Plan Review Details - Permit 02020149
Plan Review Stops For Permit 02020149
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2002-02-11 Cont ID  
Sent By btrobaug Date 2002-02-11 Time 12:58 Rev Time 0.00
Received By btrobaug Date 2002-02-11 Time 12:35 Sent To M
Notes
2002-02-11 00:00:00PLEASE PROVIDE THE FOLLOWING FOR
 ELECTRICAL REVIEW:
  
 1)LOAD CALCULATIONS OF THE PANEL FEEDING
 THE NEW A/C SYSTEM.
  
 2)DRAWING WITH CONDUIT & WIRE SIZE TO
 NEW UNITS.
  
 3)SHOW GFI AT CONDESING UNIT PER 309.2
 MECHANICAL CODE.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 (561) 659-8096
 EXT 8392