| Plan Review Stops For Permit 02020701 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-04-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2002-04-02 |
Time |
15:11 |
Rev Time |
1.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-04-02 00:00:00 | PLANS TO BE SUBMITTED TO COUNTY FOR | | | IMPACT FEE ASSESSMENT BEFORE ISUANCE |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2002-03-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-03-29 |
Time |
10:01 |
Rev Time |
1.75 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-08 00:00:00 | PERMIT # 02020701 | | | 247 SEVILLE ROAD | | | O/B WESTERVELT, THEODORE | | | HOME: 582-4579 | | | CELL: (561) 308-6458 | | | | | | 1997 STANDARD BUILDING CODE | | | | | | 1)- MISSING PRODUCT APPROVALS (2 COPIES) | | | FOR WINDOW AND FOR ROOFING MATERIALS TO | | | BE USED, TESTED FOR 110 MPH WIND ZONE. | | | 2)- PLANS DO NOT INDICATE HOW THE RAFTER | | | WILL CANTALEVER FROM THE DOUBLE 2X12 AT | | | THE CARPORT. SHEET A-2 | | | 3)- KNEE WALL ATTACHMENT TO BEAM? | | | 4)- THERE IS AN INDICATION OF A THROUGH | | | THE WALL AIR CONDITIONER, PLANS DO NOT | | | INDICATE IF THERE IS INSULATION OR A | | | CEILING. | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | (561)659-8096 X8412 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2002-05-01 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-05-01 |
Time |
13:58 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-05-01 |
Time |
12:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2002-04-16 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-04-16 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-04-16 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2002-04-16 00:00:00 | ***************UNSAT!******************* | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} PENCIL IN NOTES ON THE SEALED | | | DRAWINGS IS UNACCEPTABLE. | | | | | | PLEASE CORRECT THESE ITEMS AND RESUBMIT | | | FOR REVIEW. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/659-8096 EXT.8392 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2002-03-29 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-03-29 |
Time |
10:00 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-03-29 |
Time |
07:33 |
Sent To |
B |
|
| Notes |
| 2002-03-29 00:00:00 | **************** UNSAT ***************** | | | | | | 1}PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2} WIRE SIZE LISTED FOR THE SERVICE | | | FEEDER IS INCORRECT FOR 200 AMPS. | | | | | | 3} PLAN ONLY SHOWS THE PANEL | | | LOCATION,PLEASE SHOW METER AND | | | DISCONNECT LOCATION ALSO. | | | | | | PLEASE PROVIDE INFORMATION REQUESTED AND | | | RESUMBIT FOR REVIEW. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/659-8096 EXT. 8392 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-02-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-02-21 |
Time |
16:17 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-02-21 |
Time |
16:17 |
Sent To |
P |
|
| Notes |
| 2002-02-21 00:00:00 | *************** UNSAT **************** | | | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW EQUIPMENT BEING INSTALLED. | | | MAINS/PANELS/BREAKERS MUST BE RATED FOR | | | THE AVAILABLE FAULT CURRENT PER 110-9. | | | | | | 2)NOTE: PLEASE NOTE PERMIT APPLICATION | | | MENTIONS A NEW UNDERGROUND TO MAIN | | | HOUSE BUT NOTHING SHOWN ON ELECTRICAL | | | PLANS?? PLEASE CLARIFY GROUPING OF MAINS | | | AND NEW? SERVICE FOR MAIN HOUSE. | | | SUBMIT ON RISER DIAGRAM. | | | PER ZONING REG`S, ONLY ONE METER | | | PERMITTED. | | | | | | 3)NOTE: PLEASE NOTE THAT PER 210-8 ALL | | | OUTLETS IN GARAGE NEED TO BE SHOWN AS | | | GFI/GFI PROTECTED. | | | | | | 4)NOTE: PLEASE NOTE MISSING EQUIPMENT | | | GROUND BETWEEN MAIN DISCONNECT AND | | | PANEL PER 250-122 | | | | | | 5)NOTE: PLEASE NOTE THAT BLDG/FOOTER | | | STEEL IS REQ`D PER 250-50. | | | PLEASE SHOW ON RISER. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2002-03-05 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-05 |
Time |
08:51 |
Rev Time |
0.20 |
| Received By |
pkrauss |
Date |
2002-03-05 |
Time |
08:50 |
Sent To |
R |
|
| Notes |
| 2002-03-05 00:00:00 | NO MECHANICAL PLANS SUBMITTED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2002-03-03 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-02-21 |
Time |
16:59 |
Rev Time |
1.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-03 00:00:00 | TWO WAY CO REQ. PES |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
N |
Date |
2002-03-08 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-03-05 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-02-20 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-02-20 |
Time |
12:41 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|