| Plan Review Stops For Permit 02021488 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2003-01-28 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2003-01-28 |
Time |
14:12 |
Rev Time |
0.50 |
| Received By |
jwitmer |
Date |
2003-01-28 |
Time |
13:52 |
Sent To |
|
|
| Notes |
| 2003-01-28 00:00:00 | BUTT GLASS DETAIL/ ENGINEEREDOK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
P |
Date |
2002-08-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-08-30 |
Time |
14:41 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
2002-08-30 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2002-08-30 00:00:00 | REVISION 8/23/02 GARAGE ENTRY |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2002-08-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-08-02 |
Time |
09:32 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-08-02 00:00:00 | ******PROVISO****** | | | SHEET A3/4 INDICATES USE OF A CIRCULAR | | | STAIRWAY. THIS SHALL NOT BE COVERED | | | UNDER THIS PERMIT. A SEPERATE PERMIT | | | SHALL BE REQUIRED WITH PLANS REVIEWS | | | AND ASSOCIATED FEES. | | | JIM WITMER | | | BUILDING PLAN REVIEW |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
F |
Date |
2002-07-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-07-29 |
Time |
16:16 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2002-07-29 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2002-07-29 00:00:00 | | | | BUILDING PLAN REVIEW | | | PERMIT: 02021488 | | | ADD: 7645 HAWKS LANDING DR | | | CONT: CRIBB CONSTRUCTION | | | TEL: (561)689-6900 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1) SHEET A3/4 INDICATE THE USE OF A | | | CIRCULAR STAIR TO A LOFT. PROVIDE THE | | | MANUFACTURERS SPEC TO ASURE COMPLIANCE | | | WITH SBC 1007.8.2. | | | | | | 2) PROVIDE ENGINEERING FOR BUTT GLASS | | | ASSEMBLIES PER 1997 SBC 2406.2. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2002-06-29 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-07-24 |
Time |
10:22 |
Rev Time |
1.50 |
| Received By |
jwitmer |
Date |
2002-06-29 |
Time |
15:41 |
Sent To |
|
|
| Notes |
| 2002-06-29 00:00:00 | | | | BUILDING PLAN REVIEW | | | PERMIT: 02021488 | | | ADD: 7645 HAWKS LANDING | | | CONT: CRIBB CONSTRUCTION | | | TEL: (561) 689-6900 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1) CLOSPAY DOOR (GARAGE DOOR) AS PER | | | NOTE TO BE SUBMITTED LATER, IF REMOVED | | | FROM PERMIT, A SEPERATE PERMIT, REVIEW | | | AND FEES SHALL OCCUR? | | | | | | THE ARCHETECT SHALL INDICATE AS TO WHAT | | | SIZE MULLION IS TO BE USED IN CONJUNC- | | | TION WITH THE DIFFERENT CONFIGURATION | | | OF GLAZING ARANGEMENTS, OR THE GLAZING | | | CONTRACTOR SUBMIT SHOP DRAWINGS THAT THE | | | DESIGNER OF RECORD HAS REVIEWED AND | | | APPROVED. | | | | | | THE PRODUCT TESTING REPORTS SUBMITTED | | | FOR OPERABLE WINDOWS IS FOR CASEMENT | | | WINDOWS, SHEET A-3 INDICATES THE USE OF | | | SINGLE HUNG WINDOWS. SUBMIT THE APPROPRI | | | ATE REPORTS. | | | | | | SHEETS A3/4 INDICATE THE USE