Plan Review Details - Permit 02020812
Plan Review Stops For Permit 02020812
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2002-06-27 Cont ID  
Sent By rbrown Date 2002-06-27 Time 20:42 Rev Time 0.00
Received By rbrown Date 2002-06-27 Time 20:42 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2002-06-11 Cont ID  
Sent By rbrown Date 2002-06-11 Time 17:19 Rev Time 0.00
Received By rbrown Date 2002-06-11 Time 17:18 Sent To  
Notes
2002-06-11 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 NOTE:
 THE PLANS WERE ORIGINALLY SUBMITTED FOR
 PLAN REVIEW UNDER 1997 STANDARD BUILDING
 CODE PRIOR TO MARCH 1, 2002.CHANGE OF
 STATUS FROM PLAN REVIEW TO PERMIT
 APPLICATION AFTER THAT DATE REQUIRES
 THAT THE PLANS BE REVIEWED FOR
 COMPLIANCE WITH 2001 FLORIDA BUILDING
 CODE.THIS REVIEW HAS BEEN CARRIED OUT
 TO THE NEW CODE.THE PLANS SHALL NOT
 MAKE REFERENCE TO THE OUTGOING CODE.
  
 SHEET CS, COVER SHEET, SHALL BE AMENDED
 TO REFER TO 2001 FLORIDA BUILDING CODE
 INSTEAD OF 1997 SATNDARD BUILDING CODE.
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 4/19/02:
  
 3) FBC 1606.1.4PROTECTION OF OPENINGS
 PLEASE NOTE THAT THE STOREFRONT DOOR
 PRODUCT APPROVAL NOTICE OF ACCEPTANCE
 NO. 01-0919.02, SHEET 2, SPECIFIC
 CONDITIONS, ITEM 3.2 STATES THAT THE
 DOOR UNIT SHALL ONLY BE INSTALLED AT
 LOCATIONS PROTECTED BY A CANOPY OR
 OVERHANG.REFER TO THE PRODUCT APPROVAL
 FOR FURTHER DETAILS AND DESCRIBE THE
 METHOD PROPOSED TO RESTRICT WATER
 INFILTRATION.
  
 6) FBC 11-4.1.3(10)ACCESSIBLE DRINKING
 FOUNTAIN.BOTH DETAIL 6/A-5 AND 20/A-5
 SHOW THE 36" MAXIMUM HEIGHT DIMENSION
 INCORRECTLY.THE DIMENSION SHOULD SHOW
 36" MAXIMUM SPOUT HEIGHT ABOVE THE FLOOR
 SEE FIG. 27.
  
 THE FOLLOWING COMMENT IS A RESULT OF THE
 REVISIONS TO THE PLANS SINCE THE LAST
 REVIEW:
  
 C) FBC 704.1OCCUPANCY SEPARATION.
 SHEET A-1, PARTITION TYPE A2 IS REQUIRED
 TO BE TWO-HOUR FIRE-RATED.AMEND THE
 PLANS TO SHOW THE UL LISTING REFERENCE
 FOR THE PROPOSED TWO-HOUR ASSEMBLY.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2002-04-19 Cont ID  
Sent By rbrown Date 2002-04-19 Time 15:13 Rev Time 0.00
Received By rbrown Date 2002-04-19 Time 15:13 Sent To  
Notes
2002-04-19 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY AMEND)
 FL ACC CODE = FLORIDA ACCESSIBILITY CODE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS
 ARE NUMBERED AS PER THE BUILDING PLAN
 REVIEW OF 2/25/02:
  
 3) SBC 1606.4PROTECTION OF OPENINGS.
 THE DETAIL 4/A-3 REFERENCE TO PRODUCT
 APPROVALS FOR THE STOREFRONT IS NOTED.
 HOWEVER, TWO COPIES OF EACH PRODUCT
 APPROVAL NOTICE OF ACCEPTANCE, WITH
 ASSOCIATED APPROVED DRAWINGS, MUST BE
 SUBMITTED.
  
