| Plan Review Stops For Permit 02021424 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2003-02-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-07 |
Time |
11:10 |
Rev Time |
0.50 |
| Received By |
dpalmer |
Date |
2003-02-07 |
Time |
11:10 |
Sent To |
P |
|
| Notes |
| 2003-02-07 00:00:00 | 210-52D. NOTED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2002-06-25 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-01-27 |
Time |
12:48 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-06-25 |
Time |
16:00 |
Sent To |
R |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-05-13 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-19 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-05-13 |
Time |
14:26 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-03-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-12 |
Time |
05:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-03-11 |
Time |
16:47 |
Sent To |
B |
|
| Notes |
| 2002-03-12 00:00:00 | ***************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2) NOTE: PLEASE LIST THE REQ`D BATH(S) | | | CIRCUIT(S) PER 210-11-C-3. | | | MUST BE 20A AND #12AWG. | | | | | | 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT | | | PROTECTED CIRCUITS ON PANEL SCHEDULE PER | | | 210-12 | | | | | | 4) NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | GOING TO BUILDING STEEL AND COLD WATER | | | PER 250-50. | | | MISSING FOOTER STEEL. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2003-01-27 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2003-01-27 |
Time |
12:48 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2003-01-24 |
Time |
12:48 |
Sent To |
E |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
N |
Date |
2003-02-10 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2003-02-10 |
Time |
15:09 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2003-02-10 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2003-02-10 00:00:00 | NO MECHANICAL PLANS SUBMITTED FOR | | | RE-STAMP |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2003-02-07 |
|
|
Cont ID |
|
| Sent By |
hmoser |
Date |
2003-02-07 |
Time |
09:08 |
Rev Time |
0.50 |
| Received By |
hmoser |
Date |
2003-02-07 |
Time |
09:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2002-06-27 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-27 |
Time |
08:41 |
Rev Time |
0.40 |
| Received By |
pkrauss |
Date |
2002-06-27 |
Time |
08:40 |
Sent To |
R |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2002-06-19 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-19 |
Time |
09:56 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-06-19 |
Time |
09:56 |
Sent To |
E |
|
| Notes |
| 2002-06-19 00:00:00 | | | | ONLY ONE SET OF ENERGY CALCS SUBMITTED | | | & NO MANUAL J CALCULATIONS SUBMITTED. | | | | | | AS PER 1997 SMC 304.4.1, ACCESS OPENING | | | FOR EQUIPMENT IN THE ATTIC SHALL BE NO | | | LESS THAN 22" X 36" CONTINUOUS FROM THE | | | OPENING TO ITS CONTROLS.AS PER COUNTY | | | WIDE AMMENDMENTS 304.4.2 EQUIPMENT IN | | | THE ATTIC MUST ALSO HAVE AN ACCESSIBLE | | | DISCONNECT SWITCH & A 110-120 VOLT A/C | | | GROUNDING TYPE CONVENIENCE OUTLET & A | | | LIGHT ON THE SERVICE SIDE OF THE EQUIP. | | | CONTROLED BY A SWITCH AT THE ACCESS | | | OPENING. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2002-05-28 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-20 |
