| Plan Review Stops For Permit 02020712 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-03-18 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-03-14 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-03-14 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2002-03-14 00:00:00 | BUILDING PLAN REVIEW | | | *******PROVISO****** | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | | | | --PASSED WITH THE FOLLOWING PROVISO-- | | | SUBMIT REVISED PLANS IF ANY OF THE FIVE | | | UNLABELLED ROOMS ARE TO BE USED AS | | | SLEEPING ROOMS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-02-22 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-02-22 |
Time |
11:37 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2002-02-22 |
Time |
11:37 |
Sent To |
|
|
| Notes |
| 2002-02-22 00:00:00 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 659 8096 EXT 8499 | | | | | | FBC = FLORIDA BUILDING CODE 2001 | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | | | | 1) UNTIL MARCH 1, 2002 EITHER STANDARD | | | BUILDING CODE 1997 OR FLORIDA BUILDING | | | CODE 2001 MAY BE USED.NEITHER CODE IS | | | REFERENCED ON THE PLANS.STATE WHICH | | | CODE THE WORK IS TO BE CONSTRUCTED TO. | | | | | | 2) AMEND THE PLANS TO SHOW THE | | | USE/OCCUPANCY OF EACH ROOM. | | | | | | 3) THE PROJECT DESCRIPTION ON THE PERMIT | | | APPLICATION FORM STATES "TENANT | | | SEPARATION WALLS", BUT THE NEW WALLS ON | | | THE PLANS ARE ANNOTATED AS "NEW INTERIOR | | | PARTITION",AND THERE ARE INTERCONNECTING | | | DOORS BETWEEN ROOMS EAST OF THE ELEVATOR | | | ANNOTATE THE PLANS TO CLARIFY THE SCOPE | | | OF THE PERMIT APPLICATION. | | | | | | 4) FBC 1005.4EVERY SLEEPING ROOM SHALL | | | HAVE AT LEAST ONE EXTERIOR EMERGENCY | | | ESCAPE AND RESCUE OPENING.IDENTIFY THE | | | BEDROOMS ON THE PLANS AND DEMONSTRATE | | | COMPLIANCE.THE INTERNAL DOOR HARDWARE | | | SHALL NOT BE LOCKABLE, PREVENTING ACCESS | | | TO THE EXISTING EXIT DOOR. | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO | | | IF YOU HAVE ANY QUERIES PLEASE CALL: | | | ROBERT BROWN(561) 659 8096 EXT 8499 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-03-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-03-14 |
Time |
13:30 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-03-14 |
Time |
13:30 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-02-14 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-02-14 |
Time |
07:30 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-02-14 |
Time |
07:30 |
Sent To |
|
|
| Notes |
| 2002-02-14 00:00:00 | ************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE NOTE THAT PERMIT | | | APPLICATION SAYS TENANT WALLS? AND | | | ELEC/PLUMB/MECH BOXES ARE CHECKED?? | | | | | | 2)NOTE: PLEASE NOTE PLANS CALL FOR ALL | | | RESIDENTIAL ?? PLEASE SUBMIT LOAD | | | CALCULATIONS AND PANEL SCHEDULES. | | | PLEASE CLARIFY 2ND FLOOR IS SHOWN AS | | | ALL ONE UNIT? PLEASE CLARIFY HOW THERE | | | IS TENANT SEPARATION WALLS IN ONE UNIT | | | OR ARRE THEY JUST INTERIOR WALLS FOR | | | BEDROOMS? | | | | | | | | | 3)NOTE: PLEASE SHOW ALL CIRCUITING #`S | | | ON PLANS. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-03-19 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-03-19 |
Time |
09:39 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-03-19 |
Time |
09:39 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-02-14 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-02-14 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-02-14 |
Time |
10:43 |
Sent To |
|
|
| Notes |
| 2002-02-14 00:00:00 | 1) IS THE ENTIRE FLOOR SPACE USED | | | FOR RESIDENTIAL PURPOSES. IS THE FLOOR | | | A MIXED USE. | | | 2) ADDITIONAL SMOKE DETECTORS MAY BE | | | NEEDED. | | | 3) PLEASE IDENTIFY ROOMS OR ROOM USES. | | | | | | MIKE CARSILLO, CAPTAIN | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-03-15 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-15 |
Time |
15:47 |
Rev Time |
0.35 |
| Received By |
pkrauss |
Date |
2002-03-15 |
Time |
15:47 |
Sent To |
|
|
| Notes |
| 2002-03-15 00:00:00 | | | | PROVISO ON PLAN |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-02-20 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-20 |
Time |
09:55 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-02-20 |
Time |
09:55 |
Sent To |
|
|
| Notes |
| 2002-02-20 00:00:00 | *******************DENIED*************** | | | | | | | | | APPLICATION INDICATES TENANT SEPARATION, | | | SHOW COMPLIANCE WITH FLA ENERGY CODE | | | (1997), THE SUPPLY OF HEATING & COOLING | | | TO EACH ZONE SHALL BE CONTROLLED BY | | | INDIVIDUAL THERMOSTATIC CONTROLS FOR | | | CONTROLLING THE TEMPERATURE WITHIN THE | | | ZONE. | | | | | | INDICATE THE USE OF THE ROOM TO THE | | | SOUTHEAST.NO VENTILATION PROVIDED FOR | | | THIS SPACE.ELECTIRICAL PLAN INDICATES | | | AN OUTLET FOR TELEPHONE & COMPUTER. | | | | | | PROVIDE OUTSIDE AIR CALCULATIONS AS PER | | | ASHRAE 62-89. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2002-03-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-03-15 |
Time |
16:16 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2002-03-15 |
Time |
16:16 |
Sent To |
|
|
| Notes |
| 2002-03-15 00:00:00 | PASSED/PROVISO | | | | | | BECAUSE OF CHANGE OF OCCUPANCY FROM | | | COMMERCIAL TO RESIDENTIAL A WASHING | | | MACHINE CONNECTION WAS REQUIRED. SPC-94 | | | TABLE 407. | | | SUBSEQUENTLY A REVISION SHALL BE | | | REQUIRED SHOWING THE WASHING MACHINE | | | CONNECTION BOTH ON THE FLOOR PLAN AND | | | ON A RISER DIAGRAM. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2002-02-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-02-19 |
Time |
09:22 |
Rev Time |
0.33 |
| Received By |
kstevens |
Date |
2002-02-19 |
Time |
09:22 |
Sent To |
|
|
| Notes |
| 2002-02-19 00:00:00 | NO PLUMBING INFORMATION ON THESE PLANS |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2002-03-20 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2002-03-20 |
Time |
15:55 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|