 6) FL ACC CODE 4.1.3(10)ACCESSIBLE
 DRINKING FOUNTAIN.ON DETAIL 6/A-5,
 BREAKROOM/KITCHEN ELEVATION, THE 27"
 MINIMUM LEG CLEARANCE HEIGHT DIMENSION
 IS SHOWN INCORRECTLY.ADD A SIDE
 ELEVATION OF THE DRINKING FOUNTAIN TO
 DEMONSTRATE COMPLIANCE WITH THIS, AND
 EACH OF THE OTHER, CLEARANCE/REACH
 REQUIREMENTS SHOWN IN FIG. 27
  
  
 THE FOLLOWING COMMENTS RESULT FROM THE
 REVISIONS TO THE PLANS SINCE THE LAST
 REVIEW:
  
 A) FL ACC CODE FIG. 30(A)TOILET STALLS
 THE REVISION OF THE TOILET LAYOUT IS
 NOTED.TOILET 1 SHALL HAVE ACCESSIBLE
 STALL DIMENSIONS OF 60"WIDE AND 59"DEEP
 FOR A FLOOR MOUNTED W.C.IF THE W.C.
 WERE CHANGED TO WALL MOUNTED, THEN THE
 MIN. STALL DIMENSIONS SHALL BE 60"WIDE
 AND 56"DEEP.ANNOTATE/AMEND THE PLANS
 TO DEMONSTRATE COMPLIANCE.
  
 B) SBC* 104.2.3THE REVISED
 ARCHITECTURAL PLANS ARE NOT PROPERLY
 SEALED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUESTIONS PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-25 Cont ID  
Sent By rbrown Date 2002-02-25 Time 17:15 Rev Time 0.00
Received By rbrown Date 2002-02-25 Time 17:15 Sent To  
Notes
2002-02-25 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
  
 1) THE 'PROJECT INFORMATION' (SHEET CS)
 MAKES REFERENCE TO '1994 STANDARD
 BUILDING CODE' WHICH IS NOT A CURRENT
 CODE. UNTIL MARCH 1,2002 EITHER STANDARD
 BUILDING CODE 1997 OR FLORIDA BUILDING
 CODE 2001 MAY BE USED.NEITHER CODE IS
 REFERENCED ON THE PLANS. THE PLANS MUST
 STATE WHICH CODE THE WORK IS TO BE
 CONSTRUCTED TO.
  
 2) FBC* 104.2SHEET A-3, DETAIL 4,
 IMPLIES THAT A NEW STOREFRONT IS TO BE
 INSTALLED.ADD NOTES TO THE FLOOR PLAN
 TO CONFIRM THIS.ALSO, ON THE PERMIT
 APPLICATION FORM UNDER 'DESCRIBE PROJECT
 IN DETAIL' THE ENTRY IS SIMPLY "INTERIOR
 BUILD-OUT" WITH NO REFERENCE TO A NEW
 STOREFRONT.PROVIDE SUFFICIENT
 INFORMATION TO DESCRIBE THE SCOPE OF
 WORK.
  
 3) FBC 1606.1.4PROTECTION OF OPENINGS.
 SUBMIT A PRODUCT APPROVAL FOR THE NEW
 STOREFRONT.
  
 4) FBC 2405.2THE GLAZING IN THE NEW
 STOREFRONT, INTERNAL DOORS OR WITHIN 24"
 OF ANY DOOR OPENING IS IN A 'HAZARDOUS
 LOCATION' AND IS REQUIRED TO BE SAFETY
 GLASS SATISFYING THE REQUIREMENTS OF THE
 CONSUMER PRODUCT SAFETY COMMISSION 16,
 CODE OF FEDERAL REGULATIONS, PART 1201
 (CPSC 16-CFR, PART 1201).SUBMIT
 DETAILS TO DEMONSTRATE COMPLIANCE.
  
 5) FBC* 104.2ANNOTATE THE PLANS TO
 CLARIFY WHERE 'GLAZED' PARTITIONS ARE TO
 BE INSTALLED.IS THE L-SHAPED PARTITION
 ADJACENT THE RECEPTION DESK A GLAZED
 PARTITION, IF SO, IS A CORNER MULLION/
 FRAMING PROPOSED?THERE ARE NO NOTES
 DESCRIBING GLAZED PARTITION PROPOSALS.
  
 6) FBC 11-4.1.3(10)AN ACCESSIBLE
 DRINKING FOUNTAIN, COMPLYING WITH
 FBC 11-4.15, SHALL BE PROVIDED.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2002-07-15 Cont ID  
Sent By dpalmer Date 2002-07-15 Time 07:22 Rev Time 0.00
Received By dpalmer Date 2002-07-15 Time 07:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2002-07-01 Cont ID  
Sent By dpalmer Date 2002-07-01 Time 06:11 Rev Time 0.00
Received By dpalmer Date 2002-07-01 Time 06:11 Sent To  
Notes
2002-07-01 00:00:00************** UNSAT *************
  
 1)NOTE: PLEASE SEE NOTES ATTACHED FROM
 THE FIRST THREE REVIEWS.
  