Time |
15:26 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-05-20 |
Time |
15:25 |
Sent To |
R |
|
| Notes |
| 2002-05-20 00:00:00 | CODE REVIEWED UNDER THE 1997 SMC | | | | | | | | | NO PLANS SUBMITTED FOR THE FIRST FLOOR. | | | ENERGY CALCS INDICATE A CENTRAL UNIT | | | WITH CAPACITY OF 116.0, PLANS INDICATE | | | (2) 2 1/2 TON UNITS. | | | | | | PLEASE CLARIFY A/C FOR THE FIRST FLOOR. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-03-07 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-05-18 |
Time |
08:33 |
Rev Time |
0.50 |
| Received By |
hmoser |
Date |
2002-03-07 |
Time |
18:24 |
Sent To |
|
|
| Notes |
| 2002-03-07 00:00:00 | NO PLANS,ONLEY ONE SET OF ENERGY CALCS, | | | NO MANUAL J | | | H.MOSER [561]659-8096 EXT 8390 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2003-02-21 |
Time |
09:40 |
Rev Time |
0.25 |
| Received By |
kstevens |
Date |
2003-02-07 |
Time |
13:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-07-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2003-02-07 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-07-23 |
Time |
13:01 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-05-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-05-18 |
Time |
08:33 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-05-18 |
Time |
08:33 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-03-02 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-05-13 |
Time |
14:53 |
Rev Time |
0.50 |
| Received By |
jleech |
Date |
2002-03-02 |
Time |
10:47 |
Sent To |
|
|
| Notes |
| 2002-03-02 00:00:00 | DENIED; | | | RISER DIAGRAM; | | | 1.ONLY 2 W/C PERMITED ON 3" HORIZONTAL | | | BRANCH 94 SPC TABLE 714.1 NOTE 3 (4" | | | REQUIRED DOWN STREAM OF RISER TO BATH | | | 2 AND 3. | | | 2.TUB IN BATH 3 UNVENTED. | | | 3.BATH 4 2" TRAP AND DRAIN REQUIRED PER | | | TABLE 713.1 | | | 4.MASTER BATH BIDET NOT VENTED,2" REQ. | | | FOR SHOWER. | | | PLUMBING NOTES: PAGE 1 | | | NOTE 5 SHOCK ARRESTOR SHALL BE INSTALLED | | | PER MANUFACTORS RECOMMENDATIONS AND SPC | | | SEC 607.8.2. | | | NOTE 8 MAXIMUM FLOW FOR SHOWER HEADS IS | | | 2.5 GAL PER MIN TABLE 406. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 659-8096 EXT. 8369 |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
4 |
Status |
F |
Date |
2003-02-21 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2003-02-20 |
Time |
17:33 |
Rev Time |
1.00 |
| Received By |
jgomez |
Date |
2003-02-20 |
Time |
17:33 |
Sent To |
|
|
| Notes |
| 2003-02-20 00:00:00 | BUILDING REVIEW COMMENTS: | | | 1-MISSING SHEETS #2, #3 AND #4 TO HAVE | | | A COMPLETE SET OF DRAWINGS. | | | 2-PROVIDE ALL INFORMATION THAT WAS | | | REQUESTED ON PROVISO DATED 6-28-02, | | | WHICH WAS A CONDITION AGREED BY THE | | | OWNER IN ORDER TO ISSUE THE BUILDING | | | PERMIT AND START CONSTRUCTION. | | | SEE ATTACHED COPY. | | | 3-PLANS NEED TO BE RE-STAMPED BY THE | | | HISTORICAL PEOPLE PRIOR TO SUBMITTAL | | | TO THIS OFFICE. | | | 4-PROVIDE INFORMATION FOR PLUMBING | | | RE-STAMPING AS WELL. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
3 |
Status |
P |
Date |
2002-07-02 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2002-06-28 |
Time |
18:29 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2002-06-28 |
Time |
18:29 |
Sent To |
|
|
| Notes |
