MECHANICAL PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-11-08 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-11-08 |
Time |
18:01 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2002-11-08 |
Time |
17:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2002-03-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-10-29 |
Time |
06:22 |
Rev Time |
1.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-03 00:00:00 | PLUMBING PLAN REVIEW, PROVISO,SEE SHT-3 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-02-25 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-02-25 |
Time |
16:27 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|