  
  
  
 2)NOTE: PLEASE CLARIFY A/C LOAD?
 A/C AS 6.9? PLEASE NOTE LOAD SHOWN AS 15
 KW ON MECH PLANS?
 PLEASE NOTE LOAD CALCS SHOW AS 16.8KW?
 PLEASE CORRELATE.
  
 3)NOTE: PLEASE ALSO NOTE THAT E-3 STILLS
 SHOWS A/C EQUIPMENT COMING FROM OTHER
 SERVICE? SEE LOWER RIGHT HAND CORNER.
  
 4)NOTE: PLEASE SEE SHEET ATTACHED FOR
 FS/FAC 553.80(2)(B).
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372
  
 PLEASE ALSO NOTE WATER HEATER LOAD SHOWN
 AS 6.0 ON LOAD CALCS AND 1.5 ON PANEL
 SCHEDULE?

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-06-04 Cont ID  
Sent By dpalmer Date 2002-06-04 Time 16:15 Rev Time 0.00
Received By dpalmer Date 2002-06-04 Time 16:01 Sent To  
Notes
2002-06-04 00:00:00****************** UNSAT *************
  
 1)NOTE: PLEASE NOTE THAT RESPONSE
 LETTER NOTES COMPLIANCE WITH GROUPING OF
 MAINS AND SUPPLYING A/C EQUIPMENT FROM
 PANEL "A", HOWEVER ONLY SHEET E-2 HAS
 BEEN CHANGED TO REFLECT THOSE CHANGES.
 PLEASE NOTE THAT E-3 STILL SHOWS OLD
 CONFIGURATION .
  
 2)NOTE: PLEASE REVISE PANEL SCHEDULE
 AND LOAD CALCULATIONS TO CORRELATE WITH
 E-2.
  
 ***NOTE**
 PLEASE DO NOT SUBMIT "EXTRA" REVISED
 SHEETS. PLEASE TAKE OLD SHEETS OUT AND
 INSERT NEW/REVISED SHEETS FOR TWO
 COMPLETE SETS FOR REVIEW.
  
 ***** NOTE******
 PLEASE ALSO NOTE THAT THERE MAY BE SOME
 CHANGES NEEDED FOR OTHER TRADES DUE TO
 THE PLANS NEEDING TO MEET 2001 FBC.
 PLEASE NOTE THAT PLANS WERE NEVER
 SUBMITTED FOR PERMIT, ONLY "PLAN REVIEW"
 PLEASE ALSO NOTE THAT WE ARE STILL UNDER
 THE "99" NEC AND ONLY CHANGES TO FIRE/
 OR MECH MAY CHANGE E-SHEETS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION AS
 SET FORTH IN NOTE(1) WHEN ALL REVIEWS
 ARE DONE. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-04-24 Cont ID  
Sent By dpalmer Date 2002-04-24 Time 12:53 Rev Time 0.00
Received By dpalmer Date 2002-04-24 Time 12:52 Sent To  
Notes
2002-04-24 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE CLARIFY IF SECOND SERVICE
 IS PERMITTED DUE TO DIFFERENT VOLTAGES,
 (230-2), PLEASE NOTE GROUPING OF MAINS
 PER 230-72. PLEASE NOTE LIFE SAFETY
 ISSUE IF FIRE DEPT SHUTS DOWN MAIN FOR
 ELECTRICAL IN UNIT AND THEN 277/480V
 IS STILL PRESENT. PLEASE NOTE THAT THIS
 CREATES A PROBLEM.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-27 Cont ID  
Sent By dpalmer Date 2002-02-27 Time 6:45 Rev Time 0.00
Received By dpalmer Date 2002-02-26 Time 16:54 Sent To  
Notes
2002-02-26 00:00:00******************** UNSAT ************
  
 1)NOTE: PLEASE NOTE LOAD CALCULATIONS
 NEED TO BE SHOWN. WATTS PER SQ FT, 180VA
 PER OUTLET, 220-3,220-11,220-11,220-13,
 PLEASE ALSO NOTE THAT ALL CONTINUOUS
 LOADS NEED TO BE SHOWN AT 125%.
 215-2/3,230-42.
  
 2)NOTE: PLEASE NOTE THAT A/C SYSTEM IS
 SHOWN BEING FED FROM ANOTHER SERVICE
 THAT FEED ANOTHER SPACE. PLEASE NOTE,
 THIS IS NOT PERMITTED.
 SYSTEM NEEDS TO COME FROM THE SAME
 SERVICE AS EACH TENANT SPACE. 230-72,
 230-2 ETC.
  
