Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-03-01 Cont ID  
Sent By pkrauss Date 2002-02-28 Time 12:35 Rev Time 0.30
Received By pkrauss Date 2002-02-28 Time 12:18 Sent To  
Notes
2002-03-01 00:00:00 
 PROVISO:
  
 PLEASE PROVIDE REVISED OUTSIDE AIR
 CALCULATIONS AS PER ASHRAE 62-89.
  
 FAN SHUTDOWN BY DUCT SMOKE DETECTOR
 WITH NOTIFICATION TO ALARM/STROBE IN
 NORMALLY OCCUPIED AREAS AS PER 1997 SMC
 406.1 & NFPA 90A 4-4.4.3.
  
 PLEASE SUBMIT THE ABOVE INFORMATION
 PRIOR TO INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.