Plan Review Details - Permit 02020988
Plan Review Stops For Permit 02020988
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-08-14 Cont ID  
Sent By btrobaug Date 2002-08-14 Time 14:44 Rev Time 0.00
Received By btrobaug Date 2002-05-30 Time 16:05 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-03-11 Cont ID  
Sent By dpalmer Date 2002-03-11 Time 13:25 Rev Time 0.00
Received By dpalmer Date 2002-03-11 Time 13:26 Sent To B
Notes
2002-03-11 00:00:00****************** UNSAT **************
  
 1)NOTE: PLEASE NOTE THAT ALL CODES THAT
 ARE REFERENCED IN NOTES ARE FROM "96"
 NEC. IT HAS BEEN NOTED/REDLINED ON
 PREVIOUS PLANS FOR THE LAST YEAR OR SO.
 PLEASE MAKE CHANGES TO CODES TO REFLECT
 99' CODES. 110-26/250-122/250-140.
  
 2)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GRPOUNDING CONDUCTOR BETWEEN METER/MAIN
 AND PANEL. SIZE PER 250-122
  
 3)NOTE: PLEASE LIST THE REQ`D ARC FAULT
 CIRCUITS ON PANEL SCHEDULE.210-12
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER.
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-03-06 Cont ID  
Sent By hmoser Date 2002-03-06 Time 19:26 Rev Time 0.33
Received By hmoser Date 2002-03-06 Time 19:26 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-03-02 Cont ID  
Sent By jleech Date 2002-03-02 Time 08:49 Rev Time 0.33
Received By jleech Date 2002-03-02 Time 08:49 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 3 Status P Date 2002-08-13 Cont ID  
Sent By rmcdouga Date 2002-08-13 Time 15:13 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-08-13 00:00:00************BUILDING PROVISO************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) PROVIDE A SOIL BEARING TEST REPORT AS
 REQUIRED FOR QUESTIONABLE SOIL BEARING
 CAPACITY BY THE CITY AMENDMENTS TO THE
 1997 SBC SECTION 1804.2.2.
  
 3)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR DOUBLE OUTSWING SOLID CORE
 DOORS AS INDICATED ON THE PLANS FOR THE
 FRONT DOOR.
  
 4) PROVIDE (2) PRODUCT APPROVALS, KEY
 PLANS AND INSTALLATION SCHEDULES
 INDICATING THE SPECIFIC TYPES OF ANCHORS
 TO BE USED FOR STORM PANELS, UNDER A
 SEPARATE PERMIT. SEPARATE PERMIT AND FEE
 ARE REQUIRED BECAUSE ALL OF THE ABOVE
 INFORMATION WAS NOT SUBMITTED.

Review Stop R ROOF PLAN REVIEW
Rev No 2 Status F Date 2002-06-03 Cont ID  
Sent By rmcdouga Date 2002-06-03 Time 09:45 Rev Time 2.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-06-03 00:00:00BUILDING DENIED
  
 1)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE MEAN ROOF HEIGHT GIVEN ON THE
 PLANS (21-5") DIFFERS FROM THE ONE
 GIVEN ON THE DESIGN CERTIFICATION FORM
 (20'-4"). PLEASE CORRECT.
  
 3)THE ARCHITECT'S NAME AND CERTIFICATION
 NUMBER TYPED ON THE BOTTOM LEFT OF THE
 DESIGN CERTIFICATION FORM IS NOT THE
 ARCHITECT THAT SIGNED AND SEALED THE
 DOCUMENT. PLEASE CORRECT.
  
 4) PROVIDE A SOIL BEARING TEST REPORT AS
 REQUIRED FOR QUESTIONABLE SOIL BEARING
 CAPACITY BY THE CITY OF W.P.B.AMENDMENTS
 TO THE 97 S.B.C. SECTION 1804.2.2.
  
 5)PROVIDE (2) CURRENT AND COMPLETE
 COPIES OF SBCCI OR METRO-DADE PRODUCT
 APPROVALS FOR DOUBLE OUTSWING SOLID CORE
 DOORS AS INDICATED ON THE PLANS FOR THE
 FRONT DOOR. THE ONES SUBMITTED FOR THE
 FRONT DOOR IS FOR A SINGLE DOOR WITH
 SIDELITES.
  