 3)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 4)NOTE: PLEASE NOTE THAT INSTANT WATER
 HEATER IS SHOWN AS SINGLE PHASE 120V
 ON E-2 AND PANEL SCHEDUE AS 3-PHASE?
 PLEASE CLARIFY.
  
 5)NOTE: PLEASE NOTE MISSING OUTLET(S)
 FOR "SHOW" WINDOWS. 210-62.
  
 6)NOTE: PLEASE NOTE MISSING SIGN CIRCUIT
 PER 600-5. NOTE #8 ON E-1 NEEDS TO BE
 SHOWN.
  
 7)NOTE: PLEASE NOTE LOAD CALCS FOR TRACK
 LIGHTING NEEDS TO BE SHOWN. 220-12B.
  
 8)NOTE: PLEASE NOTE THAT PANEL IS SHOWN
 IN A STORAGE ROOM. PLEASE NOTE ON PLANS
 THAT AREA MUST MEET 110-26 AND OUTLINED
 MARKINGS ARE TO PAINTED ON FLOORS TO
 SHOW CLEARENCE REQ`MENTS.110-26 AND
 NOTE, 384-7.
  
 9)NOTE: PLEASE NOTE THAT NOTE #2 UNDER
 WIRE AND CABLE ON E-3. MENTIONS COLOR
 CODING PER NEC.
 PLEASE NOTE THAT PER LOCAL AMENDMENTS,
 215-8
 120/208V, BLK/RED/BLUE AND 277/480V
 BROWN/PURPLE/YELLOW.
 PLEASE NOTE.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-03-01 Cont ID  
Sent By pkrauss Date 2002-03-01 Time 14:20 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2002-06-28 Cont ID  
Sent By mcarsill Date 2002-06-28 Time 10:01 Rev Time 0.00
Received By mcarsill Date 2002-06-28 Time 10:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2002-05-30 Cont ID  
Sent By mcarsill Date 2002-05-30 Time 10:01 Rev Time 0.00
Received By mcarsill Date 2002-05-30 Time 10:01 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-05-07 Cont ID  
Sent By mcarsill Date 2002-05-07 Time 08:25 Rev Time 0.00
Received By mcarsill Date 2002-05-07 Time 08:25 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-02-19 Cont ID  
Sent By mcarsill Date 2002-02-19 Time 14:08 Rev Time 0.00
Received By mcarsill Date 2002-02-19 Time 14:08 Sent To  
Notes
2002-02-19 00:00:001) PLEASE INDICATE FIRE RATINGS OF
 EXISTING TENANT DEMISING WALLS. WHAT
 ARE THE OTHER OCCUPANCY TYPES ADJACENT
 TO THE PROPOSED TD WATERHOUSE.
 2) THE KEY PLAN INDICATES THAT THE
 REAR ROOM IS LABELED STORAGE. OTHER
 DRAWINGS INDICATES THAT IT IS A
 BREAKROOM.
 3) NO FIRE SPRINKLER DRAWINGS PROVIDED.
 4) NO FIRE ALARM EQUIPMENT SHOWN ON
 THE PLANS.
 5) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION INFORMATION FOR THE
 WALLS AND CEILINGS OF PROPOSED SPACE.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2002-06-22 Cont ID  
Sent By pkrauss Date 2002-06-22 Time 10:22 Rev Time 0.30
Received By pkrauss Date 2002-06-22 Time 10:22 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2002-06-10 Cont ID  
Sent By pkrauss Date 2002-06-10 Time 13:49 Rev Time 0.40
Received By pkrauss Date 2002-06-10 Time 13:40 Sent To  
Notes
2002-06-10 00:00:00PROVSIO:
 PLAN SHEET PM-1 - (OUTSIDE AIR CALCS)
 AS PER CONVERSATION W/STEVE CLEMIT/ENG.
  
  
 1.PROVIDE OUTSIDE AIR CALCULATIONS AS
 PER 2001 FBC(M) TABLE 403.3 OR
 ASHRAE 62-89.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-04-17 Cont ID  
Sent By pkrauss Date 2002-04-17 Time 16:49 Rev Time 0.40
Received By pkrauss Date 2002-04-17 Time 14:53 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-03-01 Cont ID  
Sent By pkrauss Date 2002-03-01 Time 13:55 Rev Time 1.00
Received By pkrauss Date 2002-03-01 Time 13:55 Sent To  
Notes
2002-03-01 00:00:00 
 PLANS REVIEWED UNDER THE 2001 FLORIDA
 BUILDING CODE, MECHANICAL
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION
 FOR REVIEW:
  
 1.PROVIDE LOCATION OF OU-1.PLEASE
 NOTE AS PER 2001 FBC, MECH 306.5 -
 EQUIPMENT REQUIRING ACCESS ARE
 INSTALLED ON ROOFS OR ELEVATED
 STRUCTURES AT A HEIGHT EXCEEDING 16
 FEET, AN APPROVED PERMANENT MEANS OF
 ACCESS IS REQUIRED.
  