OF A | | | CIRCULAR STAIR TO A LOFT. PROVIDE THE | | | MANUFACTURERS SPEC TO ASURE COMPLIANCE | | | WITH SBC 1007.8.2. | | | | | | GAS FIREPLACE, NO INFORMATION HAS BEEN | | | PROVIDED FOR THE GAS FIREPLACE LOCATED | | | IN THE LIVINGROOM. FACTORY BUILT FIRE- | | | PLACES SHALL MEET BE TESTED IN ACCORD- | | | ANCE WITH AND MEET THE REQUIREMENTS OF | | | UL 127. FACTORY BUILT FIREPLACES SHALL | | | BE INSTALLED IN ACCORDANCE WITH | | | 2114.3.10. PROVIDE INFORMATION FOR THE | | | COMBUSTIBLE CLEARENCES ALLOWED, FRESH | | | AIR INTAKE,AS WELL AS THE CHEMNEY. | | | | | | PROVIDE ENGINEERING FOR BUTT GLASS | | | ASSEMBLIES PER 1997 SBC 2406.2. | | | | | | SHEET A-8 DETAIL A & B INDICATE THE | | | USE OF MULTIPLE(4) STRAPS IN A CONCRETE | | | BEAM. USP REQUIRES A DERATING WHEN | | | STRAPS ARE PLACED CLOSER THAN 8" BECAUSE | | | OF THE "CONE PULL OUT AFFECT". HOW MUCH | | | DERATING DOES USP REQUIRE ON THIS TYPE | | | CONFIGURATION? | | | | | | LOOK FOR COMMENTS BY THE OTHER PLAN | | | REVIEW DISCIPLINES THAT MAY BE WRITTEN | | | ON THE APPLICATION, PLANS, OR ATTACHED | | | SEPARATELY. WHEN RESUBMITTING PLANS | | | PLEASE CLEARLY INDICATE THE REVISION AND | | | REMOVE AND REPLACE ANY PAGES AS NECESS- | | | ARY. A TRANSMITTAL LETTER LISTING THE | | | ORIGINAL REVIEW COMMENT NUMBER, WITH A | | | DESCRIPTION OF THE REVISION MADE, IDEN- | | | TIFYING THE SHEET OR SPECIFICATION PAGE | | | WHERE THE CHANGES CAN BE FOUND, WILL | | | HELP TO EXPEDITE YOUR PERMIT. THANK YOU | | | FOR YOUR ANTICIPATED COOPERATION. | | | JIM WITMER | | | PLAN REVIEW | | | TEL: (561)659-8096 EX.8412 | | | FAX: (561)659-8026 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2002-06-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-06-06 |
Time |
16:54 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2002-07-02 |
Time |
14:44 |
Sent To |
|
|
| Notes |
| 2002-06-06 00:00:00 | SEE NOTES FROM PREVIOUS REVIEW, NOT | | | COMPLETED. MONIES, DUE | | | 3RD REVIEW 10% PERMIT FEE | | | SEE NOTES FROM PREVIOUS REVIEW, NOT | | | COMPLETE, MONIES DUE+ 3RD REVIEW | | | 10% OF PERMIT FEE! |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-04-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-04-06 |
Time |
12:18 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2002-04-06 |
Time |
12:18 |
Sent To |
|
|
| Notes |
| 2002-04-06 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT # 02021488 | | | 7645 HAWKS LANDING | | | CONT: CRIBB | | | TEL: 689-6900 | | | | | | SBC= 1997 STANDARD BUILDING CODE | | | | | | 1) DESIGN CRITERIA SHEET NOT SEALED BY | | | THE ARCHETECT OF RECORD, DOCUMENTS FOR | | | PUBLIC RECORD SHALL BE SIGNED & SEALED | | | 61G1-16.003 | | | 2)- CLOSPY DOOR (GARAGE DOOR) REPORT | | | INDICATED OR WAS CIRCLED INDICATING THE | | | USE OF THE 4050 MODEL DOOR, THIS DOOR | | | DOESN'T MEET THE POSITIVE OR NEGATIVE | | | PRESSURES, ALSO WILL NOT MEET THE | | | REQUIREMENTS OF THE 16'-0" X 8'-0" | | | OPENING. | | | 3)- THE ARCH. SHALL INDICATE AS TO WHICH | | | MULLION