Plan Review Details - Permit 02021340
Plan Review Stops For Permit 02021340
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2002-10-04 Cont ID  
Sent By rmcdouga Date 2002-10-04 Time 11:39 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-06-05 Cont ID  
Sent By btrobaug Date 2002-10-02 Time 17:02 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-06-05 00:00:00BUILDING DENIED
  
 1) THE ENERGY CALC. FORM THAT WAS
 SUBMITTED IS FOR ADDITIONS OF 600 SQ.FT.
 OR LESS. PLEASE SUBMIT (2) COPIES OF THE
 PROPER FORM. SEE ATTACHED.
  
 2) PLEASE ADDRESS THE LETTER CONCERNING
 THE STORAGE TRAILER TO THE BUILDING
 OFFICIAL. THE LETTER IS REQUIRED TO BE
 NOTARIZED. THE STORAGE CONTAINER MUST BE
 PERMITTED OR REMOVED FROM THE PROPERTY.
  
 3) THE PRODUCT APPROVALS FOR THE SINGLE
 HUNG WINDOWS IS REQUIRED TO BE SBCCI OR
 METRO-DADE. IF NOT, THEN SITE SPECIFIC
 ENGINEERING (PRODUCT APPROVAL) IS
 REQUIRED. SITE SPECIFIC ENGINEERING
 REQUIRES THE WET SIGNATURE, DATE AND
 EMBOSSED SEAL OF THE ENGINEER THAT IS
 CERTIFYING THE PRODUCT AND OF AN
 ENGINEER OR ARCHITECT APPROVING THE
 INSTALLATION IN THE STRUCTURE. SEE THE
 ATTACHED FORM.
  
 4) EASEMENT RELEASES ARE REQUIRED FROM
 WPB WATER UTILITIES DEPT., TELEPHONE
 AND CABLE COMPANIES. SEE ATTACHED.
  
 5) THE PERSON RESPONSIBLE FOR THE DESIGN
 OF THE STRUCTURE IS REQUIRED TO SIGN THE
 PLANS. CITY AMENDMENTS 104.2.1
  
 6) PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE FOR STORM PANELS. INDICATE THE
 FASTENER TYPE THAT WILL BE USED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-03-25 Cont ID  
Sent By btrobaug Date 2002-06-04 Time 14:21 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-03-25 00:00:00*************BUILDING UNSAT*************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) INDICATE THE SIZE AND LOCATION OF THE
 REQUIRED EMERGENCY ESCAPE AND RESCUE
 OPENING IN THE EXISTING REAR BEDROOM.
 97 SBC 1005.4
  
 4) THE WINDOW IN THE NEW MASTER BEDROOM
 MUST COMPLY WITH EMERGENCY EGRESS
 REQUIREMENTS OF 97 SBC 1005.4. PROVIDE
 THE WIDTH AND HEIGHT DIMENSIONS OR THE
 CALL SIZE OF THE WINDOW.
  
 5) PROVIDE DETAILS INDICATING EXTERIOR
 WINDOW AND DOOR BUCK FASTENING.
  
 6) THE ROOF OVERHANG AT THE REAR OF THE
 STRUCTURE ENCROACHES INTO THE 12'-0"
 EASEMENT. PROVIDE AN EASEMENT RELEASE OR
 DOCUMENTATION THAT THE OVERHANG
 EXTENDING INTO THE EASEMENT IS ALLOWED.
  
 7) THE METAL TRAILER SHOWN ON THE SURVEY
 IS A CODE VIOLATION AND MUST BE
 CORRECTED BEFORE THE PERMIT CAN BE
 ISSUED.
  
 8)INDICATE THE SPACING OF THE REINFORCED
 FILLED CELLS ON THE FOUNDATION PLAN.
  
 9)PROVIDE A DETAIL OF THE TWO INTERIOR
 BEARING WALLS. INDICATE THE CONSTRUCTION
 AND INDICATE THE CONNECTORS USED TO
 TRANSFER LOADS FROM ROOF TO FOUNDATION.
  
 10) THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN OF THE
 ADDITION IS REQUIRED ON EACH SHEET OF
 THE PLANS. CITY AMENDMENTS 104.2.1
  
 11) THE PLANS INDICATE R-30 INSULATION
 IN THE CEILING AND THE ENERGY FORM LISTS
 R-19. PLEASE CORRECT.
  
 12) SHEET 6 LISTS SIMPSON ETA20 TRUSS
 ANCHORS, WHICH ARE NOT LISTED IN THE
 LATEST SIMPSON CATALOG. PLEASE REFER TO
 THE CATALOG AND SPECIFY THE PROPER META/
 HETA,ETC. CONNECTOR.
  
 13) NB2X12-24 BRIDGING IS REQUIRED FOR
 JOISTS SPACED 24" ON CENTER. PLEASE
 CORRECT.
  
 14) THE PROPER CONNECTORS FOR TRUSS TO
 EXISTING MASONRY IS MTSM 20 WITH (4) 1/4
 X2-1/4" TITEN SCREWS INTO MASONRY AND
 (10) 10D NAILS INTO TRUSS. NOT THE LTS
 THAT IS SPECIFIED. PLEASE CORRECT.
  
