Plan Review Details - Permit 02021497
Plan Review Stops For Permit 02021497
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2003-02-28 Cont ID  
Sent By lmartine Date 2003-02-28 Time 12:51 Rev Time 1.00
Received By lmartine Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2003-02-18 Cont ID  
Sent By dpalmer Date 2003-02-19 Time 06:54 Rev Time 3.00
Received By jgomez Date 2003-02-18 Time 16:46 Sent To  
Notes
2003-02-18 00:00:001-NEED ENERGY CALCULATIONS. INFORMATION
 SUBMITTED ARE MANUAL J CALCULATIONS
 AND THOSE ARE FOR A/C EQUIPMENT. NEED
 ENERGY CALCULATIONS, FORM 600A-97
 SINCE THIS PERMIT APPLICATION AND
 DRAWINGS ARE BASED ON THE SBC 1997.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-11-14 Cont ID  
Sent By dpalmer Date 2003-02-12 Time 14:09 Rev Time 2.00
Received By jgomez Date 2002-11-14 Time 10:39 Sent To M
Notes
2002-11-14 00:00:00SECOND CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PROVIDE ENERGY CACULATIONS AS REQUIRED
 BY FLORIDA ENERGY EFFICIENCY CODE FOR
 BUILDING CONSTRUCTION, 1997 ED.
 3-PROVIDE SOIL TEST REPORT. SECTION
 1804.2.7.2 CITY AMENDMENTS TO SBC 1997
 4-PROVIDE COMPLETE SECTION/DETAILS AND
 SPECS THRU CONCRETE BLOCK COLUMNS AT
 REAR PORCH. SPECIFY ATTACHMENT OF
 VERTICAL REINFORCEMENT TO LINTELS.
 **NOTE: PROVIDE COMPLETE STRUCTURAL
 SPECIFICATIONS FOR LINTELS TO BE USED.
 SEC. 104.2.1.2 CITY AMENDMENTS TO SBC.
 5-SPECIFY SPECIFIC LOCATION OF STORAGE
 SHED FOR ZONING REVIEW.
 6-NEED COMPLETE INFORMATION (2 COPIES)
 FOR STORM PANELS AND:
 A)KEY PLAN AND COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE.
 B)CLEARLY INDICATE ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE &
 SPACING TO BE USED ACCORDING TO THE
 DESIGN PRESSURES, PANEL SPAN, EDGE
 DISTANCE, MEAN ROOF HEIGHT, CONNECTION
 TYPE AND STRUCTURE TO BE ATTACHED TO.
 7-CLARIFY FINISH ROOF MATERIAL. DRAWINGS
 CALL FOR CEMENT TILE, BUT PRODUCT
 APPROVAL SUBMITTED IS FOR SHINGLES.
 8-DECLARED CONTRUCTION VALUE IS TOO LOW.
 OWES $642.96 FOR UPDATED VALUE AND
 RADON FEES.
  
 NOTE: ALL THESE COMMENTS WERE WRITTEN ON
 FIRST REVIEW BUT THEY WERE NOT
 ADDRESSED. ADDITIONAL FEES WILL
 BE CHARGED FOR RE-SUBMITTALS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-03-08 Cont ID  
Sent By pkrauss Date 2002-03-05 Time 09:37 Rev Time 2.50
Received By jgomez Date 2002-03-08 Time 19:40 Sent To  
Notes
2002-03-08 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-BRING DRAWINGS TO PALM BEACH COUNTY TO
 PAY IMPACT FEES. BRING BACK STAMPED
 DAWINGS AND PAID RECEIPT.
 3-PROVIDE ENERGY CALCULATIONS AS REQ'D
 BY FLORIDA ENERGY EFFICIENCY CODE FOR
 BUILDING CONSTRUCTION, 1997 ED.
 4-PROVIDE SOIL TEST REPORT. SECTION
 1804.2.7.2 CITY AMENDMENTS TO SBC 1997
 5-PROVIDE COMPLETE SECTION/DETAILS AND
 SPECS THRU CONCRETE BLOCK COLUMNS AT
 REAR PORC. SPECIFY ATTACHMENT OF STEEL
 VERTICAL REINFORCEMENT TO LINTEL.
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 6-SPECIFY EXACT LOCATION OF SHED FOR
 ZONING REVIEW.
 7-PROVIDE ATTIC ACCESS AT NEW ROOF.
 SEC. 2309.6 SBC 1997.
 8-NEED COMPLETE INFORMATION (2 COPIES)
 FOR STORM PANELS AND:
 A)KEY PLAN AND COMPLETE INSTALLATION
 SCHEDULE. SEE CITY SAMPLE ATTACHED.
 B)CLEARLY INDICATE ON DRAWINGS SPECIFIC
 MOUNTING CONDITIONS AND ANCHOR TYPE &
 SPACING TO BE USED ACCORDING TO THE
 MEAN ROOF HEIGHT, DESIGN PRESSURES,
 PANEL SPAN, EDGE DISTANCE, CONNECTION
 TYPE AND STRUCTURE TO BE ATTACHED TO
 (CONCRETE BLOCK).
  
