Plan Review Details - Permit 02021488
Plan Review Stops For Permit 02021488
Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2003-01-28 Cont ID  
Sent By jwitmer Date 2003-01-28 Time 14:12 Rev Time 0.50
Received By jwitmer Date 2003-01-28 Time 13:52 Sent To  
Notes
2003-01-28 00:00:00BUTT GLASS DETAIL/ ENGINEEREDOK

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2002-08-30 Cont ID  
Sent By jwitmer Date 2002-08-30 Time 14:41 Rev Time 1.00
Received By jwitmer Date 2002-08-30 Time 14:40 Sent To  
Notes
2002-08-30 00:00:00REVISION 8/23/02 GARAGE ENTRY

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2002-08-02 Cont ID  
Sent By jwitmer Date 2002-08-02 Time 09:32 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-08-02 00:00:00******PROVISO******
 SHEET A3/4 INDICATES USE OF A CIRCULAR
 STAIRWAY. THIS SHALL NOT BE COVERED
 UNDER THIS PERMIT. A SEPERATE PERMIT
 SHALL BE REQUIRED WITH PLANS REVIEWS
 AND ASSOCIATED FEES.
 JIM WITMER
 BUILDING PLAN REVIEW

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2002-07-29 Cont ID  
Sent By jwitmer Date 2002-07-29 Time 16:16 Rev Time 1.50
Received By jwitmer Date 2002-07-29 Time 16:16 Sent To  
Notes
2002-07-29 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02021488
 ADD: 7645 HAWKS LANDING DR
 CONT: CRIBB CONSTRUCTION
 TEL: (561)689-6900
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) SHEET A3/4 INDICATE THE USE OF A
 CIRCULAR STAIR TO A LOFT. PROVIDE THE
 MANUFACTURERS SPEC TO ASURE COMPLIANCE
 WITH SBC 1007.8.2.
  
 2) PROVIDE ENGINEERING FOR BUTT GLASS
 ASSEMBLIES PER 1997 SBC 2406.2.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2002-06-29 Cont ID  
Sent By pkrauss Date 2002-07-24 Time 10:22 Rev Time 1.50
Received By jwitmer Date 2002-06-29 Time 15:41 Sent To  
Notes
2002-06-29 00:00:00 
 BUILDING PLAN REVIEW
 PERMIT: 02021488
 ADD: 7645 HAWKS LANDING
 CONT: CRIBB CONSTRUCTION
 TEL: (561) 689-6900
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1) CLOSPAY DOOR (GARAGE DOOR) AS PER
 NOTE TO BE SUBMITTED LATER, IF REMOVED
 FROM PERMIT, A SEPERATE PERMIT, REVIEW
 AND FEES SHALL OCCUR?
  
 THE ARCHETECT SHALL INDICATE AS TO WHAT
 SIZE MULLION IS TO BE USED IN CONJUNC-
 TION WITH THE DIFFERENT CONFIGURATION
 OF GLAZING ARANGEMENTS, OR THE GLAZING
 CONTRACTOR SUBMIT SHOP DRAWINGS THAT THE
 DESIGNER OF RECORD HAS REVIEWED AND
 APPROVED.
  
 THE PRODUCT TESTING REPORTS SUBMITTED
 FOR OPERABLE WINDOWS IS FOR CASEMENT
 WINDOWS, SHEET A-3 INDICATES THE USE OF
 SINGLE HUNG WINDOWS. SUBMIT THE APPROPRI
 ATE REPORTS.
  
 SHEETS A3/4 INDICATE THE USE OF A
 CIRCULAR STAIR TO A LOFT. PROVIDE THE
 MANUFACTURERS SPEC TO ASURE COMPLIANCE
 WITH SBC 1007.8.2.
  
 GAS FIREPLACE, NO INFORMATION HAS BEEN
 PROVIDED FOR THE GAS FIREPLACE LOCATED
 IN THE LIVINGROOM. FACTORY BUILT FIRE-
 PLACES SHALL MEET BE TESTED IN ACCORD-
 ANCE WITH AND MEET THE REQUIREMENTS OF
 UL 127. FACTORY BUILT FIREPLACES SHALL
 BE INSTALLED IN ACCORDANCE WITH
 2114.3.10. PROVIDE INFORMATION FOR THE
 COMBUSTIBLE CLEARENCES ALLOWED, FRESH
 AIR INTAKE,AS WELL AS THE CHEMNEY.
  
 PROVIDE ENGINEERING FOR BUTT GLASS
 ASSEMBLIES PER 1997 SBC 2406.2.
  