IS TO BE USED IN CONJUNCTION | | | WITH THE DIFFERENT WINDOW CONFIGURATIONS | | | HORIZONTAL & VERTICAL MULLIONS. | | | 4)- PRODUCT APPROVAL FOR CASEMENT WINDOW | | | BUT NOT FOR SINGLE HUNG WINDOWS. | | | 5)- SHEET A-3&4 INDICATE THE USE OF A | | | CIRCULAR STAIR TO A LOFT. PROVIDE THE | | | MANUFACTURERS SPEC FOR COMPARISON TO | | | SBC 1007.8.2. | | | 6)- SBC 104.2.2 ADDITIONAL INFORMATION | | | SHALL BE REQUIRED ON THE LOFT IN THE | | | LIBRARY. A CUT SECTION THROUGH WOULD | | | GIVE BETTER DETAIL. SBC 503.2.3 MEZANINE | | | SBC 1203.2.1 OCCUPIABLE ROOMS MINIMUM | | | CEILING HEIGTH OF 7'-6" ARE CONCERNS. | | | INDICATE STRUCTURAL DETAILS? | | | 7)- SBC 104.2.2 MISSING INFORMATION ON | | | THE FIRE PLACE &CHIMNEY IN THE LIVING | | | ROOM, THE VENTLESS FIREPLACE IN THE | | | COVERED PORCH AND THE GRILL. | | | 8)-SHEET A-8 DISCREPANCY THE TRUSS | | | STRAP SCHEDULE INDICATES THE USE OF USP | | | FOR TRUSS ANCHORS VS THE DETAILS WHICH | | | SPECIFY SEMCO WHICH IS NO LONGER IN | | | BUSINESS?WHAT ARE THE NEW CATALOG #? | | | 9)- SHEET A-8DEAIL A & B INDICATE THE | | | USE OF MULTIPLE OR SEVERAL STRAPS IN | | | A CONCRETE BEAM OR CMU. USP REQUIRES A | | | DERATING WHEN STRAPS ARE PLACED CLOSER | | | THAN 8" BECAUSE OF THE CONE PILL OUT | | | AFFECT. HOW MUCH DERATING DOES USP | | | REQUIRE? | | | 10)- PLANS ARE TO BE ASSESSED BY PALM | | | BEACH COUNTY FOR IMPACT FEES BEFORE | | | THE ISSUANCE OF A PERMIT. | | | 11)- ADDITIONAL FEES DUE! | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561)659-8096 X 8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2002-07-24 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-07-24 |
Time |
07:46 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-07-23 |
Time |
14:42 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2002-06-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-21 |
Time |
14:44 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-06-27 |
Time |
09:48 |
Sent To |
R |
|
| Notes |
| 2002-06-27 00:00:00 | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ | | | NOT ALL NOTES FROM THE FIRST AND SECOND | | | REVIEWS HAVE BEEN CORRECTED.PLEASE | | | CORRECT THEM AND THE FOLLOWING AND | | | RESUBMIT FOR REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | NEED THE RATING NOT A NOTE. | | | | | | 2} CORRECT THE MARKING ON THE SERVICE | | | GEAR,"TMB","TLO". | | | | | | 3} LIST THE OCP AND WIRE SIZE FOR PANEL | | | "C" ON PANEL"B"SCHEDULE.INCLUDE IN THE | | | CALCULATION FOR "B" PANEL. | | | | | | 4} PLEASE NOTE THE OCP FOR THE 5KW HEAT | | | STRIP EXCEEDS 150%. | | | | | | 5} SMOKE DETECTORS PER 2-2.1.1.1(BED RMS | | | 3 & 4). | | | | | | 6} GFI TO BE INSTALLED IN FRONT OF THE | | | RESIDENCE PER 210-52(E). | | | | | | 7} THE RERIGERATOR CIRCUIT IN PANEL "A" | | | IS SHOWN AS 3KW ON A SINGLE POLE 20AMP | | | BREAKER EXCEEDING 80% OF THE BREAKER | | | RATING.PLEASE CORRECT. | | | | | | 8} ATTIC ACCESS FOR AHU #2 MUST COMPLY | | | WITH 210-70(A)(3) & 210-63.PLEASE | | | INDICATE SAME ON PLANS. | | | | | | 9} THE PLAN SHOWS A DISCONNECT NEXT TO | | | THE METER AND NOT ON THE RISER,PLEASE | | | CLARIFY ON THE PLAN. | | | | | | 10} NOTE THE LIVING ROOM IS MISSING A | | | RECEPTACLE PER 210-52(A)(1). | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT.8392 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2002-06-05 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-06-05 |
