Plan Review Details - Permit 02021370
Plan Review Stops For Permit 02021370
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-05-01 Cont ID  
Sent By btrobaug Date 2002-05-01 Time 11:47 Rev Time 0.00
Received By btrobaug Date 2002-05-01 Time 10:19 Sent To R
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-11 Cont ID  
Sent By dpalmer Date 2002-03-11 Time 16:06 Rev Time 0.00
Received By dpalmer Date 2002-03-11 Time 15:59 Sent To B
Notes
2002-03-11 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE MEANS OF DISCONNECT
 FOR DETACHED STRUCTURE.
 225-31
  
 2)NOTE: PLEASE NOTE MEANS OF GROUNDING
 AT DETACHED BLDG. PER 250-32.
  
 3)NOTE: PLEASE NOTE MISSING OUTLET PER
 210-52 UPSTAIRS WALL. OVER 2'.
  
 4)NOTE: PLEASE NOTE MISSING OUTLET FOR
 KITCHEN PENINSULAR. 210-52C-3.
  
 5)NOTE: PLEASE NOTE MISSING BLDG/FOOTER
 STEEL PER 250-50. GROUNDING ELECTRODE
 SYSTEM.
  
 6)NOTE: PLEASE NOTE CLEARENCE FOR A/C
 COND UNIT DISCONNECTS PER 110-26.
  
 7)NOTE: PLEASE NOTETHAT RISER DIAGRAM
 SHOWS MAIN DISCONNECT NEXT TO METER
 AND FLOOR LAYOUT NEEDS TO SHOW MAIN DISC
 NEXT TO METER.
  
 8)NOTE: PLEASE NOTE CLEARENCE FOR CLOSET
 LT UNDER STAIRS(TYPE OF FIXTURE).
  
 9)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTION PER 210-12. ON PANEL SCHEDULE
  
 10)NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-03-06 Cont ID  
Sent By hmoser Date 2002-03-06 Time 20:04 Rev Time 0.50
Received By hmoser Date 2002-03-06 Time 20:04 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-03-02 Cont ID  
Sent By jleech Date 2002-03-02 Time 09:05 Rev Time 0.33
Received By jleech Date 2002-03-02 Time 09:05 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status P Date 2002-05-11 Cont ID  
Sent By jgomez Date 2002-05-11 Time 14:09 Rev Time 3.00
Received By jgomez Date 2002-05-11 Time 14:09 Sent To  
Notes
2002-05-11 00:00:00APPROVED WITH PROVISO:
 1-SUBMIT PRODUCT APPROVAL FOR REVIEW
 PRIOR TO INSTALLATION FOR:
 A)OUTSWING FRENCH DOORS WITH SIDELITES
 AS SHOWN ON PLANS.
 B)INSWING FRENCH DOORS AS SHOWN ON PLANS
 C)UL LISTING AND SPECS FOR FIREPLACE.
 D)GARAGE DOOR THAT MEETS THE DESIGN
 PRESSURES CALCULATED BY THE ARCHITECT.
 SEE PLANS.
 E)IMPACT WINDOW MULLIONS.
 F)ARCHED WINDOWS AS SHOWN ON PLANS.
 G)FIXED WINDOWS AS SHOWN ON PLANS.
  
