| Plan Review Stops For Permit 02020391 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-02-21 |
|
|
Cont ID |
|
| Sent By |
sjohnson |
Date |
2002-02-21 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
sjohnson |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-02-21 00:00:00 | APPROVED PER DEWEY PALMER |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-02-11 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2002-02-11 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2002-02-11 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2002-02-11 00:00:00 | ********************UNSAT!************** | | | PLEASE PROVIDE THE FOLLOWING AND | | | RESUBMIT: | | | | | | 1) A.I.C. RATING AT FIST MEANS OF | | | DISCONNECT,AS PER 110-9 & 110-10. | | | | | | 2) LOAD CALCULATIONS AS PER 215-5. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561) 659-8096 EXT.8392 |
|
|
|