 SHEET A-8 DETAIL A & B INDICATE THE
 USE OF MULTIPLE(4) STRAPS IN A CONCRETE
 BEAM. USP REQUIRES A DERATING WHEN
 STRAPS ARE PLACED CLOSER THAN 8" BECAUSE
 OF THE "CONE PULL OUT AFFECT". HOW MUCH
 DERATING DOES USP REQUIRE ON THIS TYPE
 CONFIGURATION?
  
 LOOK FOR COMMENTS BY THE OTHER PLAN
 REVIEW DISCIPLINES THAT MAY BE WRITTEN
 ON THE APPLICATION, PLANS, OR ATTACHED
 SEPARATELY. WHEN RESUBMITTING PLANS
 PLEASE CLEARLY INDICATE THE REVISION AND
 REMOVE AND REPLACE ANY PAGES AS NECESS-
 ARY. A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A
 DESCRIPTION OF THE REVISION MADE, IDEN-
 TIFYING THE SHEET OR SPECIFICATION PAGE
 WHERE THE CHANGES CAN BE FOUND, WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
 JIM WITMER
 PLAN REVIEW
 TEL: (561)659-8096 EX.8412
 FAX: (561)659-8026

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-06-06 Cont ID  
Sent By jwitmer Date 2002-06-06 Time 16:54 Rev Time 0.00
Received By jwitmer Date 2002-07-02 Time 14:44 Sent To  
Notes
2002-06-06 00:00:00SEE NOTES FROM PREVIOUS REVIEW, NOT
 COMPLETED. MONIES, DUE
 3RD REVIEW 10% PERMIT FEE
 SEE NOTES FROM PREVIOUS REVIEW, NOT
 COMPLETE, MONIES DUE+ 3RD REVIEW
 10% OF PERMIT FEE!

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-04-06 Cont ID  
Sent By jwitmer Date 2002-04-06 Time 12:18 Rev Time 2.22
Received By jwitmer Date 2002-04-06 Time 12:18 Sent To  
Notes
2002-04-06 00:00:00BUILDING PLAN REVIEW
 PERMIT # 02021488
 7645 HAWKS LANDING
 CONT: CRIBB
 TEL: 689-6900
  
 SBC= 1997 STANDARD BUILDING CODE
  
 1) DESIGN CRITERIA SHEET NOT SEALED BY
 THE ARCHETECT OF RECORD, DOCUMENTS FOR
 PUBLIC RECORD SHALL BE SIGNED & SEALED
 61G1-16.003
 2)- CLOSPY DOOR (GARAGE DOOR) REPORT
 INDICATED OR WAS CIRCLED INDICATING THE
 USE OF THE 4050 MODEL DOOR, THIS DOOR
 DOESN'T MEET THE POSITIVE OR NEGATIVE
 PRESSURES, ALSO WILL NOT MEET THE
 REQUIREMENTS OF THE 16'-0" X 8'-0"
 OPENING.
 3)- THE ARCH. SHALL INDICATE AS TO WHICH
 MULLION IS TO BE USED IN CONJUNCTION
 WITH THE DIFFERENT WINDOW CONFIGURATIONS
 HORIZONTAL & VERTICAL MULLIONS.
 4)- PRODUCT APPROVAL FOR CASEMENT WINDOW
 BUT NOT FOR SINGLE HUNG WINDOWS.
 5)- SHEET A-3&4 INDICATE THE USE OF A
 CIRCULAR STAIR TO A LOFT. PROVIDE THE
 MANUFACTURERS SPEC FOR COMPARISON TO
 SBC 1007.8.2.
 6)- SBC 104.2.2 ADDITIONAL INFORMATION
 SHALL BE REQUIRED ON THE LOFT IN THE
 LIBRARY. A CUT SECTION THROUGH WOULD
 GIVE BETTER DETAIL. SBC 503.2.3 MEZANINE
 SBC 1203.2.1 OCCUPIABLE ROOMS MINIMUM
 CEILING HEIGTH OF 7'-6" ARE CONCERNS.
 INDICATE STRUCTURAL DETAILS?
 7)- SBC 104.2.2 MISSING INFORMATION ON
 THE FIRE PLACE &CHIMNEY IN THE LIVING
 ROOM, THE VENTLESS FIREPLACE IN THE
 COVERED PORCH AND THE GRILL.
 8)-SHEET A-8 DISCREPANCY THE TRUSS
 STRAP SCHEDULE INDICATES THE USE OF USP
 FOR TRUSS ANCHORS VS THE DETAILS WHICH
 SPECIFY SEMCO WHICH IS NO LONGER IN
 BUSINESS?WHAT ARE THE NEW CATALOG #?
 9)- SHEET A-8DEAIL A & B INDICATE THE
 USE OF MULTIPLE OR SEVERAL STRAPS IN
 A CONCRETE BEAM OR CMU. USP REQUIRES A
 DERATING WHEN STRAPS ARE PLACED CLOSER
 THAN 8" BECAUSE OF THE CONE PILL OUT
 AFFECT. HOW MUCH DERATING DOES USP
 REQUIRE?
 10)- PLANS ARE TO BE ASSESSED BY PALM
 BEACH COUNTY FOR IMPACT FEES BEFORE
 THE ISSUANCE OF A PERMIT.
 11)- ADDITIONAL FEES DUE!
  
