Plan Review Details - Permit 02020452
Plan Review Stops For Permit 02020452
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-03-19 Cont ID  
Sent By rbrown Date 2002-03-19 Time 14:24 Rev Time 0.00
Received By rbrown Date 2002-03-19 Time 14:24 Sent To  
Notes
2002-03-19 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 659 8096 EXT 8499
  
 SBC = STANDARD BUILDING CODE 1997
 SBC*= STANDARD BUILD'G CODE (CITY
 AMEND)FL ENERGY CODE = FLORIDA ENERGY
 EFFICIENCY CODE FOR BUILD'G CONSTR'N
  
 1) UNTIL MARCH 1, 2002 EITHER STANDARD
 BUILDING CODE 1997 OR FLORIDA BUILDING
 CODE 2001 MAY BE USED.NEITHER CODE IS
 REFERENCED ON THE PLANS.STATE ON THE
 PLANS WHICH CODE IS TO BE USED.
  
 2) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 4) FL ENERGY CODE 101.1.2 AND 103.0
 THE ADDITION SHALL COMPLY WITH FLORIDA
 ENERGY CODE.SUBMIT ENERGY CODE
 COMPLIANCE FORMS TO DEMONSTRATE
 COMPLIANCE.
  
 5) SBC 1501INSUFFICIENT ROOF COVERING
 INFORMATION WAS SUBMITTED AT THE TIME OF
 APPLICATION.A SEPARATE ROOFING PERMIT
 APPLICATION IS REQUIRED.
  
 6) SBC* 1606.4THE SUBMITTED PRODUCT
 CONTROL NOTICES OF ACCEPTANCE FOR THE
 WINDOW AND GLASS SLIDING DOOR ARE
 EXPIRED AND THE ASSOCIATED DRAWINGS FOR
 THE GLASS SLIDING DOOR ARE MISSING.
 SUBMIT CURRENT AND COMPLETE PRODUCT
 APPROVALS.
  
 7) SBC 2308PROVIDE DETAILS OF THE
 MEANS OF ATTACHMENT OF THE NEW WALLS TO
 THE EXISTING BUILDING.ALSO, THE
 PLYWOOD SHEATHING ON THE ADDITION SHALL
 BE MIN. 5/8" THICK (SEE
 SBC TABLE 2308.2.2B)
  
 8) SBC 1804.1THE BASE OF THE FOOTERS
 SHALL BE MIN. 12" BELOW FINISHED GRADE.
 ANNOTATE THE PLANS TO SHOW COMPLIANCE.
  
 9) SBC 2303.1THE GROUND AROUND THE
 BUILDING SHALL BE GRADED TO SLOPE AWAY
 FROM IT.ANNOTATE THE PLANS TO SHOW
 COMPLIANCE.
  
 10) SBC 1909.1WHAT IS THE THICKNESS OF
 THE FLOOR SLAB?ALSO, THE PROPOSED
 RECESS IN THE TOP OF THE SLAB TO
 ACCOMMODATE THE WALL SOLE PLATE IS NOT
 NECESSARY.IT WILL REDUCE THE CONCRETE
 COVER TO THE REINFORCEMENT AND IS NOT
 RECOMMENDED.
  
 11) SBC 1909.2A VAPOR RETARDER OF 6MIL
 (MINIMUM) POLYTHENE OR OTHER APPROVED
 MATERIAL SHALL BE INSTALLED UNDERNEATH
 THE SLAB.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 12) SBC* 2304.1.2TERMITE TREATMENT OF
 SOIL UNDER AND AROUND THE SLAB AND
 FOOTINGS IS REQUIRED.ANNOTATE THE
 PLANS TO DEMONSTRATE COMPLIANCE.
  
 13) SBC* 2304.2.5LATH AND STUCCO.
 ANNOTATE THE PLANS TO SHOW AN APPROVED
 WEEP SCREED (STUCCO STOP) PLACED NOT
 LESS THAN 6" ABOVE FINISHED GRADE TO
 TERMINATE THE STUCCO AT THE BASE OF THE
 WALL.
  
 14) ANNOTATE THE PLANS TO SHOW THE SIZE
 OF THE J-BOLT BETWEEN THE WALL SOLE
 PLATE AND FOOTINGS.
  
 15) ANNOTATE THE PLANS TO SHOW THAT ALL
 FRAMING AND SHEATHING IS THE BE
 PRESERVATIVE TREATED WOOD.
  
 16) SBC 2308.3.2 THE WINDOW AND DOOR
 HEADERS SHALL BE SUPPORTED BY A JACK
 STUD AT EACH END IN ACCORDANCE WITH
 TABLE 2308.3A.ANNOTATE THE PLANS TO
 DEMONSTRATE COMPLIANCE.
  
 17) SBC 1606.1.1WIND FORCES.CONFIRM
 THE BASIS OF DESIGN FOR RESISTANCE TO
 WIND LOAD AND STATE THE BASIC VELOCITY
 PRESSURE.
  
 18) SBC 1503.1.2.3WALL SECTION.IF
 THE ROOF COVERING IS NOT OF A TYPE
 RECOGNIZED AS 'WATER RETAINING', THE
 MINIMUM SLOPE OF 1/4 INCH/FT (INCREASED
 AS NECESSARY TO ACCOUNT FOR DEFLECTION)
 AND THE DIRECTION OF SLOPE SHALL BE
 SHOWN.
  
 19) SBC 2309.7.2THE FLAT ROOF VOID
 SHALL BE VENTILATED BY A NETT AREA OF
 OPENING NOT LESS THAN 1/250 OF THE AREA
 OF THE CEILING BELOW.ANNOTATE THE
 PLANS TO DEMONSTRATE COMPLIANCE.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 IF YOU HAVE ANY QUERIES PLEASE CALL:
 ROBERT BROWN(561) 659 8096 EXT 8499

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-12 Cont ID  
Sent By dpalmer Date 2002-02-12 Time 07:46 Rev Time 0.00
Received By dpalmer Date 2002-02-12 Time 07:45 Sent To  
Notes
2002-02-12 00:00:00****************** UNSAT *************
  
 1)NOTE:PLEASE NOTE THAT TWO SETS NEED
 TO BE SUBMITTED FOR REVIEW. ONE SET WILL
 GO OUT FOR JOBSITE COPY AND ONE IS FOR
 RECORD.
  
 2)NOTE: PLEASE CLARFIY IF THIS ROOM IS
 GOING TO BE A BEDROOM?
  
 PLANS ARE COMING BACK FOR BLDG PLAN
 REVIEW COMMENTS. PLEASE SUBMIT THE
 ABOVE INFORMATION FOR REVIEW. IF THERE
 ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-03-19 Cont ID  
Sent By rbrown Date 2002-03-19 Time 16:56 Rev Time 0.00
Received By rbrown Date   Time   Sent To  
Notes
2002-03-19 00:00:00NO MECHANICAL PLANS SUBMITTED.SUBMIT
 PLANS WITH THE MECHANICAL PERMIT
 APPLICATION.

Review Stop P PLUMBING
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2002-02-08 Cont ID  
Sent By sgraham Date 2002-02-08 Time 14:46 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***