 2.PROVIDE INFORMATION AS TO WHAT WILL
 BE KEPT IN THE "STORAGE" SPACE.
  
 3.SEE ELECTRICAL PLAN REVIEW COMMENT
 #3.
  
 PLEASE NOTE, AS PER 2001 FBC, MECHANICAL
 401.5, OUTSIDE AIR EXHAUST & INTAKE
 OPENINGS SHALL BE LOCTED A MINUMUM OF
 10 FT FROM LOT LINES OR BUILDINGS ON
 THE SAME LOT.401.5.2, EXHAUST
 OPENINGS SHALL NOT BE DIRECTED ONTO
 WALKWAYS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-07-05 Cont ID  
Sent By kstevens Date 2002-07-05 Time 19:49 Rev Time 0.00
Received By kstevens Date 2002-07-05 Time 19:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-06-12 Cont ID  
Sent By kstevens Date 2002-06-12 Time 10:21 Rev Time 0.00
Received By kstevens Date 2002-06-12 Time 10:21 Sent To  
Notes
2002-06-12 00:00:00DENIED
 REFERENCE: FBC-2001 CHAPTER 11
 FBC-2001 PLUMBING
  
 1) CODE REFERENCE SHALL BE FBC FOR ANY
 APPLICATION RECIEVED AFTER FEBRUARY 28,
 2002. PLEASE CHANGE ALL CODE REFERENCES
 2) PER FBC-2001 TABLE 403.1 A SERVICE
 SINK IS REQUIRED.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-05-04 Cont ID  
Sent By kstevens Date 2002-05-04 Time 16:31 Rev Time 0.00
Received By kstevens Date 2002-05-04 Time 16:31 Sent To  
Notes
2002-05-04 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHTS A-1/A-2 PER RULE 9B-7.0043 FLA.
 ADMIN CODE, (SEE FIG 30(E)) A LAVATORY
 SHALL BE PROVIDED WITHIN THE ACCESSIBLE
 TOILET STALL.
 2) SHTS A-1/A-2 WOMENS RESTROOM, THE
 5' TURNING RADIUS SHALL BE IN THE TOILET
 ROOM, NOT THE STALL.
 3) ALL HDCP LAVSSHALL BE 1'3" TO CENT-
 ER OFF THE WALL AND BE CENTERED IN THE
 30" CLEAR FLOOR SPACE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-02-27 Cont ID  
Sent By kstevens Date 2002-02-27 Time 13:52 Rev Time 1.00
Received By kstevens Date 2002-02-27 Time 13:51 Sent To  
Notes
2002-02-27 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHT CS MINIMUM FACILITIES CALL FOR
 1 W/C & 1 LAV MALE - 2 W/C'S & 2 LAV'S
 FEMALE. ALSO 1 DRINKING FOUNTAIN REQUIR-
 ED. SPC TABLE 407 & SEC 407.1.3.
 2) SHT A-2 SHOW CLEAR FLOOR SPACE FOR
 ALL HDCP FIXTURES. LAV'S, W/C'S, DRINK-
 ING FOUNTAIN, AND BREAK ROOM SINK.
 3) SHT A-5 DETAIL #6, PLEASE SHOW COMP-
 LIANCE WITH FACBC SEC 4.24 AND ALL SUB-
 SECTIONS.
 4) SHT A-5 SHOW DETAIL OF DRINKING FOUN-
 TAIN. COMPLY WITH FACBC SEC 4.15 AND ALL
 SUBSECTIONS, AND SEC 4.1.3(10) FOR THOSE
 WHO HAVE DIFFICULTY BENDING OR STOOPING.
 5) SHT PM-1 PLEASE SUBMIT MANUFACTURE'S
 INFORMATION ON INSTANTANIOUS W/HEATERS.
 SHOW LISTING FOR PRODUCT.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status N Date 2002-03-01 Cont ID  
Sent By pkrauss Date 2002-03-01 Time 14:20 Rev Time 0.05
Received By pkrauss Date   Time   Sent To  
Notes
***NONE***