| 2002-06-28 00:00:00 | APPROVED WITH PROVISO: | | | 1-FLOOD ZONE A5. NEED TO PROVIDE THE | | | ELEVATION CERTIFICATE. | | | 2-PROVIDE ATTIC ACCESS @ MASTER BATHROOM | | | ROOF. SEC. 2309.6 SBC 1997. | | | 3-BEFORE INSTALLATION OR CONSTRUCTION | | | PROVIDE PRODUCT APPROVAL FOR: | | | A)ENTRY DOOR. SEE PLANS FOR SIZE & SHAPE | | | B)GARAGE SIDE DOOR. SEE SIZE ON PLANS. | | | C)FRENCH DOORS AS SHOWN ON PLANS. | | | D)CASEMENT WINDOWS. | | | E)WINDOW MULLIONS AS SPECIFIED ON | | | ARCHITECTURAL PLANS. | | | F)FIXED WINDOWS AS SHOWN ON PLANS. | | | G)ARCHED WINDOWS AS SHOWN ON PLANS. | | | H)FIREPLACE UL LISTING & SPECIFICATIONS. | | | I)EXTERIOR DOOR AT 3RD FLOOR BALCONY. | | | SEE PLANS FOR SIZE AND SHAPE. | | | | | | 4-PROVIDE COMPLETE INFORMATION FOR STORM | | | SHUTTERS UNDER A SEPARATE PERMIT. | | | 5-SPECIFY SIZE OF ROOF SCUPPERS. SECTION | | | 1517.6.4 THRU 1517.6.4.3 SBC 1997. | | | 6-SPECIFY HOW ARE SOIL AND FOOTINGS | | | GOING TO BE PROTECTED FROM WATER | | | FALLING FROM ROOF VALLEYS & SCUPPERS. | | | SEC. 1804.1.6 SBC 1997. | | | 7-SEE COMMENTS ATTACHED TO TRUSS PACKAGE |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2002-05-30 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-06-27 |
Time |
09:47 |
Rev Time |
4.00 |
| Received By |
jgomez |
Date |
2002-05-30 |
Time |
17:11 |
Sent To |
|
|
| Notes |
| 2002-05-30 00:00:00 | SECOND CHECKLIST: | | | 1-AFTER CORRECTING ORIGINAL DRAWINGS, | | | PLEASE PAY IMPACT FEES TO PALM BEACH | | | COUNTY. BRING BACK STAMPED DRAWINGS | | | AND COPY OF PAID RECEIPT. | | | 2-NEED RECORDED NOTICE OF COMMENCEMENT. | | | 3-CLARIFY DISCREPANCY WITH THE FINISH | | | FLOOR ELEVATION. ARCHITECT'S SITE PLAN | | | NOTES SAYS 10.5" ABOVE SEA LEVEL. | | | SURVEY SAYS 7.5', BUT THE LIVING ROOM | | | WILL BE AT 7' ACCORDING TO ARCHITECT'S | | | PLANS. (NEED 7.5'MIN. FIN. FL. ELEV. | | | AT FLOOD ZONE A5). | | | ON THE OTHER HAND NEED TO CONSIDER | | | SOUTH NEIGHBOR FOR DRAINAGE SINCE THE | | | HOUSE HAS 6.5' FIN. FL. ELEV. | | | 4-ARCHITECT CHANGED PLANS TO FBC 2001. | | | SEE COMMENTS ON PLANS & REVISE/UPDATE | | | THEM AS REQUIRED. NOTE: COMMENTS WERE | | | NOT REVISED FROM PREVIOUS CHECKLIST. | | | **PLEASE, PUT TOGETHER TWO NEW SETS AND | | | RETURN ALL THE REVIEWED DRAWINGS TO | | | EXPEDITE REVIEW PROCESS. | | | 5-OWES $662.35 FOR UPDATED VALUATION AND | | | RADON FEES.PLEASE PAY ATTACHED RECEIPT | | | 6-PROVIDE ATTIC ACCESS AT MASTER BATHRM | | | WING. SEC. 2309.6 FBC 2001 | | | 7-CLEARLY SPECIFY ON PLANS AREAS TO HAVE | | | SAFETY GLASS. IT'S NOT CLEAR IF ALL | | | GLASS AREAS WILL BE MISSILE IMPACT | | | GLAZING OR NOT. SEE SECTION 2405.1 AND | | | SEC 2405.2 FBC 2001. | | | 8-PROVIDE PRODUCT APPROVAL FOR: | | | A)ENTRY DOOR. SEE SIZE, SHAPE AND DESIGN | | | PRESSURES SHOWN ON PLANS. | | | B)GARAGE SWING DOOR AS SHOWN ON PLANS. | | | C)FRENCH DOORS AS SHOWN ON PLANS. | | | D)CASEMENT WINDOWS (MISSING DRAWINGS). | | | E)WINDOW MULLIONS (FOR IMPACT ASSEMBLIES | | | IF USING IMPACT WINDOWS) | | | F)FIXED WINDOWS AS SHOWN ON PLANS. | | | G)ARCHED WINDOWS AS SHOWN ON PLANS. | | | H)FIREPLACE UL LISTING & SPECIFICATIONS. | | | I)EXTERIOR DOOR AT 3RD FLOOR BALCONY. | | | SEE SIZE AND SHAPE ON DRAWINGS. | | | 9-REVISE A/C AREA ON ENERGY CALCULATIONS | | | TO MATCH A/C AREA ON ARCHITECT'S PLANS | | | NOTE: OWNERAGENT TO SIGN AND DATE | | | BOTTOM OF FORM. | | | 10-PROVIDE COMPLETE INFORMATION FOR | | | STORM SHUTTERS: KEY PLAN AND COMPLETE | | | INSTALLATION SCHEDULE. | | | 11-SPECIFY DRAINAGE & EMERGENCY SCUPPERS | | | @ 