Time |
06:05 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-06-05 |
Time |
06:05 |
Sent To |
M |
|
| Notes |
| 2002-06-05 00:00:00 | ***************** UNSAT ************* | | | | | | PLEASE NOTE THAT NO ALL NOTES FORM FIRST | | | REVIEW WERE ADDRESSED. | | | | | | 1)NOTE: PLEASE SEE 310-15 FOR SIZING OF | | | 350MCM FOR SERVICE. A 400A SERVICE IS | | | SHOWN.(NOTE#4 FIRST REVIEW) | | | | | | 2)NOTE: PLEASE NOTE THAT PANEL "B" STILL | | | DOES NOT SHOW OCP FOR FEEDING PANEL "C" | | | IF PANEL "B" HAS FEED THROUGH LUGS, THEN | | | WIRE SIZE NEEDS TO INCREASE TO MEET MAIN | | | OCP OF 200AMPS. (NOTE #6 FIRST REVIEW) | | | LOAD CALCS NOT INCLUDED ON "B" FOR "C"?? | | | 3)NOTE: PLEASE NOTE PLANS STILL MISSING | | | OUTLET SPACING TO MEET 210-52/210-52H | | | PLEASE ALSO NOTE KITCHEN LAYOUT FOR | | | COUNTERSPACE HAS CHANGED. PLEASE NOTE | | | MISSING GFI/OUTLET(S) PER210-52-C-1. | | | (NOTE# 9 FIRST REVIEW) | | | | | | 4)NOTE: PLEASE NOTE PANEL SCHEDULE SHOWS | | | BEDROOM CIRCUITS, BUT NO MENTION OF | | | ARC FAULT PROTECTION PER 210-12. CAN BE | | | A NOTE ON PLANS. | | | | | | 5)NOTE: PLEASE NOTE SMOKE DETECTORS | | | STILL MISSING PER NFPA-72. MISSING IN | | | VICINITY OF STAIRS LEADING TO ABOVE FLR. | | | 2-5.2.1.4 PLEASE ALSO NOTE A SD HAS BEEN | | | PLACED IN MASTER BATH. PLEASE NOTE THAT | | | THIS IS NOT PERMITTED PER 2-5.2.1.6. | | | PLEASE NOTE THERE A FEW SD`S SHOWN THAT | | | GO ABOVE AND BEYOND WHAT IS REQ`D. | | | PLEASE NOTE, IF SHOWN ON PLANS THEN | | | THEY WILL BE REQ`D TO BE INSTALLED OR | | | PLANS MAY NEED TO BE REVISED AT A LATER | | | DATE. JUST A NOTE. | | | (NOTE#2 FROM FIRST REVIEW) | | | | | | 6)NOTE: PLEASE NOTE OCP FOR 5KW HEAT | | | STRIP SHOWN AT 50AMPS? PLEASE VERIFY. | | | MAX OCP 150%? | | | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. | | | ONCE AGAIN, IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-03-08 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-08 |
Time |
10:27 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-03-08 |
Time |
10:27 |
Sent To |
B |
|
| Notes |
| 2002-03-08 00:00:00 | ***************** UNSAT ************* | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | THIS NOTE IS ON THE PLANS AND ARE FROM | | | PREVIOUS REVIEW NOTES? PLEASE ACTUALLY | | | SUBMIT THE RATINGS. | | | | | | 2) NOTE: SMOKE DETECTORS ARE REQUIRED | | | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. | | | ALSO ON EACH LEVEL OF A MULTI-LEVEL | | | DWELLING UNIT. ROOMS WITH BATHS AND OR | | | CLOSETS ARE CONSIDERED SLEEPING ROOMS. | | | PER NFPA-72 2-2.1.1.1. | | | MISSING IN MANY LOCATIONS. PLEASE