 6) PROVIDE (2) COPIES OF KEY PLANS AND
 INSTALLATION SCHEDULES FOR STORM PANELS.
 INDICATE THE FASTENER TYPE THAT WILL BE
 USED. IF THIS INFORMATION IS NOT
 PROVIDED AT TIME OF PERMIT, A SEPARATE
 PERMIT AND ADDITIONAL FEES WILL BE
 REQUIRED FOR THE STORM PANELS.
  
 7) PLEASE INSERT THE NEW PAGES INTO THE
 PLANS.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status F Date 2002-03-19 Cont ID  
Sent By rmcdouga Date 2002-03-19 Time 18:20 Rev Time 4.00
Received By rmcdouga Date   Time   Sent To  
Notes
2002-03-19 00:00:00*************BUILDING UNSAT*************
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SAFETY GLASS IS REQUIRED IN THE 1ST
 FLOOR POWDER ROOM WINDOW, WHICH IS
 WITHIN 2' OF A DOOR PER 97 SBC SECT.
 2405.2.1(3).
  
 3) THE REMARKS FOR WINDOW E IN THE
 WINDOW SCHEDULE DOES NOT INDICATE SAFETY
 GLASS. SAFETY GLASS IS REQUIRED IN THE
 WINDOWS AT THE 2ND FLOOR BATHTUB AND
 SHOWER. PLEASE CORRECT.
  
 4) THE MEAN ROOF HEIGHT LISTED ON THE
 PLANS (21'-5") AND THE DESIGN COMPLIANCE
 FORM (20'-4") DO NOT AGREE. PLEASE
 CORRECT. THIS INFORMATION IS REQUIRED TO
 BE ON THE PLANS FOR FUTURE SUBMITTALS.
  
 5) THE NAME AND CERTIFICATION # OF THE
 PERSON PRINTED ON THE DESIGN COMPLIANCE
 FORM IS NOT THE SAME AS THE PERSON THAT
 SIGNED AND SEALED THE DOCUMENT. PLEASE
 CORRECT.
  
 6) INDICATE COMPLIANCE WITH FIRE CUT
 REQUIREMENTS PER 97 SBC 2305.4, WHERE
 FLOOR TRUSSES ENTER MASONRY WALLS.
  
 7) RISERS ARE INDICATED AS 7-24/32" ON
 A-5, THIS EXCEEDS THE 7-3/4" MAXIMUM
 ALLOWED BY 97 SBC 1007.3.1. PLEASE
 CORRECT.
  
 8) THE STAIRS DO NOT MEET THE MINIMUM
 WIDTH OF 36" REQUIRED BY 97 SBC 1007.6.3
 PLEASE CORRECT.
  
 9) GUARDRAILS SHALL COMPLY WITH 1015.3,
 HAVING INTERMEDIATE RAILS SUCH THAT A
 4-INCH DIAMETER SPHERE CAN NOT PASS
 THROUGH ANY OPENING. PLEASE INDICATE
 THIS ON PLANS.
  
 10) PROVIDE A SOIL BEARING TEST REPORT
 PER CITY OF WPB AMENDEMENTS TO 97SBC
 SECT.1804.2.2.
  
 11) PRODUCT APPROVAL SUBMITTED FOR FRONT
 DOOR DOES NOT MATCH THE PLANS. PLANS
 INDICATE DOUBLE OUTSWING SOLID CORE DOOR
 PLEASE PROVIDE PROPER PRODUCT APPROVAL.
  
 12) PROVIDE KEY PLAN AND INSTALLATION
 SCHEDULE FOR STORM PANELS. INDICATE
 THE TYPE OF FASTENERS THAT WILL BE USED
 ON THE PRODUCT APPROVALS. THIS
 INFORMATION IS REQUIRED AT TIME OF
 PERMIT OR A SEPARATE PERMIT WILL BE
 REQUIRED TO INSTALL STORM PANELS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)659-8096 EXT.8202

Review Stop Z ZONING
Rev No 1 Status P Date 2002-02-28 Cont ID  
Sent By sgraham Date 2002-02-28 Time 09:46 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***