Plan Review Details - Permit 02020541
Plan Review Stops For Permit 02020541
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-02-13 Cont ID  
Sent By btrobaug Date 2002-02-13 Time 17:53 Rev Time 0.00
Received By btrobaug Date 2002-02-13 Time 17:18 Sent To  
Notes
2002-02-13 00:00:00****************PROVISO!****************
 PLEASE NOTE: THIS SERVICE REQUIRES A #4
 GROUNDING ELECTRODE CONDUCTOR AS PER
 250-66.INSTALL SAME.
 ALSO NOTE TWO GROUND RODS MAY BE
 REQUIRED AS PER250-50(A).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW