Plan Review Details - Permit 02021008
| Plan Review Stops For Permit 02021008 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-03-28 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-03-28 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-03-28 |
Time |
16:44 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-02-26 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-02-26 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-02-26 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2002-02-26 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | SBC = STANDARD BUILDING CODE 1997 | | | SBC*= STANDARD BUILD'G CODE (CITY AMEND) | | | | | | 1) A RECORDED COPY OF THE NOTICE OF | | | COMMENCEMENT MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) SBC* 104.2SHEET A8-3, 8TH FLOOR | | | REFLECTED CEILING PLAN.THE SHEET TITLE | | | STATES "NINTH FLOOR REFLECTED CEILING | | | PLAN" AND SHOULD BE CORRECTED TO READ | | | "EIGHTH FLOOR....." | | | | | | 3) SBC* 104.2SHEET A9-3, DETAIL 9.IS | | | THE 'EXISTING OPERABLE HORIZONTAL | | | ROLLING ROAD PANEL' TO BE FIXED SHUT, AS | | | IT IS CONNECTED TO THE NEW PARTITION BY | | | THE PROPOSED SEALANT AND NEOPRENE PAD | | | DETAIL?IF IT IS TO BE FIXED SHUT, IS | | | THE ADJACENT PANEL TO THE EAST AN | | | OPERABLE PANEL?ANNOTATE DETAIL 9 TO | | | CLARIFY THE PROPOSALS. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | IF YOU HAVE ANY QUERIES PLEASE CALL: | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-03-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-21 |
Time |
13:45 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-03-21 |
Time |
13:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-02-25 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-02-25 |
Time |
07:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-02-25 |
Time |
07:10 |
Sent To |
|
|
| Notes |
| 2002-02-25 00:00:00 | ************** UNSAT ****************** | | | | | | 1)NOTE: PLEASE CLARIFY "ER"? EXISTING | | | RELOCATE? AND "RL"? RELOCATE? | | | SHOW AS NOTE> | | | | | | 2)NOTE: PLEASE NOTE THAT 21 NEW OUTLETS | | | ARE SHOWN AS NEW ON 8TH FLOOR AND ALL | | | ARE SHOWN ON THE SAME CIRCUIT P-8? | | | PLEASE SEE 220-13 FOR LOAD PER OUTLET | | | AT 180VA. PLEASE NOTE THIS LOAD FIGURED | | | WOULD EXCEED RATING FOR CIRCUIT. PLEASE | | | ALSO NOTE THAT SAME APPLYS TO NEW | | | OUTLETS SHOWN FOR 9TH FLOOR, ALL ON THE | | | SAME CIRCUIT. PLEASE ADJUST | | | | | | 3)NOTE: PLEASE NOTE THAT FIRE COMMENTS | | | MAY CHANGE ELEC LAYOUT FOR EXITING? | | | | | | 4)NOTE: PLEASE NOTE THAT COVER SHEET | | | SHOWS "96" NEC AND WE ARE UNDER THE "99" | | | NEC. PLEASE CORRECT. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-03-15 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-03-15 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-03-15 |
Time |
16:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-02-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-02-20 |
Time |
12:07 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-02-20 |
Time |
12:06 |
Sent To |
|
|
| Notes |
| 2002-02-20 00:00:00 | A) LOCKS ON EXIT DOORS TO COMPLY WITH | | | DELAYED EGRESS LOCKS PER NFPA 101, 2000 | | | EDITION, SECTION 7.2.1.6.1 OR ACCESS | | | CONTROLLED EGRESS DOORS PER NFPA 101, | | | 2000 EDITION, SECTION 7.2.1.6.2. PLEASE | | | REVIEW THESE SECTIONS OF THE CODE AND | | | ADD NOTES TO THE DRAWINGS. | | | B) PLEASE PROVIDE INFORMATION CONCERNING | | | NOTE 4, A8-2 "PROVIDE POWER AND CONDUIT | | | FOR NEW ELEVATOR SECURITY SYSTEM. | | | C) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION INFORMATION FOR WALLS | | | AND CEILINGS. | | | D) PLEASE DISPLAY EXIT ROUTES ON PLANS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2002-02-25 |
|
|
Cont ID |
|
| Sent By |
ndenmark |
Date |
2002-02-25 |
Time |
14:50 |
Rev Time |
0.33 |
| Received By |
ndenmark |
Date |
2002-02-25 |
Time |
14:50 |
Sent To |
|
|
| Notes |
| 2002-02-25 00:00:00 | PROVISO: | | | PROVIDE OPENING FOR RETURN AIR IN ALL | | | SOLID WALLS FROM OFFICES INTO CORRIDORS |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2002-02-26 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-02-26 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy