Plan Review Details - Permit 02020391
Plan Review Stops For Permit 02020391
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-02-21 Cont ID  
Sent By sjohnson Date 2002-02-21 Time 13:51 Rev Time 0.00
Received By sjohnson Date   Time   Sent To  
Notes
2002-02-21 00:00:00APPROVED PER DEWEY PALMER

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-11 Cont ID  
Sent By btrobaug Date 2002-02-11 Time 08:48 Rev Time 0.00
Received By btrobaug Date 2002-02-11 Time 08:40 Sent To  
Notes
2002-02-11 00:00:00********************UNSAT!**************
 PLEASE PROVIDE THE FOLLOWING AND
 RESUBMIT:
  
 1) A.I.C. RATING AT FIST MEANS OF
 DISCONNECT,AS PER 110-9 & 110-10.
  
 2) LOAD CALCULATIONS AS PER 215-5.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561) 659-8096 EXT.8392