| Plan Review Stops For Permit 02020240 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2002-04-30 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-04-30 |
Time |
11:22 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2002-03-04 |
|
|
Cont ID |
|
| Sent By |
hpiskura |
Date |
2002-03-04 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
hpiskura |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
| 2002-03-04 00:00:00 | PROVISO:METRO DADE NOA 98-0130.02 AND | | | 97-0417.01 ARE BOTH EXPIRED.PROVIDE | | | CURRENT REPORTS OR TESTS FOR THE | | | HURRICANE SHUTTER SYSTEM BEFORE | | | INSTALLATION. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2002-04-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-04-30 |
Time |
06:32 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-04-30 |
Time |
06:32 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2002-02-27 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2002-02-27 |
Time |
14:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2002-02-27 |
Time |
14:27 |
Sent To |
|
|
| Notes |
| 2002-02-27 00:00:00 | ********** NOTE **************** | | | | | | 1)NOTE: PLESE NOTE THAT FRONT COVER | | | SHEET MENTIONS "96" NEC AND WE ARE | | | UNDER THE "99" NEC. PLEASE NOTE THAT | | | PLANS ARE COMING BACK FOR OTHER COMMENTS | | | AND COVER SHEET CAN BE CORRECTED. | | | | | | PLEASE REVISE AND SUBMIT THE ABOVE | | | INFORMATION FOR REVIEW. IF THERE ARE | | | ANY QUESTIONS, PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | 561-659-8096 EXT 8372 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
N |
Date |
2002-06-28 |
|
|
Cont ID |
|
| Sent By |
mamini |
Date |
2002-06-21 |
Time |
13:56 |
Rev Time |
0.00 |
| Received By |
mamini |
Date |
2002-06-28 |
Time |
13:19 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2002-05-22 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-05-22 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-05-22 |
Time |
10:23 |
Sent To |
|
|
| Notes |
| 2002-05-22 00:00:00 | PLAN WAS APPROVED ON 5.7.02. NOTE WAS | | | NOT PUT INTO COMPUTER. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096, EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2002-02-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2002-02-20 |
Time |
13:14 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2002-02-20 |
Time |
13:14 |
Sent To |
|
|
| Notes |
| 2002-02-20 00:00:00 | A) BUILDING ADDRESSES REQUIRED. | | | B) DOORS 2-191 AND 3-192 OPEN INTO THE | | | CORRIDORS. | | | C) PLEASE PROVIDE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 659-8096,EXT.8497 | | | 835-2910 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2002-05-02 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-05-02 |
Time |
15:58 |
Rev Time |
0.45 |
| Received By |
pkrauss |
Date |
2002-05-02 |
Time |
15:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2002-02-26 |
|
|
Cont ID |
|
| Sent By |
pkrauss |
Date |
2002-02-26 |
Time |
10:15 |
Rev Time |
1.00 |
| Received By |
pkrauss |
Date |
2002-02-26 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2002-02-26 00:00:00 | | | | INDICATE HOW AIR IS TO BE TRANFERRED | | | FROM OFFICE AREAS WITH CFM GREATER THAN | | | 300.SHOW COMPLIANCE WITH 1997 SMC | | | 501.2. | | | | | | DUCT SMOKE DETECTORS REQUIRED FOR UNITS | | | LESS THAN 2,000 CFM THAT ARE SERVING AN | | | AREA USED FOR EGRESS. 1997 SMC 406.2. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT 659-8096 | | | EXT. 8388. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2002-06-19 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-06-19 |
Time |
19:27 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-06-19 |
Time |
19:27 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2002-05-11 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-05-11 |
Time |
09:22 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2002-05-11 |
Time |
09:18 |
Sent To |
|
|
| Notes |
| 2002-05-11 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) FROM PREVIOUS REVIEW - PER TABLE 407 | | | DRINKING FOUNTAINS ARE REQUIRED. WATER | | | COOLERS ARE NOT AN ACCEPTABLE SUBSTITUTE | | | FOR DRINKING FOUNTAINS. THEY ARE NOT A | | | FIXTURE AND D.F FIXTURES ARE REQUIRED. | | | 2) DRINKING FOUNTAINS SHALL BE AT HDCP | | | HEIGHT (36" TO SPOUT) AND HAVE CLEAR | | | FLOOR SPACE. PROVISIONS FOR THOSE WHO | | | HAVE DIFFICULTY BENDING OR STOOPING. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2002-02-25 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2002-02-25 |
Time |
14:04 |
Rev Time |
1.25 |
| Received By |
kstevens |
Date |
2002-02-25 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2002-02-25 00:00:00 | DENIED | | | REFERENCE: SPC-94-FACBC-97 | | | | | | 1) SHTS A1-1/A7-1 DETAIL #3 SINK TO COM- | | | PLY WITH FACBC SEC 4.24. SHOW DETAILS. | | | 2) SHT A1-1 MINIMUM FACILITIES REQUIRE | | | 2 MALE AND 2 FEMALE WATER CLOSETS AND | | | LAVS. BLDG "A" SPC TABLE 407 | | | 3) SHT A1-1 MINIMUM FACILITIES REQUIRE | | | 1 MALE AND 2 FEMALE WATER CLOSETS AND | | | LAVS. BLDG "B" SPC TABLE 407 | | | 4) SHT A1-1 MINIMUM FACILITIES REQUIRE | | | ONE DRINKING FOUNTAIN. IF DRINKING FOUN- | | | TAINS ARE NOT HI/LOW THEN PROVISIONS | | | SHALL BE MADE FOR THOSE WHO HAVE DIFFI- | | | CULTY BENDING OR STOOPING. FACBC SEC | | | 4.1.3(10) | | | 5) SHTS A1-1/A7-1 DETAIL #8 SINK TO COM- | | | PLY WITH FACBC SEC 4.24 SHOW DETAILS. | | | 6) SHTS A1-1/A7-2 DETAIL #17 SINK TO | | | COMPLY WITH FACBC SEC 4.24. SHOW DETAILS | | | 7) SHT P-4 WATER HEATER DETAIL, DIELECT- | | | RIC UNIONS NOT APPROVED FOR USE IN WATER | | | SYSTEM. THESE ARE GAS FITTINGS. | | | | | | REVIEW BY KEN STEVENS | | | (561) 659-8096 EXT 8377 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2002-02-15 |
|
|
Cont ID |
|
| Sent By |
sgraham |
Date |
2002-02-15 |
Time |
14:28 |
Rev Time |
0.25 |
| Received By |
sgraham |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|