 9-CLARIFY IF FINISH ROOF IS GOING TO BE
 SHINGLES OR CONCRETE TILE. DRAWINGS
 CALL FOR CONCRETE TILE. PRODUCT
 APPROVAL SUBMITTED IS FOR SHINGLES.
 10-CONSTRUCTION VALUE DECLARED WAS TOO
 LOW. OWES $642.96 FOR UPDATED VALUE
 AND RADON FEES.
  
 NOTE: SEE ELECTRICAL, PLUMBING AND
 MECHANICAL COMMENTS ATTACHED.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2003-02-19 Cont ID  
Sent By dpalmer Date 2003-02-19 Time 06:54 Rev Time 0.50
Received By dpalmer Date 2003-02-19 Time 06:54 Sent To B
Notes
2003-02-19 00:00:00************** PROVISO/NOTES **********
  
 1)NOTE: PLEASE SEE LOAD CALCUALTIONS
 DONE BY ENGINEER AND ELECTRICAL
 CONTRACTOR. PLEASE NOTE, AHU HEAT IS
 DERATED AT 65% AND THEN AGAIN @ 40%??
 PLEASE SEE NEC 220 FOR LOAD CALCS FOR
 DERATING. CAN NOT BE DERATED TWICE.
 PLEASE ALSO SEE LOAD CALCS DONE BY
 ELECTRICAL CONTRACTOR. PLEASE NOTE,
 AHU HEAT IS DERATED @40%.? CAN BE DONE
 AT 100% OR DERATED AT 65%. PLEASE ALSO
 SEE 3WATTS PER SQ FT BY ENGINEER AND
 CONT., PLEASE RECONFIGURE LOAD CALCS.
 ADDITION IS SHOWN AS BEING AS LARGE
 AS EXISTING RES?
  
 2)NOTE: PLEASE LIST THE REQ'D ARC FAULT
 PROTECTED CIRCUITS ON PANEL SCHEDULE
 PER 210-12.
  
 PLEASE REVISE AND SUBMIT THE ABOVE
 INFORMATION FOR REVEIW BEFORE ANY
 ROUGH ELECTRICAL INSPECTION OS CALLED
 IN. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-6659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2003-02-12 Cont ID  
Sent By dpalmer Date 2003-02-12 Time 13:36 Rev Time 0.33
Received By dpalmer Date 2003-02-12 Time 13:36 Sent To B
Notes
2003-02-12 00:00:00*************** UNSAT ***************
  
 PLEASE SEE THE SAME PLANS WERE SUBMITTED
 WITH NO CHANGES. PLEASE SEE COMMENTS
 FROM FIRST TWO REVIEWS.
  