3RD FL BALCONY. SEC. 1503.4 THRU | | | 1503.4.4 FBC 2001. | | | 12-SPECIFY ON PLANS HOW SOIL EROSION IS | | | TO BE PREVENTED FROM WATER IMPACT FROM | | | ROOF VALLEYS, SCUPPERS. ETC. AS REQ'D | | | BY SECTION 1804.1.6 FBC 2001. | | | 13-AFTER ALL CORRECTIONS ARE DONE TO ALL | | | ORIGINAL DRAWINGS, PLEASE TAKE THEM TO | | | THE HISTORICAL DISTRICT PLAN REVIEWER | | | FOR APPROVAL PRIOR TO SUBMITTING THEM | | | TO THE BUILDING DEPARTMENT. |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2002-04-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-28 |
Time |
07:45 |
Rev Time |
5.00 |
| Received By |
jgomez |
Date |
2002-04-04 |
Time |
18:19 |
Sent To |
|
|
| Notes |
| 2002-04-05 00:00:00 | CHECKLIST: | | | 1-AFTER CORRECTING ORIGINAL DRAWINGS, | | | PLEASE PAY IMPACT FEES TO PALM BEACH | | | COUNTY. BRING BACK STAMPED DRAWINGS | | | AND PAID RECEIPT. | | | 2-NEED RECORDED NOTICE OF COMMENCEMENT. | | | 3-CONTRACTOR TO UPDATE INSURANCES. | | | 4-UPDATE/REVISE DRAWINGS. SEE COMMENTS | | | ON PLANS. PLEASE, BRING BACK REVIEWED | | | SET TO EXPEDITE REVIEW PROCESS. | | | 5-OWES $662.35 FOR UPDATED VALUATION AND | | | RADON FEES. | | | 6-PROVIDE EGRESS WINDOW THAT COMPLIES | | | WITH SEC. 1005.4 SBC 1997 AT LIBRARY. | | | OR, WRITE VISIBLE NOTE UNDER LIBRARY | | | STATING THAT ROOM NOT TO BE USED FOR | | | SLEEPING PURPOSES (AS PER BUILDING | | | OFFICIAL INTERPRETATION). | | | 7-PROVIDE ATTIC ACCESS AT ENTRY CUPOLA, | | | AND MASTER BEDROOM WING. SEE SECTION | | | 2309.6 SBC 1997. | | | 8-CLEARLY SPECIFY ON PLANS AREAS TO HAVE | | | SAFETY GLASS. SEE PLANS AND SECTION | | | 2405.2 SBC 1997. | | | 9-PROVIDE PRODUCT APPROVAL FOR: | | | A)ENTRY DOOR. SEE SIZE & SHAPE ON PLANS. | | | B)GARAGE SWING DOOR. SEE SIZE AND TYPE. | | | C)FRENCH DOORS. SEE SIZES ON PLANS. | | | D)CASEMENT WINDOWS (MISSING DRAWINGS) | | | E)WINDOW MULLIONS(IMPACT IF USING | | | IMPACT WINDOWS). | | | F)FIXED WINDOWS. SEE SIZES ON PLANS. | | | G)ARCHED WINDOWS. SEE SIZES ON PLANS. | | | H)FIREPLACE UL LISTING & COMPLETE SPECS. | | | I)EXT. DOOR @ 3RD FL. BALCONY. SEE SIZE | | | AND SHAPE ON PLANS. | | | 10-SPECIFY HEIGHT OF CHIMNEY TO VERIFY | | | COMPLIANCE WITH SEC. 2804 SBC 1997. | | | 11-PROVIDE COMPLETE SPECIFICATIONS FOR | | | CEILING INSTALLATION AT PORCHES. | | | SPECIFY ALL FASTENERS AS REQUIRED. SEE | | | ASTM C-1063. (SEC. 2505.2 SBC 1997) | | | 12-INFORMATION ON DESIGN CERTIFICATION | | | BUILDING CODE COMPLIANCE FORM IS | | | INCORRECT. SEE TABLE 1606.2A SBC 1997. | | | NOTE: INFORMATION IN THIS FORM SHALL BE | | | INCLUDED ON PLANS. NO SEPARATE FORM. | | | 13-PROVIDE TWO COPIES OF ENERGY CALCS. | | | 14-PROVIDE CURRENT SOIL TEST REPORT. | | | SEE COMMENTS ON REPORT SUBMITTED. | | | 15-PROVIDE COMPLETE INFORMATION FOR | | | SHUTTERS INCLUDING KEY PLAN & COMPLETE | | | INSTALLATION SCHEDULE (SEE SAMPLE). | | | ALSO, ON STORM PANEL DWGS INDICATE | | | SPECIFIC MOUNTING CODITIONS AND ANCHOR | | | TYPE AND SPACING TO BE USED ACCORDING | | | TO MEAN ROOF HEIGHT, DESIGN PRESSURES, | | | PANEL SPAN, EDGE DISTANCE, CONNECTION | | | TYPE AND STRUCTURE TO BE ATTACHED TO. | | | 16-SPECIFY DRAINAGE AND SCUPPERS FOR | | | BALCONY AT THIRD FLOOR. SEC 1503.1.2.3 | | | AND 1517.6.4 SBC 1997. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-02-28 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-02-28 |
Time |
12:03 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|