Plan Review Details - Permit 02020158
Plan Review Stops For Permit 02020158
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-26 Cont ID  
Sent By jgomez Date 2002-02-26 Time 19:47 Rev Time 3.00
Received By jgomez Date 2002-02-26 Time 19:47 Sent To  
Notes
2002-02-26 00:00:00CHECKLIST:
 1-NEED RECORDED NOTICE OF COMMENCEMENT.
 2-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING STAMPED DRAWINGS & PAID RECEIPT.
 3-HOUSE IS LOCATED ON FLOOD ZONE A5.
 CHAPTER 12 OF CITY CODE REQUIRES MIN.
 FLOOR ELEVATION TO BE AT 7'-6".
 PROVIDE SURVEY INDICATING ACTUAL FLOOR
 ELEVATION AND PROPOSED FLOOR ELEVATION
 4-CLEARLY SPECIFY ON PLANS NAMES OF NEW
 ROOMS AND NAMES OF EXISTING ADJACENT
 ROOMS TO VERIFY FOR EGRESS REQUIREMENT
 5-A)SPECIFY ALL WINDOW TYPES AND SIZES.
 MISSING INFORMATION ON NORTH AND SOUTH
 ELEVATIONS. CHECK FOR EGRESS REQMTS.
 B)WINDOWS SPECIFIED ON FLOOR PLAN DON'T
 MATCH WINDOWS SHOWN ON EXTERIOR
 ELEVATIONS. REVISE AS REQUIRED.
  
 6-PROVIDE PRODUCT APPROVAL AND COMPLETE
 INSTALLATION SCHEDULE AND KEY PLAN
 FOR STORM SHUTTERS. SEE CITY SAMPLE.
 7-SPECIFY FIREBLOCKING AT WALL SECTION.
 SEE PLANS AND SEC. 2305 SBC 1997.
 8-SPECIFY VENTILATION SIZE & SPACING TO
 COMPLY WITH SEC. 2309.7 SBC 1997.
 9-PROVIDE SOIL TEST REPORT WITH THE MIN.
 INFO. REQUIRED ON SEC. 1804.2.7 OF
 CITY AMENDMENTS TO SBC 1997.
 10-SPECIFY ON DRAWINGS THE DESIGN
 PRESSURES CALCULATED AT ALL EXTERIOR
 OPENINGS. SEC. 1606 SBC 1997.
 11-PROVIDE ATTIC ACCESS AT NEW ROOF
 SEC. 2309.6 SBC 1997.
 12-SPECIFY ON PLANS MINIMUM INSULATION
 REQUIRED AT ROOF AND WALL. SEE ENERGY
 CALCS. WHERE'S R16 IN ROOF TAKEN FROM?
 13-CLARIFY FOOTING TYPE. FOUNDATION PLAN
 AND WALL SECTION DON'T MATCH.
 14-PROVIDE COMPLETE SPECS FOR ANCHOR
 BOLTS USED WITH SIMPSOM HD2A. SPECIFY
 ANCHOR TYPE & MIN. EMBEDMENT AS REQ'D
 BY SIMPSOM COMPANY.
 -REVISE ANCHOR TYPE ON WALL SECTION AND
 ROOF FRAMING PLAN TO MATCH.
 SECTION 104.2.2 CITY AMENDMENTS TO SBC
 15-SPECIFY LINTELS ON PLANS. SECTION
 104.2.2 CITY AMENDMENTS TO SBC 1997.
 16-PROVIDE PRODUCT APPROVAL FOR:
 A)SINGLE HUNG WINDOWS (DRAWINGS ARE NOT
 LEGIBLE).
 B)HORIZONTAL ROLLER WINDOWS.
 17-SEE PLANS FOR ADDITIONAL COMMENTS.
 INCLUDING COMMENTS BY THE OTHER TRADES
 18-OWES $290.29 FOR UPDATED VALUATION &
 RADON FEES. PLEASE PAY RECEIPT AND
 BRING BACK PAID RECEIPT.
 19-CLARIFY WHO'S THE OWNER DONADONI OR
 WAGNER. BRING PROOF OF OWNERSHIP.
 20-PROVIDE STRUCTURAL BUCK DETAILS FOR
 EXTERIOR DOORS AND WINDOWS.
 SEE PRODUCT APPROVALS FOR RQUIRED BUCK
 SEC. 104.2.2 CITY AMENDMENTS TO SBC/97
 21-INFORMATION GIVEN IN THE DESIGN
 CERTIFICATION FOR BUILDING CODE
 COMPLIANCE FORM TO BE INCLUDED IN THE
 PLANS NOT ON SEPARATE FORMS. REQUESTED
 BY BUILDING OFFICIAL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-11 Cont ID  
Sent By dpalmer Date 2002-02-11 Time 14:04 Rev Time 0.00
Received By dpalmer Date 2002-02-11 Time 14:04 Sent To P
Notes
2002-02-11 00:00:00***************** UNSAT ***************
  
 1)NOTE: PLEASE NOTE MISSING EGRESS
 LIGHTING PER 210-70. NO CONTROL FOR
 CEILING FAN?
  
 2) NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ALSO ON EACH LEVEL OF A MULTI-LEVEL
 DWELLING UNIT. ROOMS WITH BATHS AND OR
 CLOSETS ARE CONSIDERED SLEEPING ROOMS.
 PER NFPA-72 2-2.1.1.1.
  
 3) NOTE: PLEASE SHOW ALL OUTLET SPACING
 TO MEET 2`,6`,12` RULE PER 210-52.
  
  
 4) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 5)NOTE: PLEASE NOTE THAT BATH REC NEEDS
 TO BE SHOWN AS GFI.210-8
  
 PLEASE MAKE THE ABOVE CHANGES AND SUBMIT
 FOR REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2002-02-21 Cont ID  
Sent By pkrauss Date 2002-02-21 Time 12:01 Rev Time 0.30
Received By pkrauss Date   Time   Sent To  
Notes
2002-02-21 00:00:00 
 NO INDICATION OF THE CODE PLANS WHERE
 DESIGNED TO.PLANS REVIEWED UNDER THE
 1997 SMC.
  
 PROVIDE INFORMATION ON EXISTING
 EQUIPMENT - MANUFACTURER, MODEL,
 (TONNAGE).
  
 INDICATE SIZE & MATERIAL OF NEW
 DUCTWORK.
  
 INDICATE SQUARE FOOTAGE OF EXISTING
 HOUSE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-02-20 Cont ID  
Sent By dpalmer Date 2002-02-11 Time 14:05 Rev Time 0.33
Received By kstevens Date 2002-02-20 Time 13:57 Sent To  
Notes
2002-02-20 00:00:00REVIEWED UNDER SPC-94 CODE SINCE NO CODE
 WAS REFERENCED ON PLANS.

Review Stop Z ZONING
Rev No 1 Status P Date 2002-02-06 Cont ID  
Sent By sgraham Date 2002-02-06 Time 12:49 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***