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X 8412

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-07-24 Cont ID  
Sent By btrobaug Date 2002-07-24 Time 07:46 Rev Time 0.00
Received By btrobaug Date 2002-07-23 Time 14:42 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-06-27 Cont ID  
Sent By pkrauss Date 2002-06-21 Time 14:44 Rev Time 0.00
Received By btrobaug Date 2002-06-27 Time 09:48 Sent To R
Notes
2002-06-27 00:00:00UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 NOT ALL NOTES FROM THE FIRST AND SECOND
 REVIEWS HAVE BEEN CORRECTED.PLEASE
 CORRECT THEM AND THE FOLLOWING AND
 RESUBMIT FOR REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 NEED THE RATING NOT A NOTE.
  
 2} CORRECT THE MARKING ON THE SERVICE
 GEAR,"TMB","TLO".
  
 3} LIST THE OCP AND WIRE SIZE FOR PANEL
 "C" ON PANEL"B"SCHEDULE.INCLUDE IN THE
 CALCULATION FOR "B" PANEL.
  
 4} PLEASE NOTE THE OCP FOR THE 5KW HEAT
 STRIP EXCEEDS 150%.
  
 5} SMOKE DETECTORS PER 2-2.1.1.1(BED RMS
 3 & 4).
  
 6} GFI TO BE INSTALLED IN FRONT OF THE
 RESIDENCE PER 210-52(E).
  
 7} THE RERIGERATOR CIRCUIT IN PANEL "A"
 IS SHOWN AS 3KW ON A SINGLE POLE 20AMP
 BREAKER EXCEEDING 80% OF THE BREAKER
 RATING.PLEASE CORRECT.
  
 8} ATTIC ACCESS FOR AHU #2 MUST COMPLY
 WITH 210-70(A)(3) & 210-63.PLEASE
 INDICATE SAME ON PLANS.
  
 9} THE PLAN SHOWS A DISCONNECT NEXT TO
 THE METER AND NOT ON THE RISER,PLEASE
 CLARIFY ON THE PLAN.
  
 10} NOTE THE LIVING ROOM IS MISSING A
 RECEPTACLE PER 210-52(A)(1).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-06-05 Cont ID  
Sent By dpalmer Date 2002-06-05 Time 06:05 Rev Time 0.00
Received By dpalmer Date 2002-06-05 Time 06:05 Sent To M
Notes
2002-06-05 00:00:00***************** UNSAT *************
  
 PLEASE NOTE THAT NO ALL NOTES FORM FIRST
 REVIEW WERE ADDRESSED.
  
 1)NOTE: PLEASE SEE 310-15 FOR SIZING OF
 350MCM FOR SERVICE. A 400A SERVICE IS
 SHOWN.(NOTE#4 FIRST REVIEW)
  
 2)NOTE: PLEASE NOTE THAT PANEL "B" STILL
 DOES NOT SHOW OCP FOR FEEDING PANEL "C"
 IF PANEL "B" HAS FEED THROUGH LUGS, THEN
 WIRE SIZE NEEDS TO INCREASE TO MEET MAIN
 OCP OF 200AMPS. (NOTE #6 FIRST REVIEW)
 LOAD CALCS NOT INCLUDED ON "B" FOR "C"??
 3)NOTE: PLEASE NOTE PLANS STILL MISSING
 OUTLET SPACING TO MEET 210-52/210-52H
 PLEASE ALSO NOTE KITCHEN LAYOUT FOR
 COUNTERSPACE HAS CHANGED. PLEASE NOTE
 MISSING GFI/OUTLET(S) PER210-52-C-1.
 (NOTE# 9 FIRST REVIEW)
  
 4)NOTE: PLEASE NOTE PANEL SCHEDULE SHOWS
 BEDROOM CIRCUITS, BUT NO MENTION OF
 ARC FAULT PROTECTION PER 210-12. CAN BE
 A NOTE ON PLANS.
  
