Plan Review Details - Permit 02020240
Plan Review Stops For Permit 02020240
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-04-30 Cont ID  
Sent By hpiskura Date 2002-04-30 Time 11:22 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2002-03-04 Cont ID  
Sent By hpiskura Date 2002-03-04 Time 11:38 Rev Time 0.00
Received By hpiskura Date   Time   Sent To  
Notes
2002-03-04 00:00:00PROVISO:METRO DADE NOA 98-0130.02 AND
 97-0417.01 ARE BOTH EXPIRED.PROVIDE
 CURRENT REPORTS OR TESTS FOR THE
 HURRICANE SHUTTER SYSTEM BEFORE
 INSTALLATION.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-04-30 Cont ID  
Sent By dpalmer Date 2002-04-30 Time 06:32 Rev Time 0.00
Received By dpalmer Date 2002-04-30 Time 06:32 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-27 Cont ID  
Sent By dpalmer Date 2002-02-27 Time 14:27 Rev Time 0.00
Received By dpalmer Date 2002-02-27 Time 14:27 Sent To  
Notes
2002-02-27 00:00:00********** NOTE ****************
  
 1)NOTE: PLESE NOTE THAT FRONT COVER
 SHEET MENTIONS "96" NEC AND WE ARE
 UNDER THE "99" NEC. PLEASE NOTE THAT
 PLANS ARE COMING BACK FOR OTHER COMMENTS
 AND COVER SHEET CAN BE CORRECTED.
  
 PLEASE REVISE AND SUBMIT THE ABOVE
 INFORMATION FOR REVIEW. IF THERE ARE
 ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2002-06-28 Cont ID  
Sent By mamini Date 2002-06-21 Time 13:56 Rev Time 0.00
Received By mamini Date 2002-06-28 Time 13:19 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2002-05-22 Cont ID  
Sent By mcarsill Date 2002-05-22 Time 10:23 Rev Time 0.00
Received By mcarsill Date 2002-05-22 Time 10:23 Sent To  
Notes
2002-05-22 00:00:00PLAN WAS APPROVED ON 5.7.02. NOTE WAS
 NOT PUT INTO COMPUTER.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096, EXT.8497
 835-2910

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2002-02-20 Cont ID  
Sent By mcarsill Date 2002-02-20 Time 13:14 Rev Time 0.00
Received By mcarsill Date 2002-02-20 Time 13:14 Sent To  
Notes
2002-02-20 00:00:00A) BUILDING ADDRESSES REQUIRED.
 B) DOORS 2-191 AND 3-192 OPEN INTO THE
 CORRIDORS.
 C) PLEASE PROVIDE INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILINGS.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 659-8096,EXT.8497
 835-2910

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-05-02 Cont ID  
Sent By pkrauss Date 2002-05-02 Time 15:58 Rev Time 0.45
Received By pkrauss Date 2002-05-02 Time 15:26 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-02-26 Cont ID  
Sent By pkrauss Date 2002-02-26 Time 10:15 Rev Time 1.00
Received By pkrauss Date 2002-02-26 Time 10:15 Sent To  
Notes
2002-02-26 00:00:00 
 INDICATE HOW AIR IS TO BE TRANFERRED
 FROM OFFICE AREAS WITH CFM GREATER THAN
 300.SHOW COMPLIANCE WITH 1997 SMC
 501.2.
  
 DUCT SMOKE DETECTORS REQUIRED FOR UNITS
 LESS THAN 2,000 CFM THAT ARE SERVING AN
 AREA USED FOR EGRESS. 1997 SMC 406.2.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 3 Status P Date 2002-06-19 Cont ID  
Sent By kstevens Date 2002-06-19 Time 19:27 Rev Time 0.00
Received By kstevens Date 2002-06-19 Time 19:27 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-05-11 Cont ID  
Sent By kstevens Date 2002-05-11 Time 09:22 Rev Time 0.00
Received By kstevens Date 2002-05-11 Time 09:18 Sent To  
Notes
2002-05-11 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) FROM PREVIOUS REVIEW - PER TABLE 407
 DRINKING FOUNTAINS ARE REQUIRED. WATER
 COOLERS ARE NOT AN ACCEPTABLE SUBSTITUTE
 FOR DRINKING FOUNTAINS. THEY ARE NOT A
 FIXTURE AND D.F FIXTURES ARE REQUIRED.
 2) DRINKING FOUNTAINS SHALL BE AT HDCP
 HEIGHT (36" TO SPOUT) AND HAVE CLEAR
 FLOOR SPACE. PROVISIONS FOR THOSE WHO
 HAVE DIFFICULTY BENDING OR STOOPING.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-02-25 Cont ID  
Sent By kstevens Date 2002-02-25 Time 14:04 Rev Time 1.25
Received By kstevens Date 2002-02-25 Time 14:04 Sent To  
Notes
2002-02-25 00:00:00DENIED
 REFERENCE: SPC-94-FACBC-97
  
 1) SHTS A1-1/A7-1 DETAIL #3 SINK TO COM-
 PLY WITH FACBC SEC 4.24. SHOW DETAILS.
 2) SHT A1-1 MINIMUM FACILITIES REQUIRE
 2 MALE AND 2 FEMALE WATER CLOSETS AND
 LAVS. BLDG "A" SPC TABLE 407
 3) SHT A1-1 MINIMUM FACILITIES REQUIRE
 1 MALE AND 2 FEMALE WATER CLOSETS AND
 LAVS. BLDG "B" SPC TABLE 407
 4) SHT A1-1 MINIMUM FACILITIES REQUIRE
 ONE DRINKING FOUNTAIN. IF DRINKING FOUN-
 TAINS ARE NOT HI/LOW THEN PROVISIONS
 SHALL BE MADE FOR THOSE WHO HAVE DIFFI-
 CULTY BENDING OR STOOPING. FACBC SEC
 4.1.3(10)
 5) SHTS A1-1/A7-1 DETAIL #8 SINK TO COM-
 PLY WITH FACBC SEC 4.24 SHOW DETAILS.
 6) SHTS A1-1/A7-2 DETAIL #17 SINK TO
 COMPLY WITH FACBC SEC 4.24. SHOW DETAILS
 7) SHT P-4 WATER HEATER DETAIL, DIELECT-
 RIC UNIONS NOT APPROVED FOR USE IN WATER
 SYSTEM. THESE ARE GAS FITTINGS.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop Z ZONING
Rev No 1 Status P Date 2002-02-15 Cont ID  
Sent By sgraham Date 2002-02-15 Time 14:28 Rev Time 0.25
Received By sgraham Date   Time   Sent To  
Notes
***NONE***