Plan Review Details - Permit 02021008
Plan Review Stops For Permit 02021008
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-03-28 Cont ID  
Sent By rbrown Date 2002-03-28 Time 16:44 Rev Time 0.00
Received By rbrown Date 2002-03-28 Time 16:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-26 Cont ID  
Sent By rbrown Date 2002-02-26 Time 10:39 Rev Time 0.00
Received By rbrown Date 2002-02-26 Time 10:39 Sent To  
Notes
2002-02-26 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SBC* 104.2SHEET A8-3, 8TH FLOOR
 REFLECTED CEILING PLAN.THE SHEET TITLE
 STATES "NINTH FLOOR REFLECTED CEILING
 PLAN" AND SHOULD BE CORRECTED TO READ
 "EIGHTH FLOOR....."
  
 3) SBC* 104.2SHEET A9-3, DETAIL 9.IS
 THE 'EXISTING OPERABLE HORIZONTAL
 ROLLING ROAD PANEL' TO BE FIXED SHUT, AS
 IT IS CONNECTED TO THE NEW PARTITION BY
 THE PROPOSED SEALANT AND NEOPRENE PAD
 DETAIL?IF IT IS TO BE FIXED SHUT, IS
 THE ADJACENT PANEL TO THE EAST AN
 OPERABLE PANEL?ANNOTATE DETAIL 9 TO
 CLARIFY THE PROPOSALS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-03-21 Cont ID  
Sent By dpalmer Date 2002-03-21 Time 13:45 Rev Time 0.00
Received By dpalmer Date 2002-03-21 Time 13:45 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-25 Cont ID  
Sent By dpalmer Date 2002-02-25 Time 07:24 Rev Time 0.00
Received By dpalmer Date 2002-02-25 Time 07:10 Sent To  
Notes
2002-02-25 00:00:00************** UNSAT ******************
  
 1)NOTE: PLEASE CLARIFY "ER"? EXISTING
 RELOCATE? AND "RL"? RELOCATE?
 SHOW AS NOTE>
  
 2)NOTE: PLEASE NOTE THAT 21 NEW OUTLETS
 ARE SHOWN AS NEW ON 8TH FLOOR AND ALL
 ARE SHOWN ON THE SAME CIRCUIT P-8?
 PLEASE SEE 220-13 FOR LOAD PER OUTLET
 AT 180VA. PLEASE NOTE THIS LOAD FIGURED
 WOULD EXCEED RATING FOR CIRCUIT. PLEASE
 ALSO NOTE THAT SAME APPLYS TO NEW
 OUTLETS SHOWN FOR 9TH FLOOR, ALL ON THE
 SAME CIRCUIT. PLEASE ADJUST
  
 3)NOTE: PLEASE NOTE THAT FIRE COMMENTS
 MAY CHANGE ELEC LAYOUT FOR EXITING?
  
 4)NOTE: PLEASE NOTE THAT COVER SHEET
 SHOWS "96" NEC AND WE ARE UNDER THE "99"
 NEC. PLEASE CORRECT.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-03-15 Cont ID  
Sent By mcarsill Date 2002-03-15 Time 16:59 Rev Time 0.00
Received By mcarsill Date 2002-03-15 Time 16:59 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-02-20 Cont ID  
Sent By mcarsill Date 2002-02-20 Time 12:07 Rev Time 0.00
Received By mcarsill Date 2002-02-20 Time 12:06 Sent To  
Notes
2002-02-20 00:00:00A) LOCKS ON EXIT DOORS TO COMPLY WITH
 DELAYED EGRESS LOCKS PER NFPA 101, 2000
 EDITION, SECTION 7.2.1.6.1 OR ACCESS
 CONTROLLED EGRESS DOORS PER NFPA 101,
 2000 EDITION, SECTION 7.2.1.6.2. PLEASE
 REVIEW THESE SECTIONS OF THE CODE AND
 ADD NOTES TO THE DRAWINGS.
 B) PLEASE PROVIDE INFORMATION CONCERNING
 NOTE 4, A8-2 "PROVIDE POWER AND CONDUIT
 FOR NEW ELEVATOR SECURITY SYSTEM.
 C) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR WALLS
 AND CEILINGS.
 D) PLEASE DISPLAY EXIT ROUTES ON PLANS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-02-25 Cont ID  
Sent By ndenmark Date 2002-02-25 Time 14:50 Rev Time 0.33
Received By ndenmark Date 2002-02-25 Time 14:50 Sent To  
Notes
2002-02-25 00:00:00PROVISO:
 PROVIDE OPENING FOR RETURN AIR IN ALL
 SOLID WALLS FROM OFFICES INTO CORRIDORS

Review Stop P PLUMBING
Rev No 1 Status N Date 2002-02-26 Cont ID  
Sent By rbrown Date 2002-02-26 Time 10:51 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
***NONE***