 5)NOTE: PLEASE NOTE SMOKE DETECTORS
 STILL MISSING PER NFPA-72. MISSING IN
 VICINITY OF STAIRS LEADING TO ABOVE FLR.
 2-5.2.1.4 PLEASE ALSO NOTE A SD HAS BEEN
 PLACED IN MASTER BATH. PLEASE NOTE THAT
 THIS IS NOT PERMITTED PER 2-5.2.1.6.
 PLEASE NOTE THERE A FEW SD`S SHOWN THAT
 GO ABOVE AND BEYOND WHAT IS REQ`D.
 PLEASE NOTE, IF SHOWN ON PLANS THEN
 THEY WILL BE REQ`D TO BE INSTALLED OR
 PLANS MAY NEED TO BE REVISED AT A LATER
 DATE. JUST A NOTE.
 (NOTE#2 FROM FIRST REVIEW)
  
 6)NOTE: PLEASE NOTE OCP FOR 5KW HEAT
 STRIP SHOWN AT 50AMPS? PLEASE VERIFY.
 MAX OCP 150%?
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 ONCE AGAIN, IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-08 Cont ID  
Sent By dpalmer Date 2002-03-08 Time 10:27 Rev Time 0.00
Received By btrobaug Date 2002-03-08 Time 10:27 Sent To B
Notes
2002-03-08 00:00:00***************** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 THIS NOTE IS ON THE PLANS AND ARE FROM
 PREVIOUS REVIEW NOTES? PLEASE ACTUALLY
 SUBMIT THE RATINGS.
  
 2) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 MISSING IN MANY LOCATIONS. PLEASE NOTE
 THAT ROOMS WITH BATHS AND/OR CLOSETS ARE
 ADAPTABLE SLEEPING RMS.
  
 3) NOTE: PLEASE SHOW GROUNDING ELECTRODE
 GOING TO BUILDING STEEL AND COLD WATER
 PER 250-50.
 MISSING BLDG/FOOTER STEEL.
  
 4)NOTE: PLEASE NOTE THAT RISER DIAGRAM
 SHOWS 350 MCM BEING INSTALLED. PLEASE
 NOTE THAT PER 310-15 350MCM IS GOOD FOR
 A 350A SERVICE. PLEASE NOTE THAT TWO,
 200A PANELS ARE GOING IN?
  
 5)NOTE: PLEASE NOTE THAT THERE IS AN
 EQUIPMENT GROUNDING CONDUCTOR SHOWN
 BETWEEN GUTTER AND MAIN DISC #1. PLEASE
 NOTE THAT THIS IS PARALLELING THE
 NEUTRAL? PLEASE REMOVE.
  
 6)NOTE: PLEASE NOTE THAT PANEL "B", SHOW
 -S FEED TO PANEL "C" BUT DOES NOT SHOW
 OCP.? FEEDERS ARE NOTED ON RISER DIAGRAM
 .
  
 7)NOTE: PLEASE NOTE THAT PLAN SHOW FOUR
 A/C COND UNITS AND ONLY 3 SETSARE
 SHOWN ON PANEL SCHEDULES AND LOAD CALCS.
  
 8)NOTE: PLEASE SHOW ROOM DESIGNATION
 ON PLANS.
  
 9) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
 MISSING IN ENTIRE LIVING ROOM?
 AND A FEW OTHERS.
  
 10)PLEASE NOTE MISSING OUTLET(S) REQ`D
 BY 210-52E OF THE NEC.
 MISSING FRONT.
  
 11)NOTE: PLEASE NOTE MISSING REC FOR
 AHU #1 PER MECH CODE.309.2
  
 12)NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
 BATHS ARE NOW SHOWN AS 15A AND #14??
  
 13)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 CIRCUITS ON PLANS PER 210-12. CODE WENT
 INTO EFFECT 1/1/2002.
  
 14)NOTE: PLEASE NOTE 60A OCP SHOWN FOR
 5KW HEAT FOR A/C SYSTEM ON PANEL "C".
 PLEASE CORRECT.
  
 15)NOTE: PLEASE CLARIFY 3KW FOR A SINGLE
 POLE 20A BRKR FOR FRIG CIRCUIT.
 PLEASE NOTE 80% MAX LOAD FOR BRANCH
 CIRCUIT AND RATING OF BRKR.PER 384
  
 16)NOTE: PLEASE SHOW OUTLETS ABOVE BATH
 AS GFI/GFI PROTECTED. 210-8
  
 17)NOTE: PLEASE NOTE REC AND LT REQ`D
 FOR AHU`S #2,3, IN ATTIC.
 ATTIC ACCESS.PER 210-63/210-70 AND 309.2
 NEC AND MECH CODE.
  
