Plan Review Details - Permit 02020701
Plan Review Stops For Permit 02020701
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-04-02 Cont ID  
Sent By jwitmer Date 2002-04-02 Time 15:11 Rev Time 1.00
Received By jwitmer Date   Time   Sent To  
Notes
2002-04-02 00:00:00PLANS TO BE SUBMITTED TO COUNTY FOR
 IMPACT FEE ASSESSMENT BEFORE ISUANCE

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-03-08 Cont ID  
Sent By btrobaug Date 2002-03-29 Time 10:01 Rev Time 1.75
Received By jwitmer Date   Time   Sent To  
Notes
2002-03-08 00:00:00PERMIT # 02020701
 247 SEVILLE ROAD
 O/B WESTERVELT, THEODORE
 HOME: 582-4579
 CELL: (561) 308-6458
  
 1997 STANDARD BUILDING CODE
  
 1)- MISSING PRODUCT APPROVALS (2 COPIES)
 FOR WINDOW AND FOR ROOFING MATERIALS TO
 BE USED, TESTED FOR 110 MPH WIND ZONE.
 2)- PLANS DO NOT INDICATE HOW THE RAFTER
 WILL CANTALEVER FROM THE DOUBLE 2X12 AT
 THE CARPORT. SHEET A-2
 3)- KNEE WALL ATTACHMENT TO BEAM?
 4)- THERE IS AN INDICATION OF A THROUGH
 THE WALL AIR CONDITIONER, PLANS DO NOT
 INDICATE IF THERE IS INSULATION OR A
 CEILING.
 BUILDING PLAN REVIEW
 JIM WITMER
 (561)659-8096 X8412

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2002-05-01 Cont ID  
Sent By btrobaug Date 2002-05-01 Time 13:58 Rev Time 0.00
Received By btrobaug Date 2002-05-01 Time 12:59 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2002-04-16 Cont ID  
Sent By btrobaug Date 2002-04-16 Time 15:44 Rev Time 0.00
Received By btrobaug Date 2002-04-16 Time 13:06 Sent To  
Notes
2002-04-16 00:00:00***************UNSAT!*******************
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} PENCIL IN NOTES ON THE SEALED
 DRAWINGS IS UNACCEPTABLE.
  
 PLEASE CORRECT THESE ITEMS AND RESUBMIT
 FOR REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2002-03-29 Cont ID  
Sent By btrobaug Date 2002-03-29 Time 10:00 Rev Time 0.00
Received By btrobaug Date 2002-03-29 Time 07:33 Sent To B
Notes
2002-03-29 00:00:00**************** UNSAT *****************
  
 1}PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2} WIRE SIZE LISTED FOR THE SERVICE
 FEEDER IS INCORRECT FOR 200 AMPS.
  
 3} PLAN ONLY SHOWS THE PANEL
 LOCATION,PLEASE SHOW METER AND
 DISCONNECT LOCATION ALSO.
  
 PLEASE PROVIDE INFORMATION REQUESTED AND
 RESUMBIT FOR REVIEW.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/659-8096 EXT. 8392

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-21 Cont ID  
Sent By dpalmer Date 2002-02-21 Time 16:17 Rev Time 0.00
Received By dpalmer Date 2002-02-21 Time 16:17 Sent To P
Notes
2002-02-21 00:00:00*************** UNSAT ****************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
  
 2)NOTE: PLEASE NOTE PERMIT APPLICATION
 MENTIONS A NEW UNDERGROUND TO MAIN
 HOUSE BUT NOTHING SHOWN ON ELECTRICAL
 PLANS?? PLEASE CLARIFY GROUPING OF MAINS
 AND NEW? SERVICE FOR MAIN HOUSE.
 SUBMIT ON RISER DIAGRAM.
 PER ZONING REG`S, ONLY ONE METER
 PERMITTED.
  
 3)NOTE: PLEASE NOTE THAT PER 210-8 ALL
 OUTLETS IN GARAGE NEED TO BE SHOWN AS
 GFI/GFI PROTECTED.
  
 4)NOTE: PLEASE NOTE MISSING EQUIPMENT
 GROUND BETWEEN MAIN DISCONNECT AND
 PANEL PER 250-122
  
 5)NOTE: PLEASE NOTE THAT BLDG/FOOTER
 STEEL IS REQ`D PER 250-50.
 PLEASE SHOW ON RISER.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-03-05 Cont ID  
Sent By pkrauss Date 2002-03-05 Time 08:51 Rev Time 0.20
Received By pkrauss Date 2002-03-05 Time 08:50 Sent To R
Notes
2002-03-05 00:00:00NO MECHANICAL PLANS SUBMITTED.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-03-03 Cont ID  
Sent By dpalmer Date 2002-02-21 Time 16:59 Rev Time 1.00
Received By pschmitz Date   Time   Sent To  
Notes
2002-03-03 00:00:00TWO WAY CO REQ. PES

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2002-03-08 Cont ID  
Sent By pkrauss Date 2002-03-05 Time 09:26 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-02-20 Cont ID  
Sent By sgraham Date 2002-02-20 Time 12:41 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***