| 2002-03-21 00:00:00 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |
| | |
| | UNTIL MARCH 1, 2002 EITHER STANDARD |
| | BUILDING CODE 1997 OR FLORIDA BUILDING |
| | CODE 2001 MAY BE USED. BECAUSE THE PLANS |
| | REFER TO "STANDARD BUILDING CODE AS |
| | ADOPTED BY THE CITY", THEY HAVE BEEN |
| | REVIEWED FOR COMPLIANCE WITH STANDARD |
| | BUILDING CODE 1997. |
| | |
| | SBC = STANDARD BUILDING CODE 1997 |
| | SBC*= STANDARD BUILD'G CODE (CITY AMEND) |
| | |
| | 1) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 2) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 3) SBC* 1606.4SUBMIT PRODUCT APPROVALS |
| | FOR THE MULLIONS AND TRANSOMS TO BE USED |
| | IN WINDOWS INCORPORATING MULTIPLE WINDOW |
| | UNITS.ALSO, THE SUBMITTED NOTICE OF |
| | ACCEPTANCE (NO. 99-1110.04) FOR THE |
| | SERIES 6000 ALUMINUM FIXED WINDOW IS |
| | MISSING DRAWING SHEET 2 OF 4. |
| | |
| | 4) SBC* 1606.4STATE THE REQUIREMENT |
| | FOR INSTALLATION OF HURRICANE PROTECTION |
| | SHUTTERS ON THE PLANS. |
| | |
| | 5) SBC 1507.1.2ROOF TILE PRODUCT |
| | APPROVAL.THE NOTICE OF ACCEPTANCE NO |
| | AND MANUFACTURER ON SHEET 2 OF THE |
| | SUBMITTED PRODUCT APPROVAL DOES NOT |
| | CORRESPOND TO THAT OF THE REMAINING |
| | SHEETS.REPLACE SHEET 2 OR SUBMIT A |
| | COMPLETE AND CONSISTENT PRODUCT APPROVAL |
| | |
| | 6) SBC 2309.7SHEET A8, TYPICAL WALL |
| | SECTION.CROSS VENTILATION SHALL BE |
| | PROVIDED FOR EACH SEPARATE ATTIC SPACE. |
| | AT LEAST 50% OF THE REQUIRED VENTILATION |
| | AREA SHALL BE AT A LEVEL NO LESS THAN |
| | 3FT ABOVE THE EAVES VENTS. AMEND THE |
| | THE PLANS TO DEMONSTRATE COMPLIANCE. |
| | |
| | 7) SBC* 104.2SHEET A3, FLOOR PLAN. |
| | THE MASTER BEDROOM PRIVACY WALL CROSS- |
| | SECTION REFERENCE A7/25 SHOULD READ |
| | A8/25. |
| | |
| | 8) SBC* 104.2SHEET A2, FOUNDATION PLAN |
| | THICKENED EDGE TE1 AND TE2 ARE NOT SHOWN |
| | ON THE FOOTING SCHEDULE.IT SHOULD BE |
| | AMENDED TO REFER TO THE TE1 AND TE2 |
| | DETAILS ON SHEET A8. |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |
| | THE CODE REFERENCES GIVE ADDITIONAL INFO |
| | IF YOU HAVE ANY QUERIES PLEASE CALL: |
| | ROBERT BROWN(561) 659 8096 EXT 8499 |