 15) INDICATE HOW THE WOOD INTERIOR
 BEARING WALL IS CONNECTED TO THE NEW AND
 EXISTING MASONRY WALLS.
  
 16) INDICATE HOW THE NEW FOOTER AND TIE
 BEAM WILL BE CONNECTED TO THE EXISTING.
 (DOWELS AND EPOXY ?)
  
 17) PROVIDE SOIL BEARING TEST PER CITY
 OF W.P.B. AMENDMENTS TO THE 97 SBC SECT.
 1804.2.2.
  
 18)PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS. MISSILE
 IMPACT PROTECTION IS REQUIRED.
  
 19)PROVIDE TWO COPIES OF ALL SUBMITTALS.
 PROVIDE AN ADDITIONAL COPY OF THE ENERGY
 FORM.
  
 20) A MINIMUM 1/4" PER FOOT ROOF SLOPE
 IS REQUIRED PER 97 SBC 1503.1.2.3.
  
 21) PROVIDE TWO (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR:
 - INSWING DOUBLE FRENCH DOORS WITH
 SIDELITES AS SHOWN ON PLANS
 - ADDITIONAL COPY OF PRODUCT APP. FOR
 SINGLE HUNG WINDOWS AND ROOF COVERING
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2002-10-02 Cont ID  
Sent By btrobaug Date 2002-10-02 Time 17:01 Rev Time 0.50
Received By btrobaug Date 2002-10-02 Time 15:37 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-06-04 Cont ID  
Sent By btrobaug Date 2002-06-04 Time 14:04 Rev Time 0.00
Received By btrobaug Date 2002-06-04 Time 12:42 Sent To B
Notes
2002-06-04 00:00:00UNSAT
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE PROVIDE THE FOLLOWING
 INFORMATION,MAKE ANY NECESSARY
 CORRECTIONS TO PLANS AND RESUBMIT FOR
 REVIEW.
  
 1} SHOW SERVICE AND GEAR LOCATIONS ON
 PLAN.
  
 2} GROUND SERVICE PER 250-50(A) & (C),IF
 AVAIALABLE,INDICATE SAME ON PLANS.
  
 3} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4} PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S). PER 210-11-C-3
 MUST BE 20A AND #12AWG.
  
 5} PLEASE LIST THE REQ`D ARC
 FAULT PROTECTED CIRCUITS ON PANEL
 SCHEDULE. PER 210-12
  
 6} PLEASE NOTE FRONT AND REAR
 RECEPTS REQ`D PER 210-52E
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT.8392

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-08 Cont ID  
Sent By dpalmer Date 2002-03-08 Time 06:15 Rev Time 0.00
Received By dpalmer Date 2002-03-08 Time 06:15 Sent To P
Notes
2002-03-08 00:00:00****************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE THAT PLANS ARE NOT
 COMPLETE FOR PROPER REVIEW.
  
 2)NOTE: PLEASE NOTE, LOAD CALCULATIONS
 ARE REQ`D FOR ADDITIONS OVER 500SQ FT.
 220-3-C1
  
 3)NOTE: PLEASE NOTE MORETHAN 50% IS
 BEING DONE, SD`S WILL BE REQ`D INSIDE
 AND OUTSIDE EXISING BEDROOMS AND
 ALSO ANY OTHER ELEC THAT MAY BE NEEDED
 TO MEET CODE.
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
 PLEASE NOTE MISSING SD OUTSIDE BEDROOMS.
  
 6)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 PROTECTION ON PANEL SCHEDULE PER 210-12.
  
 7) PLEASE NOTE MISSING OUTLET FOR A/C
 EQUIPMENT PER 210-63 OF NEC AND 309.2
 MECHANICAL CODE. PLEASE SHOW LOCATION
 OF NEW EQUIPMENT ON ELEC AND DISC`S PER
 440-11.
  
 8)NOTE:PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 IT IS NOT CLEAR IF ANY NEW SERVICE IS
 BEING ADDED.
  
  
 PLEASE COMPLETE PLANS AND RE-SUBMIT FOR
 REVIEW. PLEASE SUBMIT ALL OF THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE ANY
 QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-06-06 Cont ID  
Sent By pkrauss Date 2002-06-06 Time 08:13 Rev Time 0.35
Received By pkrauss Date 2002-06-06 Time 08:13 Sent To  
Notes
2002-06-06 00:00:00MECHANICAL PERMIT 01021344

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-03-14 Cont ID  
Sent By kstevens Date 2002-03-13 Time 09:56 Rev Time 0.30
Received By pkrauss Date 2002-03-14 Time 12:52 Sent To B
Notes
2002-03-14 00:00:00MECH PERMIT 02021344

Review Stop P PLUMBING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By   Date   Time   Sent To  
Notes
2002-10-04 00:00:00APPROVED,PES

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-03-13 Cont ID  
Sent By dpalmer Date 2002-03-08 Time 06:15 Rev Time 0.50
Received By kstevens Date 2002-03-13 Time 09:55 Sent To M
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-03-06 Cont ID  
Sent By sgraham Date 2002-02-28 Time 16:24 Rev Time 0.25
Received By gjoyce Date   Time   Sent To  
Notes
2002-03-06 00:00:00APPROVED BY AJV