Plan Review Details - Permit 02020523
| Plan Review Stops For Permit 02020523 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2002-04-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-02-25 |
Time |
13:02 |
Rev Time |
0.50 |
| Received By |
lsmith |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2002-02-25 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-02-25 |
Time |
13:02 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-02-25 |
Time |
12:49 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2002-04-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-04-11 |
Time |
11:26 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-04-11 |
Time |
11:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2002-03-10 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2002-03-10 |
Time |
12:21 |
Rev Time |
1.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-10 00:00:00 | PLUMBING PLAN REVIEW FBC 2001,DENIED. | | | 3RD TIME PLAN REVIEW FEES DUE. | | | PREVIOUS COMMENTS NOT ADDRESSED. | | | END OF COMMENTSPAUL SCHMITZ |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-03-06 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2002-03-06 |
Time |
17:40 |
Rev Time |
1.50 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-06 00:00:00 | PLUMBING PLAN REVIEW, FBC 2001,DENIED. | | | (1) GENERAL NOTES #1 THE CURRENT CODE IS | | | FBC 2001, SEC 424.2.6 ENGINEERING DESIGN | | | NOT SBCCI-94 PBC SWIMMINGPOOL CODE. | | | (2) NOTE #5 DISPOSAL OF WATER. SEE FBC | | | 2001, SEC 424.2.10 WASTE WATER DISPOSAL. | | | (3) NOTE #7 WATER SUPPLY. SEE FBC 2001 | | | SEC 424.2.9 WATER SUPPLY, AND LOCAL ORD. | | | #2853-95 BACK FLOW PREVENTER REQUIRED | | | ON WATER SERVICE. | | | (4) SEC 424.2.13.2 JOINTS, CONNECTIONS. | | | PURPLE PRIMER REQUIRED ON PVC PIPING, | | | FBC 2001 PLUMBING SEC 605.21 | | | (5A) COMPLY WITH FBC 2001,SEC 104.2 | | | BUILDING DRAWINGS, SPECIFICATIONS. | | | TO MANY SWIMMING POOL PIPING SCHEMATICS, | | | ON THE PLANS, THIS IS VERY CONFUSING, | | | SHOW INDIVIDUAL PIPING SCHEMATIC FOR EA. | | | SWIMMING POOL,SPA. SHOW PIPING FOR THE | | | ENTIRE SYSTEM, PIPE SIZES,VENTS, SUCTION | | | AND DISCHARGE PIPING,ECT. | | | (5B) PROVIDE A COPY OF CONTRACT,MATERIAL | | | FURNISHED IS VAGUE,IN WHAT IS INCLUDED | | | FOR THIS JOB. | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-02-24 |
|
|
Cont ID |
|
| Sent By |
pschmitz |
Date |
2002-02-24 |
Time |
14:26 |
Rev Time |
2.00 |
| Received By |
pschmitz |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-02-24 00:00:00 | PLUMBING PLAN REVIEW,DENIED,FBC 2001 | | | SEE ATTACHED COPY OF FBC 2001, PLEASE | | | RESPOND TO EACH CIRCLED COMMENT. | | | END OF COMMENTSPAUL SCHMITZ | | | QUESTIONS561-659-8096X8233 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-02-13 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-02-13 |
Time |
13:28 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
|