Plan Review Details - Permit 02020740
Plan Review Stops For Permit 02020740
Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-02-21 Cont ID  
Sent By pkrauss Date 2002-02-21 Time 08:55 Rev Time 0.35
Received By pkrauss Date 2002-02-21 Time 08:55 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-02-19 Cont ID  
Sent By pkrauss Date 2002-02-19 Time 11:25 Rev Time 0.35
Received By pkrauss Date 2002-02-19 Time 11:22 Sent To  
Notes
2002-02-19 00:00:00 
 ONLY ONE COPY OF PLAN SUBMITTED.
  
 CLARIFY 3 1/2 TON SYSTEM - DISTRIBUTION
 BOX #1 INDICATE 2-7" DROPS & 1-8" DROP
 (2ND FL).1ST FLOOR INDICATES 1-8",
 1-9" & 1-7"DROP.ALSO, CONDENSER UNIT
 INDICATES A 3 TON NOT A 3 1/2 TON.