 18)NOTE: PLEASE NOTE THAT PLANS ONLY
 SHOWS ONE MAIN NEXT TO METER. PLEASE
 SHOW BOTH MAINS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2003-10-01 Cont ID  
Sent By csiegber Date 2003-10-01 Time 15:29 Rev Time 0.00
Received By csiegber Date 2003-10-01 Time 15:29 Sent To P
Notes
2003-10-01 00:00:00TO KS BOX

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2003-01-09 Cont ID  
Sent By pkrauss Date 2003-01-09 Time 12:56 Rev Time 0.28
Received By pkrauss Date 2003-01-09 Time 12:30 Sent To  
Notes
2003-01-09 00:00:00MECH REV PERMIT 02021493

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-07-24 Cont ID  
Sent By pkrauss Date 2002-07-24 Time 10:17 Rev Time 0.35
Received By pkrauss Date 2002-07-24 Time 10:17 Sent To B
Notes
2002-07-24 00:00:00MECHANICAL PERMIT 02021493
  
 AIR MAKE-UP FOR THE COMBUSTION AIR ON
 PLAN SHEET A-3.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2002-06-21 Cont ID  
Sent By btrobaug Date 2002-07-24 Time 07:46 Rev Time 0.45
Received By pkrauss Date 2002-06-20 Time 11:22 Sent To E
Notes
2002-06-21 00:00:00DENIED:MECHANICAL PERMIT 02021493
  
 ITEMS#1 & 3 FROM REVIEW DATED 6/5/02
 NOT ADDRESSED.
  
 1. AXILIARY DRAIN SHALL TERMINATE AT A
 CONSPICUOUS POINT.PLEASE CLARIFY
 HOW THE AXUILIARY DRAIN LINE RUN WITH
 & TERMINATING AT THE SAME POINT AS
 THE PRIMARY DRAIN IS A "CONSPICUOUS
 POINT".
  
 3. SHOW COMPLIANCE WITH 1997 SMC 704,
 FOR COMBUSTION AIR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2002-06-06 Cont ID  
Sent By dpalmer Date 2002-06-05 Time 06:35 Rev Time 0.40
Received By pkrauss Date 2002-06-06 Time 07:01 Sent To  
Notes
2002-06-06 00:00:00 
  
 1.AS PER 1997 SMC AUXILIARY DRAIN
 SHALL TERMINATE AT A CONSPICUOUS
 POINT TO SERVICE AS AN ALARM THAT
 THE PRIMARY DRAIN IS RESTRICTED.
 PLEASE CLARIFY HOW THE AUXILARY
 DRAIN LINE RUN WITH & TERMINATING
 AT THE SAME POINT AS THE PRIMARY
 DRAIN IS A "CONSPICUOUS POINT".
  
 2.PROVIDE MANUFACTURER INSTALLATION
 INSTRUCTIONS FOR THE GAS FIREPLACE,
 GRILL W/HOOD & VENTLESS F.P. SHOWN
 ON PLAN SHEET A-3.
  
 3.PROVIDE INFORMATION ON VENT FOR THE
 GAS DRYER & SHOW COMPLIANCE WITH
 CHAPTER 7 OF THE 1997 SMC.
  
 4.AHU'S SHALL HAVE ADEQUATE ACCESS FOR
 MAINTENANCE & SERVICE AS PER 1997
 SMC 304.2 & 304.4.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-03-06 Cont ID  
Sent By hmoser Date 2002-03-06 Time 19:36 Rev Time 0.33
Received By hmoser Date 2002-03-06 Time 19:36 Sent To  
Notes
2002-03-06 00:00:00PLAN DENIED
 ENERGY CALCS AND PLANS DO NOT MATCH
 ENERGY CALCS SHOW ONE A/C UNIOT
 PLANS SHOW THREE A/C UNIOTS
 PLAN REVIEW BY HAROLD MOSER
 [561]659-8096 EXT.8390

Review Stop P PLUMBING
Rev No 2 Status P Date 2003-10-11 Cont ID  
Sent By kstevens Date 2003-10-11 Time 14:08 Rev Time 0.50
Received By kstevens Date 2003-10-11 Time 14:08 Sent To  
Notes
2003-10-11 00:00:00REVISION OK - SANT. RISER DIAGRAM

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-03-02 Cont ID  
Sent By csiegber Date 2003-10-01 Time 15:29 Rev Time 0.33
Received By jleech Date 2002-03-02 Time 08:33 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-02-28 Cont ID  
Sent By sgraham Date 2002-02-28 Time 09:46 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***