Plan Review Details - Permit 02020859
Plan Review Stops For Permit 02020859
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-03-29 Cont ID  
Sent By rbrown Date 2002-03-29 Time 17:33 Rev Time 0.00
Received By rbrown Date 2002-03-29 Time 17:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-25 Cont ID  
Sent By rbrown Date 2002-02-25 Time 19:40 Rev Time 0.00
Received By rbrown Date 2002-02-25 Time 19:40 Sent To  
Notes
2002-02-25 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 1) SPECIFY THE MAXIMUM ALLOWABLE WEIGHT
 OF CONDENSING UNIT CU-12C, SUPPORTED BY
 THE CANTILEVER BRACKET, ON DETAIL A02/7
  
 2) NEW DUCTWORK PENETRATION THROUGH ROOF
 SLAB.SUBMIT DETAILS TO DESCRIBE THE
 SIZE OF HOLE REQUIRED FOR THE NEW DUCT,
 SLAB THICKNESS AND SPAN DIRECTION, AND
 THE MEANS OF EDGE SUPPORT AROUND THE
 NEW HOLES.THE ROOF PLAN (SHEET A01)
 STATES THAT THIS DETAIL WILL BE SIMILAR
 TO DETAIL A02/4 BUT THAT IS FOR A 5" MAX
 DIAMETER CORE DRILLED HOLE WHICH IS MUCH
 SMALLER.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-03-19 Cont ID  
Sent By dpalmer Date 2002-03-19 Time 19:47 Rev Time 0.00
Received By dpalmer Date 2002-03-19 Time 19:47 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-25 Cont ID  
Sent By dpalmer Date 2002-02-25 Time 06:44 Rev Time 0.00
Received By dpalmer Date 2002-02-25 Time 06:44 Sent To  
Notes
2002-02-25 00:00:00*************** UNSAT ******************
  
 1)NOTE: PLEASE CLARIFY LOAD FOR TWO NEW
 UNITS? PLEAS NOTE, PLANS SHOW A 3P-30A
 AND NOW THATS FEDDING A 3P15 AND 3P20?
  
 2)NOTE: PLEASE ALSO CLARIFY CONDCUTORS
 SHOWN FROM AHU-12C AND CU-12C, PLEASE
 NOTE THAT PLANS SHOW ONLY ONE #12 AND
 ONE #12 GRND? DISC`S ARE SHOWN AS 3P?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-03-21 Cont ID  
Sent By mcarsill Date 2002-03-21 Time 13:58 Rev Time 0.00
Received By mcarsill Date 2002-03-21 Time 13:58 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-02-21 Cont ID  
Sent By mcarsill Date 2002-02-21 Time 14:04 Rev Time 0.00
Received By mcarsill Date 2002-02-21 Time 14:04 Sent To  
Notes
2002-02-21 00:00:00A) PLEASE EXPLAIN NOTE # 4 ON AO1. THIS
 NOTE INDICATES THAT REMOVAL OF
 EXISTING MECHANICAL EQUIPMENT WILL
 OCCUR.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT. 8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-05-06 Cont ID  
Sent By pkrauss Date 2002-05-06 Time 07:40 Rev Time 0.35
Received By pkrauss Date 2002-05-06 Time 07:39 Sent To  
Notes
2002-05-06 00:00:00MECHANICAL PERMIT 02021022

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-04-01 Cont ID  
Sent By pkrauss Date 2002-04-01 Time 11:33 Rev Time 0.30
Received By pkrauss Date 2002-04-01 Time 11:09 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2002-02-25 Cont ID  
Sent By ndenmark Date 2002-02-25 Time 14:32 Rev Time 0.33
Received By ndenmark Date 2002-02-25 Time 14:32 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-05-06 Cont ID  
Sent By kstevens Date 2002-05-06 Time 16:51 Rev Time 0.00
Received By kstevens Date 2002-05-06 Time 16:51 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-04-08 Cont ID  
Sent By jleech Date 2002-04-08 Time 15:40 Rev Time 0.75
Received By jleech Date 2002-04-08 Time 15:40 Sent To  
Notes
2002-04-08 00:00:00DENIED;
 CONDENSATE TO RUN TO THE OUTSIDE OF
 BUILDING BEFORE TIE INTO STORM DRAINAGE.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 659-8096 8369

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-02-26 Cont ID  
Sent By kstevens Date 2002-02-26 Time 09:48 Rev Time 0.50
Received By kstevens Date 2002-02-26 Time 09:48 Sent To  
Notes
2002-02-26 00:00:00DENIED
 REFERENCE: SPC-94
  
 1) SHT MO1-R1 NOTE #24 CONDENSATE DRAIN-
 ING TO SANITARY NOT ACCEPTABLE. CONDEN-
 SATE TO DRAIN TO STORM OUTSIDE OF BLDG
 OR TO CONDENSATE AT WET COLUMN OR DRAIN
 TO DRYWELL ECT. PLEASE SHOW DETAILS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2002-05-06 Cont ID  
Sent By kstevens Date 2002-05-06 Time 16:51 Rev Time 0.00
Received By kstevens Date 2002-05-06 Time 16:51 Sent To  
Notes
***NONE***