 PLEASE SUBMIT THE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 PLEASE TAKE OUT ALL OLD SHEETS AND
 INSERT NEW SHEETS INTO TWO NEW COMPLETE
 SETS FOR STAMPING AND REVIEW.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-10-29 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 16:56 Rev Time 0.25
Received By dpalmer Date 2002-10-29 Time 06:01 Sent To P
Notes
2002-10-29 00:00:00****************** UNSAT **********
  
 1)NOTE: PLEASE NOTE, FIRST TWO NOTES
 FROM FIRST REVIEW WERE NOT ADDRESSED?
 PLEASE SUBMIT A COMPLETED LOAD CALCULAT-
 ION FOR NEW AS-WELL AS EXISTING PER
 220-3-C-1. PANEL SHOWN, SHOWS NEW A/C
 SYSTEM AND NEW CIRCUIT W/OUT SHOWING
 SIZE OF EXISTING SERVICE?
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-28 Cont ID  
Sent By dpalmer Date 2002-02-28 Time 07:57 Rev Time 0.00
Received By dpalmer Date 2002-02-28 Time 07:57 Sent To P
Notes
2002-02-28 00:00:00************* UNSAT *******************
  
 1)NOTE: PLEASE NOTE, LOAD CALCULATIONS
 ARE NOT COMPLETE. PLEASE SEE 220-3-C-1
 PLEASE SHOW EXSITING AS WELL AS NEW.
  
 2)NOTE: PLEASE NOTE NO "EXISTING" RISER
 DIAGRAM WAS SUBMITTED. PLEASE CALRIFY
 SIZE OF EXSITING SERVICE AND LOADS.
  
 3) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5)NOTE : PLEASE CLARIFY IF WASHER/DRYER
 SHOWN AND WHAT APPEARS TO BE HWH IS
 EXISTING AND JUST BEING MOVED TO NEW
 LOCATION OR ARE THEY NEW? NOT SHOWN ON
 PANEL SCHEDULE.
  
 6)NOTE: PLEASE NOTE MISSING EGRESS
 LIGHTING? PLEASE CLARIFY IF FANS SHOWN
 ARE FAN/LT COMBO. 210-70
  
 7)NOTE: PLEASE NOTE MISSING GFI OUTLET
 FOR A/C CU. PER 309.2 OF THE MECH CODE.
  
 8)NOTE: PLEASE NOTE MISSING OUTLET FOR
 AHU IN ATTIC. PER 210-63
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-02-06 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 16:53 Rev Time 0.00
Received By dpalmer Date 2003-02-06 Time 16:53 Sent To E
Notes
2003-02-06 00:00:00TO ELEC INBOX

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2003-01-10 Cont ID  
Sent By dpalmer Date 2003-02-06 Time 16:53 Rev Time 0.25
Received By pkrauss Date 2003-01-10 Time 13:29 Sent To E
Notes
2003-01-10 00:00:00CALLED CONTRACTOR - CANNOT READ THE
 DUCT LAYOUT OR GRILLE SIZES ON THE PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-11-18 Cont ID  
Sent By pkrauss Date 2002-11-18 Time 13:11 Rev Time 0.45
Received By pkrauss Date 2002-11-18 Time 13:10 Sent To  
Notes
2002-11-18 00:00:00DENIED:
  
 ONLY ONE COPY OF MECHANICAL PLAN AND
 MANUAL J CALCS SUBMITTED (2 COPIES ARE
 REQUIRED).PLEASE NOTE MECHANICAL
 LAYOUT DONE IN PENCIL.MARKINGS SHALL
 BE PERMANENT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-03-05 Cont ID  
Sent By jgomez Date 2002-11-14 Time 10:58 Rev Time 0.25
Received By pkrauss Date 2002-03-05 Time 09:35 Sent To B
Notes
2002-03-05 00:00:00 
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 2 Status P Date 2002-11-08 Cont ID  
Sent By kstevens Date 2002-11-08 Time 18:01 Rev Time 0.25
Received By kstevens Date 2002-11-08 Time 17:54 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-03-03 Cont ID  
Sent By dpalmer Date 2002-10-29 Time 06:22 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2002-03-03 00:00:00PLUMBING PLAN REVIEW, PROVISO,SEE SHT-3

Review Stop Z ZONING
Rev No 1 Status P Date 2002-02-25 Cont ID  
Sent By sgraham Date 2002-02-25 Time 16:27 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***