Plan Review Details - Permit 02020138
Plan Review Stops For Permit 02020138
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2002-04-08 Cont ID  
Sent By jgomez Date 2002-04-08 Time 09:26 Rev Time 1.00
Received By jgomez Date 2002-04-08 Time 09:26 Sent To  
Notes
2002-04-08 00:00:00APPROVED WITH PROVISO:
 1-APPLY FOR SEPARATE PERMIT FOR A/C
 WORK.
 2-STORM SHUTTERS WILL BE REQUIRED IF
 GLASS REPLACEMENT IS MORE THAN 50%
 OF THE HOUSE.
 SBC 1997 AS AMENDED BY THE CITY
 SECTIONS 103.6, 1606.4 AND 1707.4.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2002-02-28 Cont ID  
Sent By btrobaug Date 2002-04-04 Time 17:48 Rev Time 2.00
Received By jgomez Date 2002-02-28 Time 12:00 Sent To  
Notes
2002-02-28 00:00:00CHECKLIST:
 1-PROVIDE CLEAR DRAWINGS AND SPECS.
 SHOWING FULL SCOPE OF WORK. CLEARLY
 INDICATE ALL EXTERIOR DOORS & WINDOWS
 THAT ARE REPLACED OR NEW. SPECIFY SIZE
 & TYPE OF WINDOWS TO CHECK FOR EGRESS
 REQUIREMENTS AND STORM SHUTTER POLICY.
 2-ACCORDING TO THE PLANS PRESENTED, IT
 LOOKS LIKE A BEARING WALL IS GOING TO
 BE DEMOLISHED AND NEW BEAM WILL BE
 INSTALLED. PROVIDE COMPLETE STRUCTURAL
 DESIGN INFORMATION BASED ON SSTD 10-97
 OR PROFESSIONAL ENGINEER TO PROVIDE
 THE STRUCTURAL DESIGN.
 -PROVIDE COMPLETE STRUCTURAL DETAILS
 AND SPECS SHOWING BEAM SIZE, CONNECTOR
 AT BOTH ENDS, TOP & BOTTOM CONNECTORS.
 -SPECIFY COLUMNS AT THE ENDS OF BEAM &
 HOW IS THE LOAD TRANSFERRED TO THE
 FOUNDATION. SPECIFY SIZE OF FOOTING.
 SEC. 104.2 CITY AMENDMENTS TO SBC 1997
 3-PROVIDE COMPLETE FRAMING DETAILS FOR
 NEW EXTERIOR DOORS AND WINDOWS.
 SPECIFY ALL FASTENERS. SEE SSTD 10-97
 4-ALL INFORMATION, DRAWINGS, SPECS SHALL
 BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 SEC. 104.2.1 CITY AMENDMENTS TO SBC/97
 5-SEE COMMENTS BY THE OTHER TRADES.
 6-VALUE DECLARED FOR THIS PROJECT IS TOO
 LOW. PROVIDE REALISTIC MARKET VALUE
 USING MATERIALS AND LABOR. (INCLUDE
 LABOR EVEN IF DONE BY THE OWNER).

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2002-04-04 Cont ID  
Sent By btrobaug Date 2002-04-04 Time 17:48 Rev Time 0.00
Received By btrobaug Date 2002-04-04 Time 12:56 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2002-02-11 Cont ID  
Sent By dpalmer Date 2002-02-11 Time 15:33 Rev Time 0.00
Received By dpalmer Date 2002-02-11 Time 15:33 Sent To P
Notes
2002-02-11 00:00:00******************** UNSAT *************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRENT PER 110-9.
 IS THE 200A PANEL NOTED NEW?
  
 2)NOTE: PLEASE SUBMIT A RISER DIAGRAM
 SHOWING THE NEW SERVICE AND GROUNDING
 DETAIL.
  
 3)NOTE: PLEASE NOTE THAT TWO PANEL
 SCHEDULE WERE SUBMITTED? BOTH DO NOT
 CORRELATE. PLEASE NOTE THAT FIRST ONE
 SHOWS GARAGE? PLEASE SHOW DETAIL FOR
 THE FEED TO THAT GARAGE. DETACHED???
  
 4) NOTE: PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210-8-A-6.
  
 5) NOTE: PLEASE LIST THE REQ`D BATH(S)
 CIRCUIT(S) PER 210-11-C-3.
 MUST BE 20A AND #12AWG.
  
 6)NOTE: PLEASE NOTE THAT PANEL SCHEDULE
 THAT SAYS LOAD CALCULATIONS,,,,PLEASE
 NOTE THAT THERE ARE NO LOAD CALCS
 SHOWN.
  
 7) PLEASE NOTE EITHER MISSING EGRESS
 LIGHTING AND/OR CLARIFY EGRESS LIGHTING
 PER 210-70 OF THE NEC.
 PLEASE DRAW IN SWITCH LEGS FOR ALL
 LIGHTING SWITCHES.
  
 8)NOTE: PLEASE SHOW WIRE SIZES ON PANEL
 SCHEDULES.
  
 9)NOTE: PLEASE NOTE THAT OUTLET SPACING
 ALONG KITCHEN COUNTERSPACE NEEDS TO
 MEET 210-52-C-1
  
 10)NOTE: PLEASE NOTE THAT BATH RECEPTS
 NEED TO BE SHOWN AS GFI. 210-8
  
  
 11)NOTE: PLEASE CLARIFY LOCATION OF
 PANEL AND HOW FEED IS COMING INTO HOUSE?
 PLEASE NOTE THAT PANEL IS SHOWN IN UTIL-
 -ITY ROOM AND DOES NOT MEET 110-26 FOR
 CLEARENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.\\
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2002-04-17 Cont ID  
Sent By pkrauss Date 2002-04-17 Time 11:03 Rev Time 0.35
Received By pkrauss Date 2002-04-17 Time 11:03 Sent To  
Notes
2002-04-17 00:00:00MECHANICAL PERMIT 02040745

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2002-02-21 Cont ID  
Sent By pkrauss Date 2002-02-21 Time 11:09 Rev Time 0.35
Received By pkrauss Date 2002-02-21 Time 11:08 Sent To B
Notes
2002-02-21 00:00:00 
 NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.PLEASE PROVIDE PLANS WITH
 MECHANICAL PERMIT APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT 659-8096
 EXT. 8388.

Review Stop P PLUMBING
Rev No 1 Status P Date 2002-02-20 Cont ID  
Sent By dpalmer Date 2002-03-15 Time 11:57 Rev Time 0.50
Received By kstevens Date 2002-02-20 Time 16:06 Sent To  
Notes
2002-02-20 00:00:00REVIEW UNDER SPC-94 CODE. NONE REFERENC-
 ED ON PLANS. KS

Review Stop Z ZONING
Rev No 1 Status P Date 2002-04-08 Cont ID  
Sent By jgomez Date 2002-04-08 Time 09:33 Rev Time 0.00
Received By jgomez Date 2002-04-08 Time 09:33 Sent To  
Notes
***NONE***