NOTE | | | THAT ROOMS WITH BATHS AND/OR CLOSETS ARE | | | ADAPTABLE SLEEPING RMS. | | | | | | 3) NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | GOING TO BUILDING STEEL AND COLD WATER | | | PER 250-50. | | | MISSING BLDG/FOOTER STEEL. | | | | | | 4)NOTE: PLEASE NOTE THAT RISER DIAGRAM | | | SHOWS 350 MCM BEING INSTALLED. PLEASE | | | NOTE THAT PER 310-15 350MCM IS GOOD FOR | | | A 350A SERVICE. PLEASE NOTE THAT TWO, | | | 200A PANELS ARE GOING IN? | | | | | | 5)NOTE: PLEASE NOTE THAT THERE IS AN | | | EQUIPMENT GROUNDING CONDUCTOR SHOWN | | | BETWEEN GUTTER AND MAIN DISC #1. PLEASE | | | NOTE THAT THIS IS PARALLELING THE | | | NEUTRAL? PLEASE REMOVE. | | | | | | 6)NOTE: PLEASE NOTE THAT PANEL "B", SHOW | | | -S FEED TO PANEL "C" BUT DOES NOT SHOW | | | OCP.? FEEDERS ARE NOTED ON RISER DIAGRAM | | | . | | | | | | 7)NOTE: PLEASE NOTE THAT PLAN SHOW FOUR | | | A/C COND UNITS AND ONLY 3 SETSARE | | | SHOWN ON PANEL SCHEDULES AND LOAD CALCS. | | | | | | 8)NOTE: PLEASE SHOW ROOM DESIGNATION | | | ON PLANS. | | | | | | 9) NOTE: PLEASE SHOW ALL OUTLET SPACING | | | TO MEET 2`,6`,12` RULE PER 210-52. | | | MISSING IN ENTIRE LIVING ROOM? | | | AND A FEW OTHERS. | | | | | | 10)PLEASE NOTE MISSING OUTLET(S) REQ`D | | | BY 210-52E OF THE NEC. | | | MISSING FRONT. | | | | | | 11)NOTE: PLEASE NOTE MISSING REC FOR | | | AHU #1 PER MECH CODE.309.2 | | | | | | 12)NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | BATHS ARE NOW SHOWN AS 15A AND #14?? | | | | | | 13)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | CIRCUITS ON PLANS PER 210-12. CODE WENT | | | INTO EFFECT 1/1/2002. | | | | | | 14)NOTE: PLEASE NOTE 60A OCP SHOWN FOR | | | 5KW HEAT FOR A/C SYSTEM ON PANEL "C". | | | PLEASE CORRECT. | | | | | | 15)NOTE: PLEASE CLARIFY 3KW FOR A SINGLE | | | POLE 20A BRKR FOR FRIG CIRCUIT. | | | PLEASE NOTE 80% MAX LOAD FOR BRANCH | | | CIRCUIT AND RATING OF BRKR.PER 384 | | | | | | 16)NOTE: PLEASE SHOW OUTLETS ABOVE BATH | | | AS GFI/GFI PROTECTED. 210-8 | | | | | | 17)NOTE: PLEASE NOTE REC AND LT REQ`D | | | FOR AHU`S #2,3, IN ATTIC. | | | ATTIC ACCESS.PER 210-63/210-70 AND 309.2 | | | NEC AND MECH CODE. | | | | | | 18)NOTE: PLEASE NOTE THAT PLANS ONLY | | | SHOWS ONE MAIN NEXT TO METER. PLEASE | | | SHOW BOTH MAINS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-10-01 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-10-01 |
Time |
15:29 |
Rev Time |
0.00 |
| Received By |
csiegber |
Date |
2003-10-01 |
Time |
15:29 |
Sent To |
P |
|
| Notes |
| 2003-10-01 00:00:00 | TO KS BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2003-01-09 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-01-09 |
Time |
12:56 |
Rev Time |
0.28 |
| Received By |
pkrauss |
Date |
2003-01-09 |
Time |
12:30 |
Sent To |
|
|
| Notes |
| 2003-01-09 00:00:00 | MECH REV PERMIT 02021493 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2002-07-24 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-07-24 |
Time |
10:17 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-07-24 |