 NOTE:
 PROVIDE ALL THESE PRODUCT APPROVALS
 PRIOR TO INSTALLATION TO AVOID CONFLICTS
 OR DELAYS.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-03-29 Cont ID  
Sent By btrobaug Date 2002-05-01 Time 11:47 Rev Time 4.00
Received By jgomez Date 2002-03-29 Time 10:34 Sent To  
Notes
2002-03-29 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING STAMPED DWGS AND PAID RECEIPT.
 3-SPECIFY RISER HEIGHT AT ENTRY STEPS.
 SEE SEC. 1007.3 SBC 1997.
 4-SPECIFY ON PLANS AREAS TO HAVE SAFETY
 GLASS. SEC. 2405.2 SBC/97. SEE PLANS.
 5-PROVIDE ATTIC ACCESS AT ENTRY ROOF.
 SEC. 2309.6 SBC 1997.
 6-TWO STORY WALL SECTION. PROVIDE SPECS
 FOR FIRE CUT AT FLOOR TRUSSES. SEE
 SEC. 2305.4 SBC 1997.
 7-FLAT ROOF TO HAVE 1/4"/FT MIN. SLOPE.
 SEC. 1503.1.2.3 SBC 1997.
 8-PROVIDE SCUPPERS AT FLAT ROOF. SEE
 SEC. 1517.6.4.3 SBC 1997.
 9-SPECIFY DRAFSTOPPING MATERIAL AND
 LOCATION AT SECOND FLOOR FRAMING PLAN.
 SEC. 2305.2.2 SBC 1997.
 10-PROVIDE COMPLETE SECTION/DETAIL THRU
 CHIMNEY. SPECIFY ALL FASTENERS AND
 TOP PLATE HEIGHT. SECTION 104.2.2 OF
 CITY AMENDMENTS TO SBC 1997.
 11-PROVIDE COMPLETE FRAMING DETAILS AND
 SPECS FOR CANVAS CANOPY. SECTION
 104.2.2 CITY AMENDMENTS TO SBC 1997.
 12-SPECIFY CEILING INSTALLATION AT ENTRY
 PORCH INCLUDING FASTENERS TO BE USED.
 SEE ASTM C1063.
 SEC. 2504.2 SBC 1997.
 13-PROVIDE SMOKE DETECTOR @ 1ST FLOOR BY
 THE STAIRWAY. SEC. 905.2.2 SBC 1997.
 14-PROVIDE COMPLETE WALL SECTION AT 2ND
 FLOOR WALL SUPPORTED ON TRUSS GIRDER @
 WEST WALL OF BEDROOM #3 AND @ SOUTH
 WALL OF BEDROOM #2.SPECIFY ALL
 FASTENERS TOP AND BOTTOM.
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 15-PROVIDE COMPLETE SECTION/DETAIL AND
 SPECS AT BALCONY GUARDRAI AND INTERIOR
 GUARDRAIL AND RAILINGS THAT COMPLY
 WITH SEC. 1608.2 SBC 1997.
 16-PROVIDE SBCCI OR DADE COUNTY (BROWARD
 COUNTY ARE NOT ACCEPTED) PRODUCT
 APPROVAL FOR:
 A)OUTSWING FRENCH DOOR WITH SIDELITES.
 B)INSWING FRENCH DOORS. SEE PLANS.
 C)UL LISTING AND SPECS.
 D)INSWING ENTRY DOOR. (SEE MASTER BEDRM)
 E)GARAGE DOOR THAT MEETS THE DESIGN
 PRESSURES CALCULATED BY THE ARCHITECT.
 F)IMPACT WINDOW MULLIONS.
 G)ARCHED WINDOWS. SEE PLANS.
 H)FIXED WINDOWS. SEE PLANS.
 17-DESIGN CERTIFICATION FOR BUILDING
 CODE COMPLIANCE FORM IS INCORRECT.
 A)REVISE MEAN ROOF HEIGHT, VELOCITY
 PRESSURE.
 B)ARCHITET TO SIGN, SEAL AND DATE FORM
 AS REQUIRED BY CHAPTER 481 FL. STATUTE
 18-PROVIDE COMPLETE FRAMING DETAILS AND
 SPECS FOR CANOPY AT GARAGE SWING DOOR.
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 19-PROVIDE COMPLETE SPECS FOR PARAPET
 WALL. HOW IS IT ATTACHED TO CONCRETE
 TIE BEAM. STEEL BARS?
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 20-TRUSS DRAWINGS:
 A)PROVIDE SIGNED, SEALED AND DATED
 ENGINEERED DRAWINGS.
 B)TRUSS ENGINEER TO SIGN, SEAL AND DATE
 TRUSS LAYOUT ALSO. CH. 471 FL. STATUTE
 C)ARCHITECT TO REVIEW ALL TRUSS DRAWINGS
 PRIOR TO SUBMITTAL. USE REVIEW STAMP.
 21-SEE PLANS FOR ADDITIONAL COMMENTS.
 PLEASE RETURN REVIEWED SET AFTER
 CORRECTIONS ARE DONE TO THE ORIGINAL
 DRAWINGS IN ORDER TO EXPEDITE THE
 REVIEW PROCESS.
 22-OWES $379.35 FOR UPDATED VALUE AND
 RADON FEES.