Plan Review Details - Permit 02020153
Plan Review Stops For Permit 02020153
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-05-15 Cont ID  
Sent By lsmith Date 2002-05-15 Time 14:54 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-27 Cont ID  
Sent By kstevens Date 2002-05-06 Time 11:49 Rev Time 0.75
Received By lsmith Date   Time   Sent To  
Notes
2002-02-27 00:00:00*************BUILDING UNSAT*************
  
 FBC 2001
  
  
 ALL POOL PERMITS MUST COMPLY WITH THE
 FBC 2001 APPLIED FOR AS OF 1/1/2002.
  
 FLORIDA STATE STATUTES DEALING WITH
 SAFETY HAVE BEEN REPLACED WITH THE FBC
 CHAPTER 424.
  
 HAVE ENGINEER OF RECORD CORRECT DRAWINGS
 AND RESUBMITSHOWING COMPLIANCE PER ABO
 VE.
  
 ANY QUESTIONS PLEASE CALL:
 LEA SMITH, BUILDING PLANS EXAMINER
 659-8096 EXT. 8394

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-02-07 Cont ID  
Sent By btrobaug Date 2002-02-07 Time 18:05 Rev Time 0.00
Received By btrobaug Date 2002-02-07 Time 18:03 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 4 Status P Date 2002-05-06 Cont ID  
Sent By kstevens Date 2002-05-06 Time 11:48 Rev Time 0.00
Received By kstevens Date 2002-05-06 Time 11:48 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status F Date 2002-04-23 Cont ID  
Sent By kstevens Date 2002-04-23 Time 16:41 Rev Time 0.00
Received By kstevens Date 2002-04-23 Time 16:41 Sent To B
Notes
2002-04-23 00:00:00DENIED
 REFERENCE: FBC-2001 424.2 SWIMMING POOLS
  
 1) ADJUST YOUR PLANS, NOTES, DETAILS, &
 SUBMITTALS TO REFLECT THE FOLLOWING IN-
 FORMATION REQUIRED FOR POOL PLUMBING
 PERMITS.
 A)
 COMPLY WITH FBC-2001 SEC 424.2
 PRIVATE SWIMMING POOLS.
 B)
 FBC-2001 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-4 92.
 C)
 FBC-2001 SEC 424.2.6.6.5 WHERE PROVIDED,
 THE VACUUM OR PRESSURE CLEANER FITTING
 SHALL BE LOCATED AT LEAST 6" AND NOT
 GREATER THAN 12" BELOW THE MINIMUM OPER-
 ATING WATER LEVEL OR AS AN ATTACHMENT TO
 THE SKIMMER.
 D)
 FBC-2001 SEC 424.2.7.2 PUMPS AND EQUIP-
 MENT SHALL BE MOUNTED ON A SUBSTANTIAL
 BASE IN A MANNER THAT WILL ELIMINATE
 STRAIN ON PIPING. SLAB SHALL BE A NOMIN-
 AL 4" THICK. (DETAIL)
 E)
 FBC-2001 SEC 424.2.9 WATER SUPPLY, LOCAL
 ORD. #2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 F)
 FBC-2001 SEC 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 G)
 FBC-2001 SEC 424.2.13.2JOINTS AND CON-
 NECTIONS, FBC PLMG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 2) FOR FUTURE REFERENCE: WHEN A POOL
 HEATER IS INSTALLED, THE FOLLOWING NOTES
 DETAILS, SUBMITTALS SHALL BE REQUIRED.
 H)
 FBC-2001 SEC 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (SUBMITTAL)
 I)
 FBC-2001 SEC 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF. (MANUFACTURE CUT SHEETS SUBMITTAL)
 J)
 FBC-2001 SEC 424.2.14.4 CONNECTIONS, ALL
 WATER HEATING EQUIPMENT SHALL BE INSTAL-
 LED WITH FLANGES OR UNION CONNECTIONS
 ADJACENT TO THE HEATER. (ADD TO NOTES)
 K)
 FBC-2001 SEC 424.2.15 GAS PIPING SHALL
 COMPLY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED.
 3) SECOND SHEET WITH NOTES AND DETAILS
 ARE VERY UNCLEAR AND HARD TO READ.
 PLEASE SUBMIT SHEET THAT HAS LARGER
 LETTERS AND IS READABLE.
  
 REVIEW BY KEN STEVENS
 (561) 659-8096 EXT 8377

Review Stop P PLUMBING
Rev No 2 Status F Date 2002-03-10 Cont ID  
Sent By pschmitz Date 2002-03-10 Time 13:16 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2002-03-10 00:00:00PLUMBING PLAN REVIEW, FBC 2001, DENIED.
 "PREVIOUS NOTES NOT ADDRESSED"
 01) GENERAL NOTES #1,THE CURRENT CODE IS
 FBC 2001 SEC 424.2 PRIVATE SWIMMING POOL
 AND SPA
 (2) SEC 424.2.6 ENGINEERING DESIGN.
 PROVIDE A COPY OF CONTRACT.
 (3) ADDRESS EACH SECTION 424.2 THRU
 424.2.23ENGINEERING DESIGN.
 (3) ENGINEER OF RECORD MR.N.KHANAL,P.E.
 IS IN VIOLATION OF 553.80(2)(B) REPETIVE
 REJECTION OF SWIMMING POOL AND SPA PLANS
 IS SUBJECT TO FOUR TIMES THE PERMIT FEE
 ATTRIBUTED TO PLAN REVIEW.
 END OF COMMENTS PAUL SCHMITZ
 QUESTIONS 561-659-8096X8233

Review Stop P PLUMBING
Rev No 1 Status F Date 2002-02-10 Cont ID  
Sent By btrobaug Date 2002-02-07 Time 18:05 Rev Time 1.50
Received By pschmitz Date   Time   Sent To  
Notes
2002-02-10 00:00:00PLUMBING PLAN REVIEWDENIED.
 COMPLY WITH FBC 2001 SEC 424.2
 SEE ATTACHED. PAUL SCHMITZ 561-659-8096
 X8233

Review Stop Z ZONING
Rev No 1 Status P Date 2002-02-07 Cont ID  
Sent By sgraham Date 2002-02-07 Time 11:05 Rev Time 0.00
Received By sgraham Date   Time   Sent To  
Notes
***NONE***