Time |
10:17 |
Sent To |
B |
|
| Notes |
| 2002-07-24 00:00:00 | MECHANICAL PERMIT 02021493 | | | | | | AIR MAKE-UP FOR THE COMBUSTION AIR ON | | | PLAN SHEET A-3. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2002-06-21 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-07-24 |
Time |
07:46 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-06-20 |
Time |
11:22 |
Sent To |
E |
|
| Notes |
| 2002-06-21 00:00:00 | DENIED:MECHANICAL PERMIT 02021493 | | | | | | ITEMS#1 & 3 FROM REVIEW DATED 6/5/02 | | | NOT ADDRESSED. | | | | | | 1. AXILIARY DRAIN SHALL TERMINATE AT A | | | CONSPICUOUS POINT.PLEASE CLARIFY | | | HOW THE AXUILIARY DRAIN LINE RUN WITH | | | & TERMINATING AT THE SAME POINT AS | | | THE PRIMARY DRAIN IS A "CONSPICUOUS | | | POINT". | | | | | | 3. SHOW COMPLIANCE WITH 1997 SMC 704, | | | FOR COMBUSTION AIR. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2002-06-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-06-05 |
Time |
06:35 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-06-06 |
Time |
07:01 |
Sent To |
|
|
| Notes |
| 2002-06-06 00:00:00 | | | | | | | 1.AS PER 1997 SMC AUXILIARY DRAIN | | | SHALL TERMINATE AT A CONSPICUOUS | | | POINT TO SERVICE AS AN ALARM THAT | | | THE PRIMARY DRAIN IS RESTRICTED. | | | PLEASE CLARIFY HOW THE AUXILARY | | | DRAIN LINE RUN WITH & TERMINATING | | | AT THE SAME POINT AS THE PRIMARY | | | DRAIN IS A "CONSPICUOUS POINT". | | | | | | 2.PROVIDE MANUFACTURER INSTALLATION | | | INSTRUCTIONS FOR THE GAS FIREPLACE, | | | GRILL W/HOOD & VENTLESS F.P. SHOWN | | | ON PLAN SHEET A-3. | | | | | | 3.PROVIDE INFORMATION ON VENT FOR THE | | | GAS DRYER & SHOW COMPLIANCE WITH | | | CHAPTER 7 OF THE 1997 SMC. | | | | | | 4.AHU'S SHALL HAVE ADEQUATE ACCESS FOR | | | MAINTENANCE & SERVICE AS PER 1997 | | | SMC 304.2 & 304.4. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-03-06 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2002-03-06 |
Time |
19:36 |
Rev Time |
0.33 |
| Received By |
hmoser |
Date |
2002-03-06 |
Time |
19:36 |
Sent To |
|
|
| Notes |
| 2002-03-06 00:00:00 | PLAN DENIED | | | ENERGY CALCS AND PLANS DO NOT MATCH | | | ENERGY CALCS SHOW ONE A/C UNIOT | | | PLANS SHOW THREE A/C UNIOTS | | | PLAN REVIEW BY HAROLD MOSER | | | [561]659-8096 EXT.8390 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2003-10-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2003-10-11 |
Time |
14:08 |
Rev Time |
0.50 |
| Received By |
kstevens |
Date |
2003-10-11 |
Time |
14:08 |
Sent To |
|
|
| Notes |
| 2003-10-11 00:00:00 | REVISION OK - SANT. RISER DIAGRAM |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2002-03-02 |
|
|
Cont ID |
|
| Sent By |
csiegber |
Date |
2003-10-01 |
Time |
15:29 |
Rev Time |
0.33 |
| Received By |
jleech |
Date |
2002-03-02 |
Time |
08:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-02-28 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-02-28 |
Time |
09:46 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|