| Plan Review Stops For Permit 02021191 |
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-03-01 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-28 |
Time |
12:35 |
Rev Time |
0.30 |
| Received By |
pkrauss |
Date |
2002-02-28 |
Time |
12:18 |
Sent To |
|
|
| Notes |
| 2002-03-01 00:00:00 | | | | PROVISO: | | | | | | PLEASE PROVIDE REVISED OUTSIDE AIR | | | CALCULATIONS AS PER ASHRAE 62-89. | | | | | | FAN SHUTDOWN BY DUCT SMOKE DETECTOR | | | WITH NOTIFICATION TO ALARM/STROBE IN | | | NORMALLY OCCUPIED AREAS AS PER 1997 SMC | | | 406.1 & NFPA 90A 4-4.4.3. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION | | | PRIOR TO INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
|