| 2002-03-11 00:00:00 | BUILDING PLAN REVIEW |
| | 221 WALTON BLVD |
| | PERMIT # 02020510 |
| | |
| | ****PLANS TO INDICATE ASTO WHICH CODE |
| | THEY ARE TO BE REVIEWED BY: |
| | 1997 STANDARD BUILDING CODEOR |
| | 2001 FLORIDA BUILDING CODE |
| | PLANS SUBMITTED FOR PERMIT IN JAN. & FEB |
| | OF 2002 MAY BE DESIGNED UNDER EITHER |
| | CODE. INDICATE WHICH CODE WAS USED. |
| | |
| | THE PLANS ARE TO INDICATE PRODUCT TEST- |
| | ING ACCEPTANCE REPORT (2 COPIES) EITHER |
| | SBCCI OR DADE COUNTY REPORTS ARE ACCEPTT |
| | ED. |
| | |
| | UNDER THE 1997 SBC TABLE 1606 USE FACTOR |
| | THE USE FACTOR IS .90 X 110 MPH= 99 MPH. |
| | THE ACTUAL STORAGE SHED ACTUALLY NEEDS |
| | TO SHOW CODE COMPLIANCE OF 99 MILE PER |
| | HOUR SINCE THERE IS LOW HAZARD TO HUMAN |
| | LIFE( STORAGE SHED). |
| | |
| | THE OTHER ISSUE IS TO SHOW REISTANCE OF |
| | MOMENT OF OVERTURNING THROUGH A MAIN |
| | WIND FORCR RESISTING SYSTEM (SBC 1606.2. |
| | 6.1) THE PRODUCT TESTING REPORT SHOULD |
| | INDICATE HOW THE STRUCTURE IS TO BE |
| | SECURED AND TRANSMITTED THROUGH TO THE |
| | FOUNDATION? |
| | |
| | ****HISTORICAL DISTRICT******** |
| | PLANS ARE ALSO REQUIRED TO BE SUBMITTED |
| | TO THE HISTORICAL PRESERVATION BOARD |
| | FOR APPROVAL, APPLICATION AND APPROVAL |
| | ARE REQUIRED FROM HISTORICS BEFORE |
| | PERMIT RESUBMITTAL TO THE BUILDING |
| | DEPARTMENT. FOR MORE INFO TELE: |
| | SHERRY PILAND 659-8031 X 8362 |
| | EMILY STEVENS 659-8031 X 8306 |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | (561)659-8096 X 8412 |